OPERATION
Major Component Descriptions
Motors
Electrical characteristics of motors are listed in
.
Table 10. Electrical Characteristics of Motors
Unit Size
Motor Type
HP
Amps
RPM
Volts
095
Fan
*
1/8
2.7
1050
115
140, 190
1/4
3.7
850
3/4
11.0
1725
095, 140, 190
Standard single-stage burner pump
1/7
2.0
3450
Optional two-stage burner pump
Optional boost pump
1/8
5.8
1725
*
The fan motor is totally enclosed and is equipped with internal overload protection.
Burner Pump
NOTE:
• IMPORTANT: Long or oversized inlet lines may require the pump to operate during the initial
bleeding period. In such cases, the priming may be assisted by injecting fuel oil into the pump
gearset. Under lift conditions, oil lines and fittings must be airtight. To ensure this, apply oil-
resistant pipe dope to both the used and unused inlet fittings and both return fittings.
• A bypass plug must be inserted when return connection is made by two-pipe supply system.
•
The unit is provided with either a standard single-stage, 3,450-RPM pump or an optional two-stage, 3,450-RPM
pump (option BZ1).
•
Burner Pump Pressure Adjustment
section for pressure check instructions.
•
section for vacuum check instructions.
•
See
for port, bleed, inlet, regulator, and bypass plug locations.
Figure 15. Burner Pump