Page No 8 of 56 Reznor, RHC21 4000 Installation EN May 2021 D301334 Issue 0
2 Technical Data
Model
RHC21
4024-05
4036-08
4050-06
4060-07
4075-09
4100-12
4125M15 4150M18
Combustion air & flue type Indoor
B
23
/ B
53
/ C
13
/ C
33
/ C
53
Combustion air & flue type External
Rooftop
Heat Input High Fire (Hs)
1
kW
29.30
44.00
61.50
77.60
91.50
120.00
153.00
183.00
Heat Input Low Fire (Hs)
1
kW
8.79
13.20
18.60
22.38
27.45
37.00
45.20
49.08
Heat Input High Fire (Hi)
2
kW
26.40
39.64
55.41
69.91
82.43
108.11
137.84
164.86
Heat Input Low Fire (Hi)
2
kW
7.92
11.89
16.76
20.16
24.73
33.33
40.72
44.22
Heat Output H2 High Fire
4
kW
24.17
36.19
51.20
64.74
76.04
99.61
125.43
151.25
Heat Output H2 Low Fire
4
kW
7.77
11.69
16.49
19.75
24.33
32.81
40.04
43.55
Gas Consumption High Fire
(Hs) G20
3
m³/h
2.79
4.19
5.86
7.39
8.71
11.43
14.57
17.42
Gas Consumption Low Fire
(Hs) G20
3
m³/h
0.84
1.26
1.77
2.13
2.61
3.52
4.30
4.67
Gas Consumption High Fire
(Hs) G25
3
m³/h
3.24
4.87
6.81
8.59
10.13
13.29
16.94
20.26
Gas Consumption Low Fire
(Hs) G25
3
m³/h
0.97
1.46
2.06
2.48
3.04
4.10
5.00
5.43
Gas Consumption High Fire
(Hs) G25.3
3
m³/h
3.17
4.77
6.66
8.41
9.91
13.00
16.58
19.83
Gas Consumption Low Fire
(Hs) G25.3
3
m³/h
0.95
1.43
2.02
2.43
2.97
4.01
4.90
5.32
Gas Service Connection
Inches BSP
1/2"
3/4"
3/4"
3/4"
3/4"
3/4"
11/4"
11/4"
Flue & Combustion Air
Connection Collars (Indoor)
Ø mm
100
130
130
130
130
130
130
130
Condensation Connection /
Outlet
Ø mm
22 OD
Minimum V1 Airflow at 15°C
with Heat Output H1
6
m³/h
N/A
N/A
3900
4700
5700
7500
N/A
N/A
kW
N/A
N/A
50.0
60.0
73.8
96.6
N/A
N/A
Temperature Rise at V1 Airflow
K
N/A
N/A
N/A
N/A
Minimum V2 Airflow at 15°C
with Heat Output H2
7
m³/h
2880
5281
5950
7150
8800
11700
9600
12300
Temperature Rise at V2 Airflow
K
25
20
26
27
26
25
39
37
Electrical Connection
1 Phase
230V 1N ~ 50Hz
Total Electric Rating
kW
0.08
0.30
0.30
0.30
0.30
0.28
0.60
0.60
Approx Appliance Weight (net)
kg
31
52
90
100
120
149
220
250
Protection Grade
IP
20 (Indoor) / X4D (External)
Table 1 : Specifications
1
Refers to gross calorific value of fuel
2
Refers to net calorific value of fuel
3
Natural gas: G20 Hs 37.78 MJ/m³, G25 Hs 32.49 MJ/m³, G25.3 Hs 33.2 MJ/m³
4
Heat output depends on airflow - heat output H2 only for airflows above V2
5
H2 = heat output at airflow V2 (V2 = minimum airflow required for high heat output H2)
6
H1 = heat output at airflow V1 (V1 = minimum airflow required through enclosure)