10.0 DIAGNOSTICS AND TROUBLESHOOTING
10.6 General Troubleshooting Guide
Diagnostics
WARNING:
Disconnect all power to unit
before servicing. Contactor may break only one side. Failure
to shut off power can cause electrical shock resulting in per
-
sonal injury or death.
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
•
Power off or loose electrical connection
•
Thermostat out of calibration - set too high
•
Defective control board
•
Blown fuses/tripped breaker
•
Transformer defective
•
High-pressure control lock-out
•
Low-pressure control lock-out
•
Miswiring of communications (communication
light on continuously)
•
Check for correct voltage at line voltage connections in con
-
densing unit.
• Reset
•
Check control board diagnostic codes
•
Replace fuses/reset breaker
•
Check wiring. Replace transformer
•
Reset by cycling power to unit. Also see high head and low
suction pressure remedies.
•
Check for refrigerant leaks.
•
Check communication wiring.
Outdoor fan runs,
compressor doesn’t
•
Run or start capacitor defective
•
Contactor defective
•
Loose connection
•
Compressor stuck, grounded or open motor
winding, open internal overload.
•
Low-voltage condition
•
Replace
•
Replace
•
Check for the correct voltage at compressor. Check and tighten
all connections.
•
Wait at least 3 hours for overload to reset. If still open, replace
the compressor.
•
Add start kit components.
Insufficient cooling
•
Improperly sized unit
•
Improper indoor airflow
•
Incorrect refrigerant charge
•
Air, noncondensibles, or moisture in system
•
Bad ID EXV or TXV
• Recalculate load
•
Check. Should be approximately 400 CFM per ton
•
Charge per procedure attached to unit service panel
•
Recover refrigerant. Evacuate and recharge. Add filter drier
•
Replace EXV or TXV
Compressor short cycle
•
Incorrect voltage
•
Defective overload protector
•
Refrigerant undercharge or undercharge (HPC
or LPC cycling)
•
At compressor terminals, voltage must be 10% of nameplate
marking when unit is operating.
•
Replace. Check for correct voltage
•
Add refrigerant
Registers sweat
•
Low indoor airflow
•
Increase speed of blower or reduce restriction.
•
Replace air filter.
High head, low suction
pressure
•
Restriction in liquid line, expansion device, or
filter drier
•
Bad EXV or TXV
•
Remove or replace defective component.
•
Verify thermistor and pressure transducer connection and
operation
•
Replace EXV or TXV
High head, high or normal
suction pressure - Cooling
mode
•
Dirty outdoor coil
•
Refrigerant overcharge
•
Outdoor fan not running
• Air or noncondensibles in system
• Clean coil
• Correct system charge
•
Repair or replace
•
Recover refrigerant. Evacuate and recharge
Low head, high suction
pressure
•
EXV in bypass mode or TXV Check valve
stuck open
•
Bad compressor
•
Verify thermistor and pressure transducer connection and
operation
•
Replace EXV or TXV
•
Replace compressor
Low suction, cool com
-
pressor, iced indoor coil
•
Low indoor airflow
•
Operating below 65oF outdoors
•
Moisture in system
• Restricted indoor coil circuit
•
Increase speed of blower or reduce restriction. Replace air filter
•
Add Low Ambient Kit
•
Recover refrigerant. Evacuate and recharge. Add filter drier
•
Repair or replace indoor coil
High suction pressure
•
Excessive load
•
Defective compressor
•
Recheck load calculation
•
Replace
Fluctuating head and
suction pressure
•
EXV or TXV hunting
• Air or noncondensibles in system
•
Check thermistor to suction line connection
•
Check air distribution on coil
•
Check suction thermistor and pressure transducer and opera
-
tion
•
Recover refrigerant. Evacuate and recharge.
•
Remove and confirm EXV movement. Clean EXV inside with
nitrogen to remove any debris then reinstall
Gurgle or pulsing noise
at expansion device or
liquid line
• Air or noncondensibles in system
•
Undercharged System
•
Recover refrigerant. Evacuate and recharge
•
Adjust charge per charging chart