Installing the water heater.

Combustion and Ventilation Air

Proper operation of the water heater 
requires air for combustion and 
ventilation. Provisions for combustion 
and ventilation air must comply with 
referenced codes and standards.

When installed in a closet, DO NOT block 
or obstruct any of the combustion air inlet 
openings located around the perimeter 
of the water heater.  A minimum of 1” is 
required between these combustion air inlet 
openings and any obstruction.

NOTICE: If the water heater is installed 
in an unconfined space within a building 
of conventional frame, masonry or metal 
construction, infiltration air is normally 
adequate for proper combustion and 
ventilation. If the water heater is installed in 
a confined space, provisions for combustion 
and ventilation air must be made.

A confined space is one having a volume 
of less than 50 cubic feet per 1000 Btuh 
of the aggregate input of all appliances 
within that space. 

The air must be supplied through two 
permanent openings of equal area. One 
is to be located within 12” above the floor 
and the other is to be located within 12” 
from the ceiling.

T

he minimum net free area of each opening 

must not be less than one square inch 
per 1000 Btuh of the total input rating 
of all the appliances in the enclosure 

(but not less than 100 square inches), if 
each opening communicates with other 
unconfined areas inside the building.

Buildings of unusually tight construction 
shall have the combustion and ventilation 
air supplied from outdoors, or a freely 
ventilated attic or crawl space.

If air is supplied from outdoors, directly or 
through vertical ducts, there must be two 
openings located as specified above and 
each must have a minimum net free area 
of not less than one square inch per 4000 
Btuh of the total input rating of all the 
appliances in the enclosure.

If horizontal ducts are used to 
communicate with the outdoors, each 
opening must have a minimum net free 
area of not less than one square inch per 
2000 Btuh of the total input rating of all 
the appliances in the enclosure. If ducts 
are used, the minimum dimensions of 
rectangular air ducts shall not be less than 
3”.

NOTICE: If the duct openings which supply 
combustion and ventilation air are to be 
covered with a protective screen or grill, 
the net free area (openings in the material) 
of the covering material must be used 
in determining the size of the openings. 
Protective screening for the openings MUST 
NOT be smaller than 1/4”mesh to prevent 
clogging by lint or other debris.

Corrosive Atmospheres

The air in beauty shops, dry cleaning 
establishments, photo processing 
labs,  and storage areas for liquid and 
powdered bleaches or swimming pool 
chemicals often contain such halogenated 
hydrocarbons.

An air supply containing halogenated 
hydrocarbons may be safe to breathe, 
but when it passes through a gas flame 
corrosive elements are released that 
will shorten the life of any gas burning 
appliance.

Propellants from common spray cans 
or gas leaks from A/C and refrigeration 
equipment are highly corrosive after 
passing through a flame.

The water heater warranty is voided when 
failure of the heater is due to operation in 
a corrosive atmosphere.

NOTICE: The water heater 
should not be installed near 
an air supply containing 
halogenated hydrocarbons.

Inspect Shipment

Inspect the water heater for possible damage. Check the markings on the rating plate of 
the water heater to be certain the type of gas supplied corresponds to the water heater 
requirements.

Содержание 30 Gallon

Страница 1: ...the proper installation and adjustment of the water heater and two for the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This...

Страница 2: ...of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips first you may not need to call for service READ THIS MANU...

Страница 3: ...nt system for proper installation at initial start up and at least annually thereafter Refer to the Care and Cleaning section of this manual for more information regarding vent system inspection DANGE...

Страница 4: ...5 minutes 125 F 11 2 to 2 minutes 130 F About 30 seconds 135 F About 10 seconds 140 F Less than 5 seconds 145 F Less than 3 seconds 150 F About 11 2 seconds 155 F About 1 second Table courtesy of Shr...

Страница 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Страница 6: ...installation For residential water heaters of a capacity greater than 52 gallons consult the local building jurisdiction for acceptable bracing procedures Have the installer show you the location of t...

Страница 7: ...ilot or main burner can ignite these vapors and create a shut down condition of the water heater which will not allow the water heater to ignite until examined by a Qualified Service Technician The wa...

Страница 8: ...located as specified above and each must have a minimum net free area of not less than one square inch per 4000 Btuh of the total input rating of all the appliances in the enclosure If horizontal duc...

Страница 9: ...reby relieving the over pressure condition and eliminating the repeated operation of the relief valve Other methods of controlling thermal expansion are also available Contact your installing contract...

Страница 10: ...e end of the discharge line should not be threaded or concealed and should be protected from freezing No valve of any type restriction or reducer coupling should be installed in the discharge line To...

Страница 11: ...er must be isolated from the gas piping system by closing the manual gas shut off valve during any pressure testing of the gas supply piping at pressures equal to or less than 3 8 psi 10 5 w c for nat...

Страница 12: ...y saving devices may shorten the life of the water heater and may endanger life and property The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauth...

Страница 13: ...ter heater jacket DON T remove the Burner Access Door unless absolutely necessary This should only be done by a qualified service technician A new burner access door gasket must be installed on any bu...

Страница 14: ...tion air inlet openings observed see page 7 Water heater completely filled with water Air purged from water heater and piping Water connections tight and free of leaks Gas line equipped with shut off...

Страница 15: ...ng unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating units Refer to the installation instructions supplied with...

Страница 16: ...ual Failure to do so can result in unsafe operation of the water heater resulting in property damage personal injury or death Should you have any problems reading or following the instructions in this...

Страница 17: ...MMABLE To dissipate such gas and to reduce risk of injury it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected...

Страница 18: ...t Therefore always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Also always supervise young children or others who...

Страница 19: ...plumbing contractor on how to correct this DO NOT plug the relief valve outlet A water heater s tank can act as a settling basin for solids suspended in the water It is therefore not uncommon for hard...

Страница 20: ...r cleaning remove the burner from the water heater A vacuum cleaner can be used on the burner and floor shield inside the water heater The burner can also be cleaned by scrubbing with mild detergent P...

Страница 21: ...he water heater requires air for ventilation air supplied to combustion and ventilation See the Combustion and the water heater location Ventilation Air information in the Installing The Water Heater...

Страница 22: ...ighting The Water Heater section of this manual The gas control thermostat z See the Water Temperature Setting of The Water may be set too low Heater section of this manual Leaking or open hot z Make...

Страница 23: ...thermostat burners vent connectors or other safety devices Refer repairs to qualified service personnel Draft hood Flue baffle and hanger Anode rod Heat Trap Heat Trap Nipple Nipple Dip tube Dip tube...

Страница 24: ...Drive East Montgomery Alabama 36109 1413 Phone 1 800 432 8373 When contacting the manufacturer the following information will be requested a Model and serial number of the water heater as shown on the...

Отзывы: