TM017 Rheem Air Sourced Heat Pump Service Instructions REV: C
Date of Issue: 5/11/05
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
3
Specifications
Water Heater
Model
55027500
55127507
Capacity - Litres
275
275
Boost Capacity - Litres
0
130
Booster element rating - kW
Not fitted
2.4 or 3.6
T&PR valve Rating - kPa
1000
1000
With ECV
680
680
Maximum inlet pressure - kPa
Without ECV
800
800
Inlet / Outlet
RP¾/20
RP¾/20
Water Connections
T&PR RP½/15
RP½/15
Quantity 2
2
Anode
Length 1153
1153
Compressor t/stat setting (fixed) - ºC
49ºC*
55ºC*
Booster thermostat setting (trade adjustable) - ºC
Not fitted
60ºC
Booster ECO setting - ºC
N/A
85ºC
*Delivered water temperature 65-75ºC
Refrigeration System
Parameter 55027500
55127507
Superheat setting (Factory)
+3ºC at 10ºC Evaporator temp.
Compressor ECO setting
105ºC, manual reset
R22 1350
grams
Refrigerant charge
R409A 1250
grams
Bypass solenoid coil resistance
2 kilo-ohms @ 20ºC
Not fitted
Capacitor
25 microfarads 370/450 VAC 50/60HZ
Fan motor winding resistance
47.2 ohms at 20ºC
Closed
–3.5ºC
De-ice thermostat
Open
3ºC +/- 1.5ºC
Not fitted
Closed 7ºC +/- 1.5ºC
Evaporator thermostat
Not fitted
Open –3.5ºC evap temp
Compressor winding resistance
Run winding - Red & Blue: 3.33 ohms
Start winding - Red & Black: 6.01 ohms at 20ºC
Preventative Maintenance
It is suggested for peak performance that the water heater be serviced annually.
1. Check for discharge from the T&PR valve. When the elements are operating a small
discharge of water may be evident. Operate the valve-easing lever to ensure the valve
opens and resets properly. Always open and close the valve gently. The T& PR valve
should be replaced at 5 yearly intervals.
2. Check for leaks at all cylinder fittings.
3. Check for signs of excessive corrosion on the water heater jacket.
4.
Isolate power
to the water heater and check all electrical connections for signs of
overheating due to poor connection.
5. Conduct an 'Electrical insulation test' on the water heater. (Refer to page 30)
6. Check evaporator fins and fan blade for build up of dust or debris.
7. Check for sludge build up and if necessary drain and flush tank.