![Rheem A17 Series Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/rheem/a17-series/a17-series_installation-instructions-manual_1451478047.webp)
47
10.7 Service Analyzer Chart (cont.)
Diagnostics
ELECTRONIC EXPANSION VALVES
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
EXV feeds too
much refrigerant,
with low super
-
heat, with low
superheat and
higher than normal
suction pressure
EXV control dc circuit failed
Verify 5Vdc to pressure transducer is present, if not,
replace EXV controller
High superheat adjustment
Change the superheat offset dip switches to increase
superheat
Moisture causing valve to stick open
Recover refrigerant, replace filter-drier, evacuate system
and recharge
Dirt or foreign material causing valve to stick open Recover refrigerant, replace filter-drier, remove EXV and
purge with nitrogen, evacuate system and recharge
If EXV is completely clogged, use the EXV control to
open the EXV, and purge with nitrogen, replace filter
drier, and recharge
Oversized EXV
Install correct EXV
Incorrect suction thermistor location
Install suction thermistor with the provided stainless steel
strap and an additional zip tie between the 10:00 and
2:00 position on suction line, and insulate
Low superheat adjustment
Change the superheat offset dip switches to increase
superheat
Incorrect sensing suction line temperature
Verify suction thermistor resistance is correct and proper
-
ly attached and insulated to the suction line
Suction thermistor incorrectly calibrated
Replace suction thermistor assembly
Suction pressure measured incorrectly
After verifying lack of connectivity, replace the pressure
transducer or harness
If harness has a short, replace harness
If gauge pressure measurement and the converted volt
-
age readings at the control are different replace pressure
transducer
If gauge pressure measurement and the converted
voltage readings at the control are the same, replace the
control
Compressor flood
back upon start-up
Refrigerant drained from flooded evaporator
Install trap riser to the top of the elevator coil
Inoperable crankcase heater or crankcase heater
needed
Replace or add crankcase heater
Any of the causes listed under symptoms of elec
-
trical problem in section 10.3
Any of the solutions listed under solutions of electrical
problems in section 10.3
Superheat is low
to normal with low
suction pressure
Unequal evaporator circuit loading
Ensure airflow is equally distributed through evaporator
Check for blocked distributor tubes
Low load or airflow entering evaporator coil
Ensure blower is moving proper air-flow
Remove/correct any airflow restriction
10.0 DIAGNOSTICS AND TROUBLESHOOTING
Содержание A17 Series
Страница 52: ...52...