background image

29

RP-HRPD-IOM (07-22) 132210-B

 

• Intermittent spark ignition safety pilot systems:

 There are two types of intermittent spark pilots: one type shuts 

off the pilot gas flow between the cycles and the other not only shuts off the pilot gas flow between cycles but 

also has a lockout device that stops the gas flow to the pilot if the pilot fails to light in 120 seconds . This lockout 

feature has a 1-hour retry or requires manual reset by interruption of the thermostat circuit . Propane units installed 

in Canada require the spark ignition system with the lockout device . Refer to the wiring diagram supplied with the 

heater for pilot system identification and wiring . Spark pilot without lockout is designated as option AH2 or with 

lockout is option AH3 .

 

• Ignition controller:

 As part of the intermittent safety pilot system, the ignition controller provides high voltage 

spark to ignite pilot gas and also acts as the flame safety device . After ignition of the pilot gas, the ignition controller 

electronically senses the pilot flame . A low voltage DC electrical signal is imposed on the separate metal probe 

in the pilot assembly . The metal probe is electrically insulated from ground . The pilot flame acts as a conduction 

path to ground to complete the DC circuit and prove pilot flame . Proper operation of the electronic spark ignition 

system requires a minimum flame signal of 0 .2 microamps, as measured by a microampmeter . With pilot flame 

proven, the ignition controller energizes the main gas valve .

Burners and Carryover System

 

• Burners:

 These duct furnaces have individually-formed steel burners with accurately die-formed ports to provide 

controlled flame stability without lifting or flashback with either natural or propane gas . All burners are lightweight 

and are factory-mounted in an assembly that permits all of the burners to be removed as a unit for inspection or 

service .

NOTE:  Natural gas burner racks (except when equipped with electronic modulation option AG39, 

AG40, AG41, or AG42) are equipped with two flash carryovers. Propane gas burners are equipped 

with one flash carryover and a regulated gas lighter tube system.

 

During regular service, check the main burner ports, the carryover assemblies, and the orifices for cleanliness .

OPERATION

⚠ WARNING ⚠

To ensure safety, follow the lighting instructions located on the outlet box cover.

Pre-Startup Checklist

 

‰

Ensure that electrical supply is in accordance with voltage rating on unit’s rating plate .

 

‰

Ensure that all field wiring is in accordance with  wiring diagram and that wire gauges are as required for electrical 

load .

 

‰

Ensure that electrical entrances are sealed against the weather .

 

‰

Ensure that fuses or circuit breakers are in place and are sized correctly .

 

‰

Ensure that condensate drain holes in the corners of the cabinet are open .

 

‰

Ensure that clearances from combustibles are in accordance with 

Clearances

 sections) .

 

‰

Check piping for leaks and proper gas line pressure and bleed trapped air from gas lines (refer to

 

Supply Piping 

Connections

 section):

a .  Turn OFF manual shutoff valve .
b .  Turn ON gas supply .
c .  Observe gas meter for movement or attach pressure gauge readable to 0 .1 IN WC and, after turning gas ON 

for 10 seconds, turn OFF gas supply—no change in pressure should occur over 3-minute period .

d .  If step c indicates leak, locate leak by brushing soapy solution on all fittings—bubbles will appear at any leaks .
e .  Repair any leaks and repeat test .

 

‰

Check to ensure that flue discharge openings are free from obstructions .

Содержание HRPD

Страница 1: ...agency or the gas supplier Be sure to read and understand the installation operation and service instructions in this manual Do not store or use gasoline or other flammable vapors and liquids in the...

Страница 2: ...Piping Connections 19 Electrical Connections 21 Control Wiring 21 CONTROLS 22 Thermostat 22 Fan Control 22 Limit Control 22 Combination Gas Valve 22 Combustion Air Proving Switch 23 Optional Two Stag...

Страница 3: ...g rate and electrical requirements are shown on the unit s rating plate Model HRPD is dual model RP furnaces configured for higher CFM capacity References TABLE OF CONTENTS CONTINUED OPERATION 29 Pre...

Страница 4: ...thoroughly before installing or servicing this equipment WARNING For your safety read the warning labels on the unit CAUTION These duct furnaces are not certified or approved for use in drying or proc...

Страница 5: ...spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c Unit is installed without proper clearance to combustible materials or without proper ven...

Страница 6: ...Figure 1 Unit Size 125 150 175 200 225 250 300 350 400 Inches 1 8 mm 3 A 30 15 16 786 36 7 16 914 41 15 16 1065 50 3 16 1275 55 11 16 1414 61 3 16 1554 B 28 1 2 648 34 864 39 1 2 1003 47 3 4 1213 53 1...

Страница 7: ...provided Table 4 Weights Model RP Unit Size 125 150 175 200 225 250 300 350 400 HRPD Unit Size 250 300 350 400 500 600 700 800 Pounds kg RP 201 91 217 98 247 112 295 134 333 151 361 164 HRPD 402 182 4...

Страница 8: ...s Check to see if there are any field installed options that need to be connected to the furnace prior to installation Shipped separate options could include a gas shutoff valve a vertical vent termin...

Страница 9: ...cy performing this work assumes responsibility for the conversion of this appliance to provide for higher CFM Theseinstructionsaredesignedtopreparetheductfurnaceforincreasedairthroughputconversion pri...

Страница 10: ...ffle b Remove both side finger baffles Figure 4 Side Finger Baffle Removal 3 Install field conversion label see Figure 5 a Fill in field conversion label PN 263310 from literature bag b Adhere label t...

Страница 11: ...ket assembly on opposite end of heat exchanger and secure using field supplied sheet metal screws 4 Reinstall airflow baffles removed in step 1 and secure using existing screws Figure 6 Airflow Baffle...

Страница 12: ...1 inch is recommended of insulation Supports suspend all ducts securely from buildings members Do not support ducts from unit duct connections Access panels Install removable access panels see Figure...

Страница 13: ...ischarge sensor is field supplied Follow the instructions below to install the sensor in the ductwork 1 Determine distance of sensor from unit a Ensure that there is sufficient distance from outlet to...

Страница 14: ...nse air temperature as it flows through holes in holder 3 At selected ductwork location mark diamond shaped hole approximately 1 1 inch 25 25 mm required for sensor holder or round hole required for m...

Страница 15: ...40 3070 0 28 2630 0 23 2300 0 22 2045 0 21 300 4420 0 58 3685 0 39 3160 0 29 2765 0 25 2455 0 22 350 5160 0 65 4300 0 44 3685 0 31 3225 0 25 2865 0 23 400 5895 0 70 4915 0 50 4210 0 30 3685 0 30 3275...

Страница 16: ...Duct Furnace Blower Connections Bypass Duct Construction When the air throughput CFM is greater than desirable or permissible for the unit a bypass duct see Figure 11 may be constructed Locate the byp...

Страница 17: ...110 3290 9 229 1700 2100 2400 2700 2970 3200 3400 3600 3800 10 254 1920 2350 2760 3090 3650 4020 4300 4550 4800 See Figure 11 NOTE Not all capacities are covered above If your installation is not cove...

Страница 18: ...ater Gas Supply Piping DANGER All components of a gas supply system must be leak tested prior to placing equipment in service NEVER TEST FOR LEAKS WITH AN OPEN FLAME Failure to comply could result in...

Страница 19: ...ne Gas Natural Gas Propane Gas Cubic Feet per Hour 20 92 56 190 116 350 214 730 445 1100 671 2100 1281 30 73 45 152 93 285 174 590 360 890 543 1650 1007 40 63 38 130 79 245 149 500 305 760 464 1450 88...

Страница 20: ...ued Figure 13 Gas Connections Table 13 Gas Connection Sizes Gas Type RP Unit Size 125 250 300 400 HRPD Unit Size 250 500 600 800 Connection Size Inches mm Natural gas 1 2 13 3 4 19 Propane 1 2 13 NOTE...

Страница 21: ...y with fused disconnect switch should be run directly from the main electrical panel to the unit making connections in the junction box Disconnect switch A disconnect switch is a required part of this...

Страница 22: ...t Use either an optional thermostat available with the system or a field supplied thermostat Install according to the thermostat manufacturer s instructions Fan Control NOTE To replace the fan control...

Страница 23: ...odels HRPD Models Units Without Option AG39 AG40 AG41 or AG42 All 0 58 0 05 IN WC 1 05 IN WC 0 73 IN WC Units with Option AG39 AG40 AG41 or AG42 125 225 250 400 0 58 0 05 IN WC 1 30 0 20 IN WC 1 05 0...

Страница 24: ...es 64 F low stage furnace 2 68 F shutdown furnace 2 70 F low stage furnace 1 74 F shutdown furnace 1 AG4 HRPD 2 70 F 66 F full rate both furnaces 70 F shutdown furnace 1 74 F shutdown furnace 2 AG15 R...

Страница 25: ...n the heater rating plate AG7 is identified as MV 1 AG8 is identified as MV 3 AG9 is identified as MV 4 AG21 is identified as MV A AG39 is identified as MP 1 and AG40 is identified as MP 2 AG39 and AG...

Страница 26: ...ual to or greater than the thermal efficiency at full fire The gas train see Figure 16 includes a single stage gas valve a modulating valve and two gas pressure switches The burner rack is equipped wi...

Страница 27: ...gear motor Replace primary manifold pressure switch YES NO YES NO YES NO YES NO YES NO NO YES YES NO Measure manifold pressure during burner cycling When the manifold pressure is BELOW 1 0 w c is the...

Страница 28: ...is available only with model HRPD natural gas units and is not available on unit size 700 Depending on its size a furnace equipped with option AG40 or AG42 has a 20 28 turndown ratio With option AG40...

Страница 29: ...trolled flame stability without lifting or flashback with either natural or propane gas All burners are lightweight and are factory mounted in an assembly that permits all of the burners to be removed...

Страница 30: ...The result is incomplete combustion which produces carbon monoxide a poisonous gas that can cause death Safe operation of indirect fired gas burning equipment requires a properly operating vent syste...

Страница 31: ...when the heater is in operation and when it is on standby Incorrect inlet pressure could cause excessive manifold gas pressure immediately or at some future time NOTE A manometer fluid filled gauge i...

Страница 32: ...turn using wrench DANGER DO NOT use an open flame to check for gas leaks Table 20 High Elevation Burner Orifices Installation Elevation Feet Meters Installation Location RP Unit Size Natural Gas Propa...

Страница 33: ...rclockwise to close the air shutter After the furnace has been in operation for 15 minutes close the air shutter until the flame turns yellow Open the shutter until yellow disappears Adjust Heat Stage...

Страница 34: ...ion and clean as necessary Clean all dirt and grease from primary and secondary combustion air openings Power vent Check flue products outlet and clean as necessary Gravity vent Check vent cap or opti...

Страница 35: ...connect electric valve leads e Uncouple union in gas supply f Remove sheet metal screws in top corners of burner rack assembly g Pull drawer type burner rack out of furnace 2 Disassemble burner rack N...

Страница 36: ...l sensing probe and the pilot hood with an emery cloth and wipe off the ceramic insulator 4 Check the spark gap see Figure 20 which should be maintained to 7 64 inch Figure 20 Pilot Assembly Spark Gap...

Страница 37: ...a If voltage between black and brown leads on main gas valve is 20 32 VAC and there is no main gas flow with built in manual valve in FULL OPEN position main valve is defective b If there is no voltag...

Страница 38: ...ner Rack Maintenance section b Remove heat exchanger V baffles see Figure 22 1 Remove ends of flue gas collection box 2 On control side of furnace remove venter assembly and flue outlet duct to gain a...

Страница 39: ...l lockout device interrupting control circuit due to above causes Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch Replace combustion air proving switch C Pil...

Страница 40: ...__________ Address ________________________________________________________ ________________________________________________________ Phone ________________________________________________________ Mode...

Отзывы: