Resol DeltaSol AL Скачать руководство пользователя страница 12

DeltaSol

®

 

AL

|

 

12

© RESOL 10341 deltasol_al.mon

us.ind

d

CMn:

collector minimum temperature
adjustment range:
10 ... 90 °C
50 ... 200 [°F]
factory setting:
10 °C; 50 [°F]

Option collector minimum limitation

OCn: 

collector minimum limitation 
adjustment range: OFF / ON 
factory setting: OFF

The collector minimum limitation option prevents the solar 
pump from being switched on too often at low collector 
temperatures. When this option is activated, the collector 
minimum temperature can be adjusted.
The collector minimum temperature is the temperature 
which must be exceeded for the solar pump (R1) to switch 
on. If the temperature falls below the minimum temperature, 

 (flashing) is shown.

CFR:
antifreeze temperature
adjustment range:
-10 ...  10 °C
10 ... 50 [°F]
factory setting:
4.0 °C; 40 [°F]

Antifreeze option

OCF: 
antifreeze function 
adjustment range: OFF  / ON 
factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the tank when the temperature falls below 
the adjusted antifreeze temperature at the collector sensor. 
This will protect the fluid against freezing or coagulating. 
When this option is activated, the antifreeze temperature 
can be adjusted.
If the adjusted antifreeze temperature is exceeded by 1 °C 
(2 °Ra), the loading circuit will be deactivated. 

Option recooling

If the adjusted maximum tank temperature (

S MX

) is 

reached, the controller keeps the solar pump running in 
order to prevent the collector from being overheated. 
The tank temperature may increase, but only up to 95 °C 
(200 °F) (emergency shutdown of the tank).
If the tank temperature is higher than the maximum tank 
temperature (

S MX

) and if the collector temperature is at 

least 5 K (10 °Ra) below the tank temperature, the solar 
system remains activated until the tank is cooled down 
below the adjusted maximum tank temperature (

S MX

via the collec tor and the pipework. 

OREC:

option recooling 
adjustment range: OFF  /  ON 
factory setting: OFF

note: 

 

Since this function uses the limited heat quantity 
of the tank, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.

if the OREC option is additionally activated:

If the tank temperature is higher than the maximum tank 
temperature (

S MX

) and if the collector temperature is at 

least 5 K (10 °Ra) below the tank temperature, the solar 
system remains activated until the tank is cooled down 
below the adjusted maximum temperature (

S MX

) via the 

collector and the pipework. 
If the system cooling function is activated,   (flashing) is shown.
Due to the cooling function, the system will have a longer 
operation time on hot summer days and guarantees thermal 
relief of the collector field and the heat transfer fluid.

Содержание DeltaSol AL

Страница 1: ...L product Please read this manual carefully to get the best performance from this unit Please keep this manual carefully RESOL DeltaSol AL Mounting Connection Operation Troubleshooting Examples Manual...

Страница 2: ...contents Advice 2 1 Overview 3 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 5 2 3 Data communication Bus 5 2 4 Terminal allocation 6 3 Operation 6 3 1 Buttons for adjustment 6 3 2 System...

Страница 3: ...tem states background illumination and operating control lamp Operation 3 push buttons at the front of the housing and 1 slide switch Functions Differential temperature controller for standard solar t...

Страница 4: ...ver Mark the upper fastening point on the wall Drill and fasten the enclosed wall plug and screw leaving the head protruding Hang the housing from the upper fastening point and mark the lower fastenin...

Страница 5: ...erminal 12 conductor R1 R normally closed contact 13 conductor R1 A normally open contact 14 neutral conductor N Depending on the product version power supply cable and sensor cables are already conne...

Страница 6: ...ards through the display menu or to increase the adjustment values Button 2 is similarly used for scrolling forward and reducing values In order to access the adjustment mode scroll down in the displa...

Страница 7: ...e indication is set to F and Ra the units are not displayed 3 2 1 Channel display Channel display 3 2 2 Tool bar The additional symbols in the tool bar indicate the current system state Tool bar 3 2 S...

Страница 8: ...ing OK red green flashing initialization phase manual operation red flashing Sensor defective sensor symbol is flashing quickly 3 4 Flashing codes 3 4 2 LED flashing codes 3 4 1 System Screen flashing...

Страница 9: ...mperature TST tank temperature TST tank temperature display range 40 260 C 40 500 F Display sensor 3 Shows the current temperature of the additional sensor without control function S3 temperature sens...

Страница 10: ...n are used for determining the heat quantity delivered It is shown in kWh in the channel kWh and in MWh in the channel MWh The overall heat quantity results from the sum of both values The accumulated...

Страница 11: ...Ra Collector temperature limitation for emergency shutdown of the collector If the adjusted collector emergency shutdown temperature EM is exceeded the controller switches off the solar pump in order...

Страница 12: ...cuit will be deactivated Option recooling If the adjusted maximum tank temperature S MX is reached the controller keeps the solar pump running in order to prevent the collector from being overheated T...

Страница 13: ...In this adjustment channel the menu language can be chosen dE German En English It Italian Fr French LANG language selection adjustment range dE En It Fr factory setting En Temperature units In this...

Страница 14: ...resistance values corresponding to different temperatures are listed yes Check the supply line and reconnect it If a malfunction occurs an error code will be indicated on the display by means of symb...

Страница 15: ...Heat exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the tube collector function Change Ton and Toff correspondingly Switch o...

Страница 16: ...Does the pump start up in manual operation yes No current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which make...

Страница 17: ...the data issued by the controller collector and tank temperature as well as heat quantity produced in the solar system The use of high efficient LEDs and antireflective filter glass assures a high opt...

Страница 18: ...DeltaSol AL 18 RESOL 10341 deltasol_al monus indd Notes...

Страница 19: ...DeltaSol AL 19 RESOL 10341 deltasol_al monus indd Notes...

Страница 20: ...f RESOL Elektronische Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice Th...

Отзывы: