PRECAUTIONS & WARNINGS
The precautions mentioned below must be strictly followed during operation
of the device:
- all works concerning electrical installation (disassembly, repair etc.) should
be made by the qualified staff, who possess the qualifications due to the domestic
and local norms, regarding electrical installations
- do not use the unit for direct exhaustion of kitchen vapors - this may result
in clogging of the exchanger and filters by fats and greases
- the unit should not work without installed G3 and F9 filters - this can lead to dirt
and clogging of the enthalpy exchanger
- if there is a risk of frosting, preheater should be used
- before service or exchange of the device it is obligatory to cut off the current
supply
- do not limit or cover the inlet and outlet of the device
- do not install, service the device with wet hands or barefoot
- the device should be kept out of reach of children and animals
- after operating time of the device, please utilize it concerning the local norms
and regulations
- it is recommended to clean the device periodically:
·
unit's casing clean from dirt (at least once per year)
·
G3 filter blow with compressed air to remove dirt and dust (at least once per
quarter)
·
enthalpy heat exchanger clean from dirts (at least once per two year)
- for installation of the device in a place where is high dust concentration,
the periodic cleaning of filter and exchanger should be performed much more
often, not allowing the items to 'clog’
-failure to comply with cleaning obligations may have a negative effect
on technical parameters of the device and lead to loss of warranty
- if the device is not used for a longer time and lead to loss of warranty disconnect
the power supply
6.
CONTROLS
6.1 CHARACTERISTIC
Energy recovery unit INSPIRO BASIC series has controller in the set, which
optimise the unit operation. Communication with the cotroller is possible with
control panel BASIC - detailed description of control panel operation can be
found in point 6.3.
The main functions of the
unit
:
- speed selection
–
regulation of supply and exhaust fans airflows - 3 different
speeds
- weekly schedule
– it is possible to set a weekly work schedule of the unit
-bypass
–the function allows to supply outside air directly (i. e. without energy
recovery) if there is no heating / cooiling demand
- filter alarm -
after working over 1000 hours in total, the icon of filter alarm
is displayed on the LCD screen - it remindes about necessity of filter cleaning
- BMS communication
– the unit can be integrated with the BMS building control
3.
ASSEMBLY
3.1. GENERAL PRINCIPLES
- device is designed for hanging mounting
- mounting elements not included in the kit, you should buy them yourself
and make sure they are suitable for this type of installation
- the device must be installed horizontally
- it is not possible to mount the unit upside down
- protect the openings of the unit against the ingress of dust during installation
- the minimum gap in which the device will be installed is at least 320 mm
(for INSPIRO BASIC 200 - INSPIRO BASIC 600) or 450 mm (for INSPIRO BASIC
800)
- the device should be installed in a way that allows easy access to the inspection
door and the electrical box
- exemplary installation with energy recovery unit is shown in the figure below
3.2
DUCTING
- connection between ducts and the openings of the device must be secured
with tape or sealed in accordance with domestic or local norms
- outside ducts (i. e. fresh and exhaust air) should be thermally insulated
and carried out with a drop of 1 - 2% toward the outside in order to prevent water
entering into the unit
- the energy recovery unit and ducts cannot run close of flues (e. g. form boiler)
- it is not allowed to make ducts in the way shown below:
- fire dampers must be installed in accordance with domestic or local fire
regulations
- the device must not be exposed to an ambient temperature above 40 ° C
- the unit should be protected against the influence of frost / water
(i. e. appropriate insulation, preventing lowering the temperature in the room
below 0 ° C, pre-heater, etc.)
- outside ducts should be ended by intake and exhaust outlets, located
in accordance with domestic or local norms
- before start up ensure there are no obstructions to or in the ducts
- operation of heater should be synchronous with the unit
- duct silencers can be used to minimize noise in the room
4. INSTALLATION INSTRUCTIONS
4.1. CONNECTION OF THE DEIVCE TO THE ELECTRICAL SYSTEM
- all works concerning electrical installation should be made by the qualified
personnel (who possess required authorizations to install electrical equipment),
based on wiring schematic diagram
(see point 7)
- the recommended cross sectional area of the supply wires is 1.5
m
m²
and the control wires 1
m
m²
- the electrical installation of the building shall have a residual current device
- it is recommended to check the electric installation and controls before the first
start
Excossive bending angle
Reduce the diameter
of the junction part
Too many bending parts
6.2
COMMISSIONING
1) Check the fans operation – in order to do that the following should be done:
- pressing button set the manual mode
- using arrows and change the fans speed
2) Check the bypass operation – in order to do that the following should be done:
- press and hold button during 2 seconds to switch between energy recovery
and bypass mode
ATTENTION!
For INSPIRO BASIC 800 fans switch off for several seconds when
the bypass damper is moving.
M
and then:
After checking all wires and conections, switch on the device with button
Содержание INSPIRO BASIC 200
Страница 4: ...INSPIRO BASIC 400 INSPIRO BASIC 600 INSPIRO BASIC 800...
Страница 7: ...7 CONNECTIONS SCHEMES INSPIRO BASIC 200 INSPIRO BASIC 600 INSPIRO BASIC 800...
Страница 9: ...Warranty card Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland...
Страница 10: ...Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland www reventongroup eu...