Reznor, Guardian 1 Phase Electric Heat with Signal Pro, Installation Manual,  EN 2021-11, D301375 Iss 0 Page No 19 

C

Keypad buttons

The buttons have the following functions:- 

MENU enters the programming menu and advances 
item to program in order below. 
OK starts programming of visible item, value flashes 
during programming. 
PLUS and MINUS adjust the value. 
OK saves the modified value or MENU stops 
programming with value reverting to old 
value. 

If more than one air curtain is connected to the 
network then for some settings all controls can be 
set together or controls can be set individually. Only 
controls that are present on the system can be
programmed, others are skipped over. 

Air curtains are addressed as 0 to 15 by the display, 
corresponding to bit switch settings 0 to F on the
air curtain control. 

Keypad display

AC:0 - denotes air curtain address ‘0’ 
22° - denotes internal temperature 22°C 
H:OFF - denotes Heat off status 
DOOR CLOSED - denotes door closed status 

Th - denotes Day on Thursday 
13:08 - denotes 1:08pm (24 hr clock) 
ON1 - ‘ON’ denotes this air curtain is active, ‘1’ 
denotes Internal Timer 
OS:23° - denotes Outside temperature 23°C 

Operation

In normal operation the home screen displays the 
status of the display panel and each connected air 
curtain in sequence. Each screen is displayed for two 
seconds.

Display Status

Top line shows day and time.

If the panel is using internal timer then the program 
time status, “ON1”, “OFF1” etc will also show.

Bottom line shows the outside temperature which is 
an average of all connected outside sensors.

If the panel has low battery then “LOW BATT” is also 
displayed.

If Overtime is active then the panel status instead 
shows overtime countdown in the top line.

Top line shows air curtain address, measured 
temperature (air outlet temperature for electric AC 
or flow temperature for LPHW AC), heating on “H1” 
or off “H0”, and fan speed “F0” for off or “F1”, 
“F2”, F3”. Ambient AC shows “Ambient” in place 
of flow temperature and heat. 

Bottom line shows operating mode: “ON MODE”, 
“OFF MODE” or “AUTO”. If the air curtain has an 
active input that will be shown in the bottom line as 
either “DOOR CLOSED”  or “TIMER OFF”. 
If the air curtain is off due to outside temperature 
limit then that will be shown in the bottom line as 
“OS TEMP LIMIT”.

If appropriate, interlock status “INTERLOCK DOOR”, 
“INTERLOCK TIMER”, “INTERLOCK FILTER” or 
“INTERLOCK STAT” will show in the bottom line.

Figure 25 Wiring of 2 or more networked air 
curtains.

 

Figure 24 Air curtain address numbers

Содержание GUARDIAN GB 1000

Страница 1: ...s document carefully before commencing installation commissioning and or servicing Leave it with the end user site agent to be placed in their premises technical file after installation WARNING Improp...

Страница 2: ......

Страница 3: ...auto mode 20 4 All on mode 20 5 All heat off 20 6 Set door open temperature 20 7 Set heat on off 21 8 Set overtime 21 9 Set time and days 21 10 Set time program 21 11 Menu end 21 Engineers instruction...

Страница 4: ...vailable at an additional cost The display program panel allows the user to control either a single air curtain or a network of up to 16 air curtains Easy programming the end users simply select wheth...

Страница 5: ...Important notice to installers Before installation check the local distribution conditions supply voltage are compatible Installation assembly commissioning service and maintenance procedures must be...

Страница 6: ...velocity at 1 metre H m s 5 6 5 2 5 4 Maximum velocity at 2 metre H m s 3 8 3 5 3 7 Maximum velocity at 3 metre H m s 2 8 2 5 2 8 Motor power L M H W 365 530 730 Noise level 3m free field L dB A 52 M...

Страница 7: ...ntry and prevents combustible surfaces overheating The minimum mounting height floor to grille outlet is 1 8m The recommended maximum mounting height is 3m for standard fan setting 4m for high Dimensi...

Страница 8: ...ces It is recommended that a minimum clearance of 100mm is allowed around the case The clearance allows for cable entry and prevents combustible surfaces overheating The minimum mounting height floor...

Страница 9: ...4 112 114 3 830 1360 1884 4 226 5 1060 1584 2111 6 448 7 1125 1650 2177 8 436 9 300 10 427 487 Figure 4 3 GB Side view Table 4 GB Dimensions Clearance distances It is recommended that a minimum cleara...

Страница 10: ...display panel is supplied with an industry standard plastic double surface mounted socket box Alternatively the display panel can be flush mounted using a customer supplied plastic or metal flush con...

Страница 11: ...al EN 2021 11 D301375 Iss 0 Page No 11 TD Component layout Figure 6 Component layout GS Location Component 1 Control panel 2 Installer terminal block 3 Fan 4 Fan motor 5 Fan deck 6 Resistor 1500 only...

Страница 12: ...the consultant architect or owner of the building is recommended to ensure that a sound stable installation can be achieved Figure 8 Honeycomb outlet position near to the door adjustable angle of 0 to...

Страница 13: ...of the lower grove in the case 3 The first cover can then be pushed to the right to release it from the screw slot see figure 10 then pull forward and lift upwards to be removed For additional covers...

Страница 14: ...ins level 6 Holes are provided in the casing for cable entry Choose the appropriate hole to suit the installation Note the terminal connection block is located to the right of the unit 7 Install the c...

Страница 15: ...nstructions grill Figure 16 Mounting bracket option Figure 16 1 Mounting bracket fitted to GB Signal Pro display panel The display panel can be installed using the standard double surface box supplied...

Страница 16: ...e units to each terminal pair EXT Only air curtain s wired this way will respond to the sensor setting If the optional external temperature sensor is connected to the air curtain If the external tempe...

Страница 17: ...itching thyristors for the heater An external circuit breaker with the appropriate rating should be installed for the protection of the installation Terminal Description Cable 3 4 Optional external sw...

Страница 18: ...red RJ45 cable to the socket in the first air curtain housing See figure 25 on page 19 Connect a second RJ45 cable in to the spare RJ45 socket of the first air curtain and then take across to one of t...

Страница 19: ...C Operation In normal operation the home screen displays the status of the display panel and each connected air curtain in sequence Each screen is displayed for two seconds Display Status Top line sho...

Страница 20: ...o heat and no fan and then returns to default display 3 All Auto mode A single press of OK quickly starts Auto timed operation for all air curtains and then returns to default display When in Auto mod...

Страница 21: ...lashing Use PLUS and MINUS to adjust hours 00 to 23 then OK Minutes starts flashing Use PLUS and MINUS to adjust minutes 00 to 59 then OK After this OK the new Time and Day is stored If MENU is presse...

Страница 22: ...ss was individual then next address is flashing Use PLUS and MINUS to set address OK to modify the fab speed or MENU to exit back to engineers menu 3 Set door closed temperature Door closed temperatur...

Страница 23: ...of the air curtains discovered then OK If lead air curtain address is set to OFF then the sequence finishes and returns to the engineers menu interlocks will not be enabled If lead air curtain addres...

Страница 24: ...work scanned for connected air curtains and when finished returns to engineers menu If scan NO then the sequence returns to the engineers menu Note This will cause the detected network type to be rese...

Страница 25: ...the air curtain on this address is not responding to the panel Display for active air curtains Electric system Where AC is address of AC with diagnostics being displayed H 1 heat on 0 heat off from AC...

Страница 26: ...e the outside limit the fan will continue to run but the heat output will be off When the outside temperature is below 0 C the air outlet temperature will be the set temperature plus the elevate at ze...

Страница 27: ...gs Bitswitch3 ON Modbus Address Switch Setting Modbus Address Switch Setting 16 0 24 8 17 1 25 9 18 2 26 A 19 3 27 B 20 4 28 C 21 5 29 D 22 6 30 E 23 7 31 F Modbus function codes supported Codes Descr...

Страница 28: ...xt_exists Read only Set if external thermistor not fitted 13 Set_fan1 Read write Switch fan 1 14 Set_fan 2 Read write Switch fan 2 15 Set_fan 2 Read write Switch fan 2 16 Heat Read write Switch heat d...

Страница 29: ...lifted out of the dog bone slot This panel can then be lifted out of the tabs at the bottom to fully release see figure 9 on page 13 2 GR units loosen the screws securing the inlet grille and hinge do...

Страница 30: ...elease the carrier from the stud side on the 2m models the centre support can be moved to one side to allow the stud side to be released On the GS units peal back the tabs which retain the honeycomb o...

Страница 31: ...to identify the nature of the fault however we do not recommend re setting without a thorough investigation into why the cut out operated Figure 31 Thermal cut out Display panel Any fault will be des...

Страница 32: ...heat Air sensor cable disconnected Air sensor broken Check cable Replace air sensor Air sensor temp too high Fan operating no heat High ambient air temperature Incorrect motor or fan deck rotation Mot...

Страница 33: ...of the unit Component 1000 1500 2000 Generic components Fan deck assembly 1026174 1026175 1026174 x 2 Signal Pro display panel 108221 RJ45 2 Resistor n a 1037491 n a Honeycomb core 1026068 1026078 102...

Страница 34: ...verse the steps remembering to reconnect the temperature sensor wire which goes through the hole in the PCB Reverse the steps to install the new control panel Set the dip switch for the location and f...

Страница 35: ...o 35 G 3 Remove the wires to the thermal cut out sensor two sensors on the 2 metre units and remove the thermal cut out 4 Remove the four securing nuts shake proof washer and flat washer that secure t...

Страница 36: ...k com www reznor eu Nortek Global HVAC is a registered trademark of the Nortek Global HVAC lLmited Because of the continuous product innovation Nortek Global HVAC reserves the right to change product...

Отзывы: