CONNECTIONS – PLUMBING 

35 

RELIEF VALVE DRAIN 

DN15 copper drain lines must be fitted to the temperature pressure relief valve 
and expansion control valve (if one is installed) to carry the discharge clear of 
the  water  heater.  Connect  the  drain  lines  to  the  valves  using  disconnection 
unions. The drain line from the valve to the point of discharge should be as short 
as  possible,  have  a  continuous  fall  all  the  way  from  the  water  heater  to  the 
discharge outlet and have no tap, valves or other restrictions in the pipe work. A 
drain  line  from  a  relief  valve  must  comply  with  the  requirements  of 
AS/NZS 3500.4 and Clause G12 of the New Zealand Building Code. 
 
The length of the drain line in metres plus the number of changes in direction 
must not exceed twelve (12). For example a drain line nine (9) metres in length 
can have no more than three bends before discharging at an outlet or air gap. 
The length of a drain line is to be reduced by one (1) metre for each additional 
bend required. Where the distance in metres and number of changes in direction 
to the point of final discharge exceeds twelve (12), the drain line can discharge 
into a tundish. 
 
In New Zealand the drain lines from the temperature pressure relief valve and 
expansion control valve from an individual water heater may be interconnected 
where  freezing  is  unlikely  to  occur.  The  combined  drain  line  must  have  a 
minimum  size  of  DN20  and  discharge  via  a  minimum  air  gap  of  a  minimum 
25 mm. 
 
The outlet of a drain line must be in such a position that flow out of the pipe can 
be  easily  seen,  but  arranged  so  discharge  will  not  cause  injury,  damage  or 
nuisance. The termination point of a drain line must comply with the requirements 
of AS/NZS 3500.4. Drain lines must not discharge into a safe tray. 
 
In  locations  where  water  pipes  are  prone  to  freezing,  drain  lines  must  be 
insulated, must not exceed 100 mm in length and are to discharge into a tundish 
through an air gap of a minimum 25 mm. 
 
If a drain line discharges into a tundish, the drain line from the tundish must be 
not less than DN20 and one size larger than drain line from the relief valve(s). 
The drain line from a tundish must meet the same requirements as for a drain 
line from a relief valve. 
 

  Warning:

  As  the  function  of  the  temperature  pressure  relief  valve  on  this 

water heater is to discharge high temperature water under certain conditions, it 
is  strongly  recommended  the  pipe  work  downstream  of  the  relief  valve  be 
capable  of  carrying  water  exceeding  93°C.  Failure  to  observe  this  precaution 
may result in damage to pipe work and property. 
 

Содержание 31202519V

Страница 1: ...s water heater must be installed and serviced by a qualified person Please leave this guide with the householder Owner s Guide and Installation Instructions Electric Domestic Water Heater Model 312025...

Страница 2: ...Zealand Limited TRADEMARKS Registered trademark of Rheem Australia Pty Ltd or Rheem New Zealand Limited TM Trademark of Rheem Australia Pty Ltd or Rheem New Zealand Limited Note Every care has been ta...

Страница 3: ...the terms of the Rheem warranty on pages 4 to 7 The other pages are intended for the installer but may be of interest Warranty 4 Safety Warnings Installation Notes 8 About Your Water Heater 12 Mainten...

Страница 4: ...om 1st November 2019 1 5 If a subsequent version of this warranty is published the terms of that warranty and what is covered by it will apply to water heaters manufactured after the date specified in...

Страница 5: ...missions b Misuse or abnormal use of the unit c Installation or use not in accordance with the Owner s Guide and Installation Instructions New Zealand Building Code requirements or with relevant statu...

Страница 6: ...process of production or manufacture or repairing or treating in trade other goods or fixtures on land 3 WHAT IS COVERED BY THE RHEEM WARRANTY FOR THE WATER HEATERS DETAILED IN THIS DOCUMENT 3 1 Rheem...

Страница 7: ...ation of the unit or if that s unavailable the date of manufacture and serial number from the rating label on the unit b A Rheem Service Centre will arrange for the unit to be tested and assessed on s...

Страница 8: ...ces must not be tampered with or removed The water heater must not be operated unless each of these devices is fitted and is in working order The Rheem warranty may not cover faults if relief valves o...

Страница 9: ...sion control valve is fitted to the cold water line to the water heater to comply with Clause G12 of the New Zealand Building Code unless the water heater is installed as a push through installation T...

Страница 10: ...one your Rheem Service Centre to arrange for an inspection The temperature pressure relief valve should be replaced at intervals not exceeding five 5 years and the expansion control valve should be ch...

Страница 11: ...l local codes and regulatory authority requirements Installation and commissioning requirements and details for the installing plumber and licensed electrical worker are contained on pages 24 to 38 Ma...

Страница 12: ...esperson adjustable thermostat which allows you to choose the most suitable temperature for your hot water needs Refer to Temperature Adjustment on page 13 To meet the requirements of the New Zealand...

Страница 13: ...rical worker adjust the thermostat to the lowest temperature setting that meets your needs especially if there are young children or elderly people in your home Refer to Hotter Water Increases The Ris...

Страница 14: ...more than a few nights conserve energy by switching the water heater off at either the switchboard or isolating switch if one is installed Note When the electrical supply is switched back on the wate...

Страница 15: ...llowing actions Replace the temperature pressure relief valve Inspect and flush the expansion control valve if fitted If required replace the valve Inspect and if required replace the anode If the ano...

Страница 16: ...ised and lowered gently Refer to Relief Valves on page 9 Warning Water discharged from the temperature pressure relief valve drain line will be hot Exercise care to avoid any splashing of water by sta...

Страница 17: ...valve and a heating unit Where there is a changeover from one water supply to another e g a rainwater tank supply bore water supply desalinated water supply public reticulated water supply or water br...

Страница 18: ...page 15 then the maximum time after installation when the anode should be replaced for this water heater is ten 10 years CAUTION If the water supply has a TDS greater than 600 mg L there is the possi...

Страница 19: ...to the temperature pressure relief valve and water heater cylinder Where the saturation index exceeds 0 80 the Rheem warranty does not apply to a standard watts density heating unit A low watts densi...

Страница 20: ...l not cover any resultant faults on the components listed below Water Chemistry Component Total Dissolved Solids TDS 600 mg L black colour coded anode installed water heater cylinder Total Dissolved S...

Страница 21: ...t is not realised the amount of hot water used Carefully review the family s hot water usage Have a plumber fit a flow control valve to each outlet to reduce water usage Relief valve running Is the re...

Страница 22: ...s cooler This valve is installed in the cold water line to the water heater refer to the cold water connection diagram on page 32 Continuous dribble Try gently raising the easing lever on the relief v...

Страница 23: ...surprising quantity of hot water and electricity Replace faulty tap washers and have a plumber rectify any leaking pipe work Has there been an increase in hot water usage An increase in hot water usag...

Страница 24: ...ly domestic dwelling for the purpose of heating potable water Its use in an application other than this may shorten its life If this water heater is to be used where an uninterrupted hot water supply...

Страница 25: ...rrier should be used between the two surfaces in this instance The barrier should extend at least 100 mm from the water heater and may be trimmed after two months Remember all local authorities have r...

Страница 26: ...ts the water temperature delivery requirements of Clause G12 of the New Zealand Building Code so that heated water delivered to sanitary fixtures and appliances used primarily for personal hygiene is...

Страница 27: ...Limiting Device A temperature limiting device cannot be installed in circulated hot water flow and return pipe work The tempered water from a temperature limiting device cannot be circulated Where a...

Страница 28: ...his model must be fitted to the water heater REDUCING HEAT LOSSES The cold water line to and the hot water line from the water heater must be insulated in accordance with the requirements of Clauses G...

Страница 29: ...g long periods of no use In areas where this is likely to occur the installer should instruct the householder on how to dissipate the gas safely refer to Caution on page 18 SADDLING PIPE WORK To preve...

Страница 30: ...INSTALLATION 30 TYPICAL INSTALLATION INDOOR LOCATION TYPICAL INSTALLATION OUTDOOR LOCATION...

Страница 31: ...Model Storage Capacity TPR Valve Setting Approx Weight empty 31202519V 25 litres 1000 kPa 16 kg This model is suitable for either indoor or outdoor installation The 312025 model has left hand LH wate...

Страница 32: ...ater All olive compression fittings must use brass or copper olives Use an approved thread sealant such as Teflon tape on all sealing threads An isolation valve and non return valve must be installed...

Страница 33: ...fitted before the water heater is operated Before fitting the relief valve make sure the probe has not been bent To fit the relief valve Seal the thread with an approved thread sealant such as Teflon...

Страница 34: ...lause G12 of the New Zealand Building Code unless the water heater is installed as a push through installation refer to Push Through Free Outlet Installation on page 28 The expansion control valve mus...

Страница 35: ...temperature pressure relief valve and expansion control valve from an individual water heater may be interconnected where freezing is unlikely to occur The combined drain line must have a minimum siz...

Страница 36: ...water heater The conduit is to be connected to the unit with a 20 mm terminator Connect the power supply wires directly to the terminal block and earth tab connection ensuring there are no excess wir...

Страница 37: ...CONNECTIONS ELECTRICAL 37 WIRING DIAGRAM SINGLE ELEMENT ELECTRIC WATER HEATERS Electrical Circuit for Single Element Models Robertshaw ST Thermostat...

Страница 38: ...the easing lever on the temperature pressure relief valve to check the smooth operation of the valve plunger and that water discharges freely from the drain line It is very important the lever is rais...

Страница 39: ...t the lever snap back or you will damage the valve seat It is very important the lever is raised and lowered gently Operating the lever will release the pressure in the water heater Undo the union at...

Страница 40: ...Revision Date 2021 July 122283C 40...

Отзывы: