INSTALLATION AND OPERATION INSTRUCTIONS
1-16
TANKLESS WATER HEATER 199
Concentric Side Wall Termination Kits
Concentric Sidewall Termination kits approved for use with the tankless water
heater are subject to restrictions. NOTE: Some jurisdictions may not allow this
type of sidewall termination due to close proximity to the neighboring properties.
You must follow the installation instructions, clearances, and wall thickness
requirements of the approved vent termination manufacturer.
Approved Concentric Sidewall Termination kits are:
•
3" PVC (UL 1738) – Ipex #397006
•
3" PVC (ULC-S636) – Ipex #196006
•
3" CPVC (ULC-S636) – Ipex #197009
•
2" Centrotherm Innoflue PPs - #ICWT242 (Termination)
#ICTCR24 (2 Pipe Adapter)
•
3" Centrotherm Innoflue PPs - #ICWT352 (Termination)
#ICCT3503 (2 Pipe Adapter)
Installation of multiple Concentric Side Wall Termination kits must be:
•
On the same horizontal line (not stacked)
•
With a minimum horizontal separation of 12" center to center
12" + Allowance
for Snow Level
Figure 17: Horizontal Polypropylene Concentric Termination - Two Kits
Figure 18: Horizontal Polypropylene Concentric Termination - Single Kit