In the HQM 1 and HQM 2 menus, up to 2 internal heat quantity measurements
can be activated and adjusted.
HQM 1 and HQM 2 respectively
Adjustment
channel
Description
Adjustment range / selection
Factory
setting
Sen. flow rate Flow rate sensor selection
US Echo II, SIKA, U/I, FlowRo-
tor, VFS, V40
-
US Echo II
Impuls rate
0.1 … 100.0 l/Imp
1.0 l/Imp
SIKA
Type
VY1030M, VY1030K, VTY20
VTY20
U/I
Voltage or current signal
4-20 mA, 0-10 V
0-10 V
Curve
Curve submenu
Unit
Flow rate unit
m³/h, l/min
l/min
Volt 1
Voltage minimum flow rate (only if
0-10 V has been selected)
0.0 … 10.0 V
1.0 V
Current 1
Current minimum flow rate (only
if 4-20 mA has been selected)
0 … 20 mA
4 mA
Fl.r.1
Minimum flow rate
0.0 … 500.0 l/min
0.0 … 30.0 m³/h
1.0 l/min
1.0 m³/h
Volt 2
Voltage maximum flow rate (only
if 0-10 V has been selected)
0.0 … 10.0 V
10.0 V
Current 2
Current maximum flow rate (only
if 4-20 mA has been selected)
0 … 20 mA
20 mA
Fl.r.2
Maximum flow rate
0.0 … 500.0 l/min
0.0 … 30.0 m³/h
10.0 l/min
10.0 m³/h
FlowRotor
Type
DN20, DN25, DN32
DN20
VFS
Type
2-40, 1-12
2-40
V40
Impuls rate
0.1 … 100.0 l/Imp
1.0 l/Imp
Fluid type
Heat transfer fluid
Tyfocor LS, Ethyl., Propyl., Water Water
Concentr.
Glycol concentration in the heat
transfer fluid (only if fluid type =
propylene glycol or ethylene glycol)
20 … 70 %
40 %
Adjustment
channel
Description
Adjustment range / selection
Factory
setting
Metering
Selection of quantity to be metered Combined, Heat, Cold
Heat
Alternative unit Alternative unit option
Yes, No
No
Unit
Alternative display unit
Coal, Gas, Oil, CO
2
,
€
CO
2
Factor
Conversion factor
0.0000001 … 100.0000000
0.5000000
S0 output
Switch input selection
-
-
Duration
Impulse duration
30 … 120 ms
100 ms
Break
Impulse break
30 … 120 ms
30 ms
Imp/kWh
Impulse rate
1 … 1000
100
Reset
back to factory setting
Yes, No
No
Funct.
Activation / Deactivation
Activated, Deactivated
Activated
S1 is the flow sensor, S2 is the return sensor. If VFS has been selected as the flow
rate sensor, the return temperature is measured automatically via the VFS sensor.
In this case, the return sensor can be changed with the Sen. return parameter.
Depending on the flow rate sensor selected further adjustment channels appear,
see page 12.
In the adjustment channel Fluid type the heat transfer fluid must be selected.
If either propylene glycol or ethylene glycol is selected, the adjustment channel
Concentration is indicated in which the antifreeze ratio of the heat transfer fluid
can be adjusted.
For temperatures below 0 °C a heat transfer fluid with antifreeze is to be used.
The Metering channel is used for selecting whether heat quantity, cold quantity or
both are to be metered.
When the Alternative unit option is activated, the device will convert the en-
ergy quantities into the quantity of fossil fuels (coal, oil or gas) saved, or the CO
2
emission saved respectively. The alternative Unit can be selected. A factor must be
adjusted for the calculation. The conversion factor depends on the arrangement in
use and has to be determined individually.
In the S0 output menu, a digital impulse output can be adjusted for each calorim-
eter, in order to issue the energy metered in form of pulses. The impulse duration,
break and rate can be adjusted.
In order to reset the settings of a calorimeter, select Reset and confirm the secu-
rity enquiry with Yes.
With the menu item Function, a calorimeter already adjusted can be temporarily
deactivated or re-activated respectively. In this case, all adjustments will remain
stored. If a calorimeter is deactivated, energy metering does not take place by this
one. Sensor faults are ignored for the deactivated HQM.