TM090 12-26 Series II CFGWH Service Instructions
REV AB
– Issued February 2019
This document is stored and maintained electronically by Rheem Technical Support. All printed copies
are deemed “uncontrolled”
40
Fault Finding Chart 2
System Not Ready
YES
Check for damage in the combustion
chamber. If no damage present, replace
over temperature limiter and check
minimum and maximum burner pressures
NO
Overheating
NO
Test 2
Replace the PCB assembly.
YES
Replace the remote controller cable.
YES
Duplicate remote controller fitted. Up to 3
remotes can be fitted but can only be one
of each type of controller (K, B1, B2).
NO
Communication
failure
NO
Fan detecting
circuit failure
YES
*Refit connector L
and restore power.
NO
* WARNING
Disconnect power prior to
removing or inserting
connector plugs
Replace the fan motor.
Error code due to supply voltage drop.
NO
Replace the PCB assembly.
YES
NO
Remove and reinsert
the gas type
connector.
YES
Gas type connector was originally not
inserted correctly.
Faulty gas type connector - replace.
YES
NO
Gas type connector
malfunction
2
YES
*Remove connector L
from the fan motor and
restore power
Test 16
Test 10
Test 6
NO
NO
Replace the lower gas burner assy
assembly.
NO
Replace the GIS valve assembly.
YES
YES
Replace the heat exchange thermistor.
Is the
resistance of the over
temp limiter normal?
Is the voltage and
resistance of S1,S2, S3
normal?
Is voltage and resistance
of GISV normal?
Is the voltage and
resistance of
heat exchange
thermistor normal?
YES
NO
Is the remote
controller cable
open circuit?
YES
NO
Is error code 14
displayed?
Is error code 71
displayed?
Is error code 76
displayed?
Is error code 79
displayed?
Is error code 82
displayed?
Is error code 82
redisplayed?
Is error code 79
redisplayed?
Is error code 79
redisplayed?
NO
YES
Replace the PCB assembly.
Replace the PCB assembly.
NO
Has the fan the
correct voltage?
Is gas type
connector fitted?
YES
Gas type connector must be
connected. Locate GTC within
heater cabinet and insert.
NO