Figure 9-55. Directional Overcurrent DCB Scheme
9.14
STUB BUS PROTECTION
The stub bus protection will clear faults instantly in the stub between the breaker (line CT) and the
open line disconnect switch, with line PT on the line side of the switch. The stub bus function uses an
input from a line disconnector 89b switch together with three phase current elements set as ‘Stub bus
pickup’. When 89b is high and the current is above the set operating threshold, a trip will be generated
after the set time delay.
89b
IA
IB
T
0
Trip Stub Bus
Stub bus time delay
IC
Figure 9-56. Stub Bus Protection
August 1, 2009
9-62