0503RHC8RJLGBEN
15/34
A
TTENTION
:
Flue pipe requirements for RHC 8125M 15, RHC 8150M 18, RHC 8175M 21, RHC 8200M 24 RJL :
To guarantee that the above-mentioned units are
working on 91% efficiency, it is necessary to seal a
number of openings in the inlet grill of the combustion
air as indicated in the table below. The openings to be
sealed depend whether it concerns a horizontal or
vertical unit.
Part nummer grill : 90 79050
Standard
Option
Standard
Option
Horizontal
Vertical
Number open
Number open
unit
unit
holes
holes
openings in grill
openings in grill
Horizontal
Vertical
Chimney diam (mm) to be sealed
to be sealed
version
version
8125 M15
130
1-2-3/14-15-16
1-2-3/14-15-16
10
10
8150 M18
130
1/16
1-2/15-16
14
12
8175 M21
130
1-2/15-16
1-2-3-4/14-15-16
12
9
8200 M24
130
1-2-3-4/13-14-15-16
1-2-3-4-5/13-14-15-16
8
7
Example :1-2-3/14-15-16
1
2
3
4
5
6
7
8
9
10
0
11
12
14
16
13
15