23

7.  CONTROLS

ROLL-OUT 

SWITCH

TEMP SENSOR 

HL1 - HIGH LIMIT

HL2 - HIGH LIMIT

T&P 

GAUGE

FLOW 

SWITCH

PROTEK 

SHIELD 

ASSY

PRV

GAS 

VALVE

CONTROL 

BEZEL

F10640-6

Figure 27.  Location of Controls (View One)

F10640-3

DRAIN 

PLUG IN 

REAR 

HEADER

PILOT

Figure 28.  Location of Controls (View Two)

Control Panel Removal

1.  Remove  screw  from  front  door.  Set  aside  door  for 

serviceability.

2.  Remove four (4) screws from sides of control panel.
3.  Rotate control panel down until panel stops. Do not 

force.

NOTE:

 Caution must be used to not damage controls 

or wiring.

F10646-9

KNURLED 

SCREW

Figure 29.  Knurled Screw Location

Control Adjustments

The  pool  heater  touch-pad,  located  on  the  upper  front 

panel of the heater, allows the user to select either POOL 

or SPA operation, and to adjust the setpoint temperature. 

The LCD display window indicates the mode (OFF, SPA, 

POOL) and the actual water temperature. A manual power 

switch  provided  below  the  touch-pad  turns  the  control 

power ON or OFF. See 

Figure 30.

TEMP

MODE

ON

OFF

LCD DISPLAY

TEMP ADJUST BUTTONS

MODE BUTTON

Figure 30.  Control Adjustment

Mode Button

The MODE button is used to select POOL or SPA operation. 

It also allows the user to turn the heater off electronically,  

allowing  the  LCD  to  remain  energized  and  to  continue 

showing the actual water temperature.

Temp Buttons

If the heater is in POOL or SPA mode, the desired water 

temperature  (SETPOINT)  will  be  displayed  and  may  be 

adjusted using the UP or DOWN buttons. 

Содержание 013731

Страница 1: ...gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do...

Страница 2: ...2 WC Max 13 WC Sediment trap is required for all installations See page 14 WATER CHEMISTRY Water chemistry requirements See page 5 POWER Supply voltage See page 21 for acceptable input voltages VENTIN...

Страница 3: ...xternal Auxiliary Bypass Valve page 17 Auxiliary Bypass Valve Adjustment page 17 Pressure Relief Valve Installation page 18 Heat Exchanger Reversal page 18 Plumbing Diagrams page 19 5 ELECTRICAL WIRIN...

Страница 4: ...hich could cause severe personal injury death or substantial property damage if ignored ACAUTION Indicates the presence of hazards or unsafe practices which could cause minor personal injury or produc...

Страница 5: ...0 ppm 2 WATER CHEMISTRY Chemical imbalance can cause severe damage to your heater and associated equipment Maintain your water chemistry according to Table A If the mineral content and dissolved solid...

Страница 6: ...rs are design certified and tested under the latest requirements of the ANSI Z21 56 CSA 4 7 Standard for Gas Fired Pool Heaters All heaters can be used either indoor or outdoors when appropriate venti...

Страница 7: ...fix the equipment nor attempt repairs according to these instructions AWARNING Improper installation adjustment alteration service or maintenance may damage the equipment creating a hazard resulting i...

Страница 8: ...d g 0 024 sheet metal with ventilated air space over 0 024 sheet metal with ventilated air space Back 4 102 Right 4 102 Left 4 102 Vent 3 76 Indoor Top 24 610 Outdoor Top Unobstructed h 1 25 mm glass...

Страница 9: ...eater to an inside corner wall for proper outdoor venting Pagoda Top Installation 1 Insert tabs into keyhole 4 places See Figure 4 detail A 2 Snap tabs into keyholes so as not to pull out See Figure 4...

Страница 10: ...Ea Pallet Anchor Bracket Use hole closest to unit 4 total 1 1 4 x 2 1 4 S S Tapcon Bolt Washer Field Supplied Ea Pallet Anchor Bracket Use hole closest to unit 4 total 2 x 6 x 1 8 Pallet Anchor Bracke...

Страница 11: ...lation air The minimum requirements are listed in the latest edition of the National Fuel Gas Code U S ANSI Z223 1 or Canada CAN CSA B149 and any local codes that may have jurisdiction The most common...

Страница 12: ...eat Exchanger Shipping Weights lbs kg Heater Mode BTUH Input kwh A Cabinet Width in mm B Flue Dia in mm C Indoor Drafthood in mm D in mm J in mm Gas Conn in Water Conn in ASME Heater w Stackless Top I...

Страница 13: ...ll be at least 5 1 5 m in vertical height above the drafthood outlet The vent cap location shall have a minimum clearance of 4 1 2 m horizontally from and in no case below unless a 4 1 2 m horizontal...

Страница 14: ...use open flame Supply Pressure ACAUTION Do not use Teflon tape on gas line pipe thread Only sealant tape or a pipe compound rated for use with natural and propane gases is recommended Apply sparingly...

Страница 15: ...vity 0 5 in WC Pressure Drop Propane Gas 2500 BTU FT3 1 53 Specific Gravity 0 5 in WC Pressure Drop Model 3 4 1 1 1 4 1 1 2 N P N P N P N P 268A 15 4 6 35 10 7 50 15 2 125 38 1 210 64 0 480 146 3 445...

Страница 16: ...is shipped loose in the accessory carton for field installation This component provides protection to the heat exchanger against galvanic corrosion when properly bonded to the heat exchanger It should...

Страница 17: ...ASSY BYPASS DISC SPRING YELLOW COLOR 268A GREEN COLOR 408A Figure 19 Internal Automatic Bypass Valve Bronze NOTE The Unitherm Governor and Bypass Valve Assy are not individually replaced components I...

Страница 18: ...e and operate properly It must therefore be installed downstream of the discharge side of the filter pump See Figure 22 and Figure 23 A typical installation is plumbed as follows 1 The inlet side of t...

Страница 19: ...IPING SYSTEM BY A PROFESSIONAL ENGINEER Figure 22 Single Pool Heater Installation THIS DIAGRAM IS A RECOMMENDATION AND IS NOT INTENDED TO REPACE AN ENGINEERED PIPING SYSTEM BY A PROFESSIONAL ENGINEER...

Страница 20: ...er 9 Re install P6 connector ground wires SPG transformer junction box front door and plug right side with the left side s grommet plug NOTE 7 8 diameter holes not utilized on jacket and control box c...

Страница 21: ...2 RED RED BLACK HOT HOT BLACK GREEN GREEN WHITE SUPPLY SIDE Figure 26 240 VAC Wire Connection Heater must be electrically grounded and bonded in accordance with local codes or in the absence of local...

Страница 22: ...22 6 WIRING DIAGRAM...

Страница 23: ...l heater touch pad located on the upper front panel of the heater allows the user to select either POOL or SPA operation and to adjust the setpoint temperature The LCD display window indicates the mod...

Страница 24: ...Strength Indicator Press the DOWN button The Supply Voltage screen indicates the voltage supplied to the control board Normal readings range from 24 to 29 volts Figure 34 Supply Voltage Indicator Pres...

Страница 25: ...red value The control can be set for a maximum of 107 F 42 C Pool Max Temp Pool Setpoint Maximum Adjustment Refer to step one above access into the program screen Press the MODE button until POOL MAX...

Страница 26: ...Faults The following conditions are displayed only while there is a demand for heat present Display Condition Water Sw Open Water pressure switch open Vent Field Sw 1 Vent spill switch field switch 1...

Страница 27: ...igure 39 Remote Control Menu Remote Operation Activating the Remote To activate or deactivate the remote function 1 Press and hold the UP and DOWN arrow buttons for 3 to 5 seconds The second line of t...

Страница 28: ...nstall the 7 Pin Remote Interface Harness to the P8 connector and turn power ON to the heater See Figure 422 For activation of the remote control see section on page 27 3 Wire Remote Control Using Thr...

Страница 29: ...i e orange to orange and orange black to orange black No further adjustment is needed Figure 44 Water Flow Switch Assembly NOTE The sheet metal cover should be in place at all times to protect the fl...

Страница 30: ...ean with a wire brush 4 Orifices usually do not need to be replaced To clean run either copper wire or wood toothpick through orifice Do not enlarge hole To remove orifice use a socket wrench and remo...

Страница 31: ...om heat exchanger stud 5 Remove heat exchanger from the heater and wash with a garden hose making sure soot is removed from spaces between fins 6 Reverse above procedure to reinstall NOTE In extreme c...

Страница 32: ...and Off See Section 7 for additional details about the use of the controls in the Control Adjustments subsection After Start Up Feel the inlet and outlet pipes Outlet pipe should be only slightly warm...

Страница 33: ...ead the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electrical power to the appliance 4 This appliance is equipped with an ignition device which automatically li...

Страница 34: ...er is dirty look to see if the filter pressure is higher than usual 4 The pump may have lost its prime and be running dry Check the pressure on the filter If there is no pressure then you are not movi...

Страница 35: ...ntinuously Dirty filter Clean or replace filter Low water level in pool Raise water level External bypass setting out of adjustment Adjust bypass Pressure switch out of adjustment Adjust pressure swit...

Страница 36: ...eather Filter not running long enough Reset time clock Dirty filter Clean filter Gas line or meter undersized Refer to installation instructions Leaking at heat exchanger Overacid Replace heat exchang...

Страница 37: ...PC board and pilot operator on gas control Check for 24 VAC across PV MV PV terminals on PC board If voltage is okay replace gas control if not replace PC board NOTE If PC board goes into lockout res...

Страница 38: ...15 21 27 32 38 41 Resistance k 261 1 199 0 153 1 118 8 93 0 73 3 58 3 51 0 If okay replace Circuit Board Sensor Failure Inspect thermistor wires and connector at Terminal P1 Check resistance value of...

Страница 39: ...ent under standard company warranties must be properly tagged with a return parts tag completely filled in with the heater serial number model number etc and shipped to the Company freight prepaid If...

Страница 40: ...ARTS LIST 12 M 8 S 3 S 8 M 7 M 2 J 1 G 10 S 1 B 5 B 4 B 3 B 1 M 2 B 16 M 1 J 7 S 1 R 6 M 4 C 3 C 11 S 17 HM 4 S 1 V 4 V 2 V 3 V 1 S 12 S 2 S 5 HM 2 HM 3 R 6 HM 9 M 3 HM 14 M 2 R 5 S 6 S 4 HM 14 S 4 S...

Страница 41: ...20 M 21 M 19 M 2 HM FOR UNITS PRIOR TO 12 2019 16 HM 15 HM 12 HM 9 HM 10 HM 2 C 6 M 11 HM 8 HM 3 C 6 C 5 HM 17 HM 14 HM 13 HM 2 HM 4 HM 7 HM 3 HM 6 HM 2 S 9 S 4 S 18 HM 24 M 24 M 6 C 19 M 23 M OUTLET...

Страница 42: ...9 P HONEYWELL IID ATMOSPHERIC PILOT PROTEK SHIELD ADAPTER KIT PROTEK ADAPTER AND TEXAS CODE OPTION PRIOR TO 12 2019 19 M 20 M 22 M 24 M 23 M 21 M 22 M OUTLET INLET 24 M 29 HM 27 HM 26 HM 24 M 23 M IN...

Страница 43: ...nt Units manufactured from 12 2019 006725F 006725F 2 C AGS 135 F Auto Gas Shutoff Red Epoxy Units manufactured prior to 12 2019 600892B 600892B 3 C High Limit 140 F Black Epoxy Units manufactured prio...

Страница 44: ...ain Plug Cover 005264F 005264F 19 HM Adapter CPVC 2 005393F 005393F 20 HM Sensor Adapter Digital Electronic 006714F 006714F 26 HM Adapter ProTek Shield Includes 27 HM from end of Q3 2020 018006F 01800...

Страница 45: ...d prior to 12 2019 010312F 010312F 5 S Jacket Side Panel Right 010376F 010376F 6 S Jacket Side Panel Left 010377F 010377F 7 S Jacket Rear Panel 2 Pcs 010373F 010375F 8 S Poolstat Cover Lock 009505 009...

Страница 46: ...sponding manuals on your smart device This QR Code will take you to the most current version of the manual Previous versions of manuals can be found in the document library at Raypak com P N 241452 Pr...

Страница 47: ...47 Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com NOTES...

Отзывы: