- BMS communication –
the unit can be integrated with the BMS building
control system
-
external
ON / OFF switch –
the unit can be turned on / off at the highest speed
according to the external switch, using 'External switch' terminals (see wiring
diagram in point 7)
1) Set up your INSPIRO model in the controller parameters – in order
6.2 COMMISSIONING
The procedure described below is identical for both versions of the control
panels. In case of doubts what are the functions of particular buttons, please
read the point 6.4 or 6.5 (depending on the model of your control panel).
After checking all wires and connections, switch on the device with POWER
ON/OFF button and then:
to do that the following should be done:
- using SET button go to parameter no. 21 (i. e. "Model INSPIRO", see point 6.3)
and press MODE button to change the value of this parameter
- using UP and DOWN arrows, change its value to the appropriate for the given
model (according to the table below)
- press and hold the MODE button for 6 seconds to enter the controller
parameters
no. 2 and 3)
no. 2 and 3 according to user's requirements
ensure that the value of OA temperature is within the range specified
- pressing MODE button verify that the given temperatures are correct values,
corresponding to the real ones
to do that the following should be done:
and different for various fan speeds
6.3 CONTROLLER'S PARAMETER
must be confirmed with SET button. The controller has the following editable
parameters:
if the OA temperature read by the unit is outside this range, you need to adjust
the range accordingly, in a manner analogous to point 1 (for parameter
- check if the bypass has been opened it should be indicated by the icon
- changing the supply fan speed (in SA or OA mode) and exhaust fan (in RA mode)
using FAN button, check that the supply and exhaust air flows are felt
2) Check the fans and temperature sensors operation – in order
and also the OA and SA temperatures should be the same (after some time)
3) Check the bypass operation – in order to do that the following should be done:
- after carrying out the test, remember to adjust the values of parameters
by parameters no. 2 and 3 (default 19 - 21°C, see parameter table in point 6.3)
To edit the controller parameters, press MODE button for at least 6 seconds.
SET button allows you to "move" between individual numbers (corresponding
parameters) and pressing MODE button again, enables you to enter
t o t h e e d i t i o n m o d e o f a p a ra m e t e r. A d j u s t m e n t o f p a ra m e t e r
value can be done with UP and DOWN arrows. Then the set value
Number
00
01
02
03
04
05
06
07
08
21
23
24
25
Parameter
Auto restart
Electrical heater
Automatic bypass
temperature ‘X’
Automatic bypass
temperature ’Y’
Defrosting interval
Defrosting entering
temperature
Defrosting duration time
Permissible CO
2
concentration value
ModBus address
INSPIRO model
Fan speed control
Multifunction setting
Filter alarm setting
Range
0-1
0-1
5-30
2-15
15-99
-9-5
2-20
00-250
1-16
0-15
0: 2 speeds
1: 3 speeds
2: 10 speeds
0: Reserved
1: Sweep filter alarm
2: Sweep weekly timer
0: 45 days
1: 60 days
2: 90 days
3: 180 days
Default
1
0
19
3
30
-1
10
00 (off)
1
0
2
0
0
Unit
-
-
°C
°C
Minute
°C
Minute
x 10 ppm
-
-
-
-
-
If the concentration of CO
2
in the air read by the sensor exceeds the maximum
allowable value, the unit starts to work automatically at the highest speed.
the previous defrosting operation is longer than the defrosting interval
(parameter 04), then the device will go into defrosting mode, i. e. fan of supply air
automatically stops and the exhaust air fan operates at the highest speed
i n o r d e r t o d e f r o s t t h e exc h a n g e r. T h e d e f r o s t i n g p r o c e s s w i l l
If the unit is equipped with an electric heater on the supply side, the parameter
should be changed to 1. Then in the TA mode, the supply air temperature
Bypass opens under the condition that the outside temperature is higher than X
(parameter 02) and lower than X + Y (parameter 03). In other cases, the bypass
remains closed.
04, 05 i 06 -
applies to automatic defrosting function
If the
FR temperature
decreases below the defrosting entering temperature
(parameter 05) and last at least 1 minute and the time which elapsed since
can be adjusted within the range of 10-25°C.
The device will return to the previous stage when the CO
2
concentration falls
below this limit value.
02 i 03 -
refers to an automatic bypass function
0: Invalid 1: Valid
01
- applies to electric heater of supply air
21 -
refers to the performance characteristics of particular INSPIRO model
end when the exhaust temperature FR is 15 degrees higher than the defrosting
entering temperature (parameter 05) for 1 minute or the specified defrosting
duration time expires (parameter 06).
08
- designate address of the unit for BMS system
0: Invalid 1: Valid
00
- refers to an automatic restart after a power supply break
07 -
refers to function of CO
2
concentration control (optional)
This value should be specified during commissioning (see point 6.2).
23 -
applies to the possibility of regulation the supply and exhaust fans operation
24 –
function enables to deactivate weekly schedule or filter alarm after
It determines how often filter alarm appears, reminding you to clean or replace
filters.
its replacement
25 –
applies to filter alarm frequency
INSPIRO 150
INSPIRO 250
INSPIRO 350
INSPIRO 500
INSPIRO 650
INSPIRO 800
6
5
4
3
7
8
INSPIRO 1000
INSPIRO 1300
9
2
Model
Value
Содержание INSPIRO
Страница 4: ...INSPIRO 350 INSPIRO 500 INSPIRO 650 INSPIRO 800 INSPIRO 1000 INSPIRO 1300...
Страница 10: ...7 CONNECTION SCHEME...
Страница 12: ...Warranty card Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland...
Страница 13: ...Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland www reventongroup eu...