4.2 Specifications of R-410A:
Application: R-410A is not a drop-in replacement for R-22;
equipment designs
must accommodate its higher pressures. It cannot be retrofitted into R-22 heat
pumps.
Physical Properties:
R-410A has an atmospheric boiling point of -62.9°F and its
saturation pressure at 77°F is 224.5 psig.
Composition:
R-410A is an azeotropic mixture of 50% by weight difluoromethane
(HFC-32) and 50% by weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater
than R-22.
Recovery and recycle equipment, pumps, hoses and the like need to
have design pressure ratings appropriate for R-410A.
Manifold sets need to range
up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard.
Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need
to have a 400 psig service pressure rating.
DOT 4BA400 or DOT BW400.
Combustibility:
At pressures above 1 atmosphere, mixture of R-410A and air can
become combustible.
R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should
never be done with a mixture of R-410A and air.
Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
4.3 Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times)
than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in color.
• R-410A, as with other HFC’s is only compatible with POE oils.
10
FIGURE 3
SCREW LOCATIONS
TABLE 2
DIMENSIONS
MODEL NUMBER
L
W
A
B
C
D
(-)ASL-024/036/039/048/060
41.5
29.813
15
38
3.5
26.5