In the submenu “Reports” different messages are indica-
ted. During normal operation, the messages to the left are 
displayed. 

6. Reports

Reports:
back
Everything OK
Version 

Note:

Error messages depend on the error and on the 
sensor type selected previously!

VBus

®

 adjustments.

 

Subaddress:

 

Î

Adjust a subaddress for a WMZ-G1

An individual module address can be adjusted for 
a WMZ-G1. This way, it is possible to use several 
WMZ-G1 with individual addresses in one system. If 
several WMZ-G1 (up to 16 in total are possible) are 
connected to one PC or datalogger, the WMZ-G1 have 
to be numbered serially, starting with 0. The connection 
sequence at the VBus

®

-connection is arbitrary.

Adjustment range: 0 ... 15.

 

Bus mode:

 

Î

Adjust the bus mode

Do not change the factory setting if the WMZ-G1 is 
connected to a RESOL controller with VBus

®

 output 

terminal (corresponds to the bus mode “Passive”). 
Select bus mode “Active”, if the WMZ is not connected 
to a controller and if data are recorded on a PC or 
datalogger.
Select bus mode “Cascaded”, if several WMZ are con-
nected to a PC or datalogger. The WMZ modules are 
serially numbered starting with 0 (see above).
Adjustment range: Active, Passive, Cascaded.

Adj. values:
VBus
Subaddress 

0

Bus mode 

active

Adj. values:
Subaddress 

0

Bus mode 

cascaded

Bus master 

yes

If subaddress “0” and bus mode “Cascaded” are selected, 
adjustments for the bus master have to be made:

 

Bus master:

 

Î

Adjust the bus master

Select bus master “No” when several WMZ-G1 mo-
dules are cascaded and used along with a controller.
Select bus master “Yes” when several WMZ-G1 mo-
dules are cascaded and used without a controller.

VBus

®

 adjustments

Note:

For detailed examples of connection see chap-
ter 7 on page 15 of this manual.

Содержание WMZ-G1

Страница 1: ...OL WMZ G1 Mounting Connection Operation Manual 48005460 48005460 Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit Please keep this m...

Страница 2: ...scription of symbols 2 Disposal 2 Information about the product 2 Technical data and overview of functions 3 VBus board 4 1 Installation 5 1 1 Mounting 5 1 2 Connections 5 1 3 Data communication Bus 5...

Страница 3: ...the number and type of sensors connected the unit is capable to show tempera ture values flow rates and relative or differential pressures or a combina tion of them Heat quantity measurement is possib...

Страница 4: ...theVBus slave board When several WMZ G1 modules are cascaded and connected to a datalogger or PC see p 14 only the VBus master boards of the WMZ G1 modules with the subaddress 1 or higher have to be...

Страница 5: ...equipped with 1 relay to which a load can be connected Relay 1 R1 conductor R1 N neutral line N 12 13 14 grounding The sensors S1 S2 are connected to the following ter minals T 1 2 temperature signal...

Страница 6: ...hed Briefly press button 3 in the relevant menu line for modification of adjustment values change value appears on the display adjust the requested value by pressing buttons 1 and 2 Briefly press butt...

Страница 7: ...eturn temperature heat quantity measurement is not carried out In that case the power is displayed as 0 Briefly press button 3 in order to get back to the main menu 2 3 Initial commissioning Language...

Страница 8: ...sensor 1 in l min m h gallon h Max maximum flow rate at sensor 1 in l min m h gallon h Acc accumulated volume since commissioning last reset in l m or gallons Display of balance values Sensor 2 Tempe...

Страница 9: ...6 bar 0 2 5 bar 0 4 bar 0 6 bar 0 10 bar 0 16 bar 0 25 bar 0 40 bar DPS Range Custom Min 0 00 15 99 bar Max 0 00 16 00 bar 0 0 6 bar 0 1 bar 0 1 6 bar 0 2 5 bar 0 4 bar 0 6 bar 0 10 bar 0 16 bar Adju...

Страница 10: ...epends on the sensor type Therefore the following parameters and adjust ment values depend on the sensor type flow rate forVFS pressure for RPS differential pressure for DPS Adjust the parameters refe...

Страница 11: ...has to be adjusted Adjustment range 0 99 9 bar Heat quantity measurement Heat quantity measurement is carried out by means of the difference between the flow and the return temperature as well as the...

Страница 12: ...hange the factory setting if the WMZ G1 is connected to a RESOL controller with VBus output terminal corresponds to the bus mode Passive Select bus mode Active if the WMZ is not connected to a control...

Страница 13: ...rm Reports Sensor 1 Min d p alarm The differential pressure at sensor 1 has fallen below the adjusted minimum value Signal failure at sensor 1 signal 1 temperature Signal failure at sensor 1 signal 2...

Страница 14: ...Min d p alarm Signal failure at sensor 2 signal 1 temperature Signal failure at sensor 2 signal 2 this can be flow rate relative pressure or differential pressure depending on the sensor type The adju...

Страница 15: ...board subaddress 1 15 bus mode Cascaded The connection sequence at theVBus is arbitrary Cascade with controller controller No adjustments have to be made WMZ G1 module must not be registered WMZ G1 0...

Страница 16: ...requires the approval of RESOL Elektronische Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen G...

Отзывы: