HRV and ERV Typical Installations
(cont’d)
8
HORIZONTAL
•
30” clearance is recommended for cleaning of the core/servicing the unit.
• Dampers are installed for horizontal installation. For vertical installation both dampers have
to be turned so they can open properly and close when there is any backdraft.
•
Make sure no screw will interfere the function of the backdraft damper flaps while
installing the duct work to the HRV/ERV.
STRAPPING SYSTEM:
(optional)
Allows one person installation for
vertical and horizontal installation.
VERTICAL
Note:
After installation make sure the HRV/ERV is properly leveled. If not levelled correctly,
then defrost will not perform effectively and/or unit may frost in winter.
Note:
UP
UP
PULL
DOWN
Strap
jtantay 01.28.1
1
*
NOT SUPPLIED
jtantay 12.23.1
1
Vibration
Spring
Washer
*
Screw
*
CHAIN MOUNTING
SYSTEM:
(optional)
Available for both
horizontal & vertical
installation.
Chain
*
Backdraft
Damper
Concrete
Concrete
Wooden Joist
Bracket
(Supplied)
Grommet
*
Washer
*
Backdraft Damper
Superior Unit
Shown
Screw
*
Flap
Flap
Backdraft Damper
27 "
3
4
/
21"
9"
20"
9"
Project Condo Unit
Shown
21"