Control wires REVCON RFE B3/D3 and REVCON RFE B2/D2
Terminal usage:
Figure 4.4.4.2
Note!
The terminals 5,6,9 and 10 are not lead through.
Terminals 1-4 (refer to figure 4.4.4.2)
These terminals are contacted to two potential free (SELV) relay contacts (one NOC
and one NCC) with a maximum current load of 5 A AC or 3 A DC. It is not allowed to
connect other voltage types than SELV!
In figure 4.4.4.2 the relay is displayed in rest position.
The relay toggles, if:
1.) Power supply is o.k.
2.) No error present, and after perhaps an
ON
-signal has been released.
1
2
3
4
5
6
7
8
9
10
11
12
+
-
External
OFF
Not
used
ON/RESET
Terminal 5 and 6 intern connected
to the temperature supervision
X2
Common fault
relay