- i
t is recommended to clean the device periodically (at least once per month):
ź
heating coil blow with compressed air
ź
fan casing and blades clean from dirt
- for installation of the device in a room where is high dust concentration,
the periodic cleaning should be performed much more often, not allowing
the heat exchanger to 'clog’
- failure to comply with cleaning obligations may have a negative effect
on technical parameters of the device
- i
f the device is not used for a longer time disconnect the voltage supply
-
the device is transported with the closed air stators. It is essential to open them
in at least for 30 % before first start
-
opening the air stators must be done by two hands in parallel.
6.
CONTROLS
Usage of automatic control dedicated to the air water heaters of Reventon
Group gives great possibilities of adjusting the efficiency of the heater
in different, depending on needs, degree of automation of its operation. We also
offer additional controls:
c
ontroller is used to regulate devices equipped with 3-stage fans. It controls
them according to set program (required air temperature). There is also
opportunity to connect the external air temperature sensor (in the set).
The controller automatically controls the actuator of two-way valve.
It has MODBUS communication too.
Voltage/ Frequency
:
230 V AC / 50 – 60 Hz
Maximum current
:
5 A
Operating temperature range
:
0 - 45°C
Regulation range
:
5°C - 35°C
Regulation accuracy
: ±0,5°C
External temperature sensor
: NTC 10K
Communication:
RS485
Dimensions
:
86 x 86 x 13,3 mm
c
ontroller is used to regulate devices equipped with 3-stage fans. It has a 3-stage
speed control and built-in thermostat switches the device of automatically when
the preset temperature is reached. In addition, the unit controls the operation
of the actuators installed on the control valve
.
Voltage/ Frequency
:
230 V AC / 50 – 60 Hz
Maximum current
e:
3 A
Regulation range
:
10°C - 30°C
Operating mode: continious or thermostatic
Regulation accuracy
: <1°C
Dimensions
:
130 x 85 x 40 mm
Weight
:
210 g
Degree of casing's protection
:
IP 30
Programmable controller HMI
3-stage speed controller with thermostat HC-3S
Model
HC 3,0 A
HC 5,0 A
HC 7,0 A
3
5
8
MC IP54-3S
HMI
HC3S
3
5
HC 14 A
RM- 16 A
16
19
Fan speed controller HC
Two-way valve with actuator ¾” (installation on the return from exchanger)
Manual thermostat HC
d
esigned to change the single-phase fan's speed voltage controlled in industrial
supply and heating systems. It is available in several versions. The selection
of the appropriate model depends on the number of the devices that have
to be connected to the to one regulator – the total intensity of the connected
devices cannot exceed the maximum current flow of the regulator.
5 control levels:
80-105-135-170-230 V
*
Voltage/ Frequency
:
230 V AC / 50 – 60 Hz
Maximum current output (depending on model):
3 A, 5 A, 7 A lub 14 A
Protection:
thermal switch
Weight(depending on model)
:
2,5 kg, 4,5 kg, 5,5 kg or 10,5 kg
Degree of protection:
IP 54
*
regulation for 3 A regulator
: 115-135-155-180-230 V
t
he two-way valve with actuator is used to automatically regulate the flow
of the heating medium.
Voltage/ Frequency
: 230 V AC / 50 – 60 Hz
Total current
: <0,25 A
Maximum operating temperature:
60ºC
Closing time:
5 - 6 min
Adjustment stroke:
3,6 mm
Degree of protection:
IP 40
r
elay module RM-16A opens and closes the circuit to affect the work of other
devices. It can be used to connect a receiver with higher power than the relay
in the controller allows. Maximum rated current is 16A.
Voltage/ Frequency
:
230 V AC / 50 – 60 Hz
Maximum current
:
16 A
Input
:
NO/COM
Input
:
SL Connection of a regulator
with the voltage relay 230 V
Dimensions
:
47 x 47 x 20 mm
c
ontrols operation of the heater. Switches the unit off automatically when
the set temperature is reached.
Voltage/ Frequency
:
230 V AC / 50 – 60 Hz
Maximum current
:
3 A
Zakres pracy:
0 - 40°C
Regulation range
:
10 - 30°C
Regulation accuracy
:
<1°C
Relay Module RM-16A
COOPERATION OF CONTROLLERS WITH EQUIPEMENT
Содержание FARMER MC-35
Страница 1: ...Technical documentation AIR WATER HEATERS IN STEEL CASING FARMER MC 3S REVENTON GROUP FARMER MC 3S...
Страница 7: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 14: ...Warranty card Reventon Group Ltd 3B Montazowa Street 43 300 Bielsko Bia a Poland...
Страница 15: ...Reventon Group Ltd 3B Montazowa Street 43 300 Bielsko Bia a Poland www reventongroup eu...