System 12: Solar system with store loading in layers and thermostatic afterheating
The controller compares the temperature at sensor S1 to the temperatures at
sensors S2 and S3. If the measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump (R1) will be activated and
the corresponding store zone will be loaded up to the adjusted store maximum
or set temperature respectively via the valve (R2). The priority logic effects prior
loading of the upper zone of the store.
Afterheating (R3 and R4) can be carried out with a thermostat function (S5). If the
value at S5 reaches the switch-on temperature for the afterheating, the relay is
switched on. If the value exceeds the switch-off temperature for the afterheating,
the relay is switched off again.
Hydraulic variant 1
Hydraulic variant 2
Sensors
S1
Temperature collector
1 / GND
S2
Temperature store
base
2 / GND
S3
Temperature store top 3 / GND
S4
Free
4 / GND
S5
Temperature
afterheating
5 / GND
S6
Free
S6
Relay
R1
Solar pump
R1 / N / PE
R2
Valve solar circuit
R2 / N / PE
R3
Store loading pump
R3 / N / PE
R4
Afterheating
R4 / R4
R3
R2
R1
S2
S3
S1
R4
S5
VBus
VBus
S5/V
40
S4
S3
GND
S6
S7
Sensors
Relais
S2
S1
N
R3
R2
R1
L
R4
PW
M
A
0-10
V
PW
M
B
0-10
V
R4
N
N
N
N
R3
R2
R1
L
1
2
3
4
5
6
7
8
9
10
11
3
3
2
2
2
3
3
2
2
Netz
Mains
Flow direction
when normally open
Содержание DeltaSol SL
Страница 82: ...en 82 82 en...
Страница 83: ...en 83 83 en...