11
Installation
Installation in rigid wall
The product was tested and approved in:
Range
Wall type
Sealing
Classification
200x200 mm ≤ CU4 ≤ 1200x800 mm
Rigid wall
Aerated concrete ≥ 150 mm
Fire-resistant gypsum
EI 240 (v
e
i
n
o) S - (500 Pa)
400
240
≥150
fire resistant plaster
≥Hn+100
≥Wn+100
!
TEST!
Maintenance
∎
No specific maintenance required.
∎
Schedule at least two running visual checks each year.
∎
Remove dust and all other particles before start-up.
∎
Follow the local maintenance regulations (i.e. BS9999 Annex V; NF S 61-933) and EN13306.
∎
Read the maintenance instructions on our website: https://www.rft.be/assets//PIM/DOCUMENTS/BROCHURE%20KITS/BRO_K139_
MAINTENANCE_C.pdf
∎
Use the damper at up to 95% humidity, non-condensing.
∎
The fire damper can be cleaned with a dry or slightly damp cloth. It is forbidden to use abrasive cleaners or mechanical cleaning
techniques (brush).