7 Frequency Converter Mounting
7.1 Installation Conditions
The frequency converter must be vertically installed.
If one frequency converter is arranged above another, make sure the upper limit
of air temperature into the inlet is not exceeded (see
). An air guide is recommended between the frequency converters to
prevent the rising hot air being drawn into the upper frequency converter if the
upper limit of air temperature is exceeded.
Fig. 7-1: Mounting distance and arrangement
d
hor
: Distance horizontal = 0 mm (0K40...22K0); Distance horizontal = 10 mm
(30K0...90K0)
d
top
: Minimum top distance = 125 mm
d
bot
: Minimum bottom distance = 125 mm
1: Air inlet at frequency converter; 2: Air inlet at control cabinet
3: Frequency converter; 4: Air outlet at frequency converter
5: Heated air conveying direction; 6: Air guide in control cabinet
7: Fan in control cabinet; 8: Discharge of heated air