The warranty given by us expires, if the unit is modified or (even partially) dismantled
or if it is used in contradiction to our instructions.
•
The constructor of the plant, who has to know the technical guidelines, bears the re-
sponsibility for the correct selection and arrangement of the electrical components.
•
Putting into operation of the power feed/feedback unit is only admissible at VDE-
conform nets of electrical power supply. Non-observance may damage the device!
•
In accordance with the corresponding standards and guidelines the operation on even
for a short time over-compensated networks (cos
ϕ≤
1) respectively on un-choked com-
pensation-units is not admissible. If this is done nevertheless, overvoltage will occur
(caused by oscillating currents), which may damage all connected components, espe-
cially electronic units like controllers and power feed/feedback units.
•
To low powered or unloaded generators and to regulating transformers it is never al-
lowed to feed back power without a previous consultation of our application depart-
ment. Otherwise unintended voltage rises / excess voltages are generated, which may
damage or destroy REVCON
and combined units!
•
Before operating at nets without reference to neutral ground additional safety meas-
ures (e.g. installation of over voltage suppressors like MOV’s) have to be done. If nec-
essary, please ask for technical support by our technicians.
•
An undisturbed operation of the power feed/feedback unit is only probable, if the fol-
lowing instructions are observed. If these instructions are not observed, tripping of the
unit and damages may occur.