UV/IR Type Flame Detector
RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 22 -
3.3.3.4 External Recovery Signal
It is used when the detector needs to recover from its default status after any fire
detection, etc. Hence, it is similar to reset product via power on/off.
Signal terminal number (TB1)
TB1
Signal name
8
RESET_RLY
[Table 14] TB1 External recovery signal terminal number
- Signal Specification
ㆍ Operating Signal : same level of signal with 24V-_IN
ㆍ Operating delayed time : 5 seconds
ㆍ Operating continuous time : after cancelling operating signal + reset time
※ After using the function above, signal must be opened first for the proper operation.
- Signal of electrical wiring
[Figure 18] External recovery signal electrical wiring diagram