Resol DeltaSol AL Скачать руководство пользователя страница 11

DeltaSol

®

 

AL

11 

|

© RESOL 10341 deltasol_al.mon

us.ind

d

CMX: 

collector maximum temperature
adjustment range:
100 ... 190 °C
210 ... 380 [°F]
factory setting:
120 °C; 250 [°F]
hysteresis: 5 K (10 °Ra)

System cooling 

When the adjusted maximum tank temperature is reached, 
the system stagnates. As soon as  the collector tempera-
ture reaches the adjusted maximum collector temperature 
(

CMX

) the solar pump is activated until the collector 

temperature is 5 K (10 °Ra) lower than the maximum tem-
perature. The tank temperature may increase, but only up to 
95 °C (200 °F) (emergency shutdown of the tank).

OCX

option system cooling
adjustment range: OFF / ON
factory setting: OFF

Maximum tank temperature 

Once the adjusted maximum temperature is exceeded, the 
solar pump is switched off and further loading of the tank 
is prevented to reduce scald risk or system damage. The   
symbol is shown on the display.

S MX

maximum tank temperature
adjustment range:
4 ... 95 °C
40 ... 200 [°F]
factory setting:
60 °C; 140 [°F]
hysteresis: 2 K (4 °Ra)

Collector temperature limitation for emergency 

shutdown of the collector

If the adjusted collector emergency shutdown temperature 
(

EM

) is exceeded, the controller switches off the solar 

pump in order to protect the system against overheating. 
The factory setting is 140 °C (280 °F) but it can be changed 
within the adjustment range of 110 ... 200 °C (230 ... 400 °F). 

 (flashing) is shown if 

EM

 is exceeded.

EM

:

collector temperature limita-
tion
adjustment range:
110 ... 200 °C 
230 ... 400 [°F]
factory setting:
140 °C; 280 [°F]
hysteresis: 10 K (20 °Ra)

note:

 

The controller is also equipped with a nonadjust-
able emergency switch-off if the tank reaches 
95  °C (200 °F).

T-regulation 

DT O

switch-on temperature dif-
ference
adjustment range:
1.0 ... 20.0 K
2.0 ... 40.0 [°Ra]
factory setting:
6.0 K; 8.0 [°Ra]

If the switch-on difference (

DT O

) is reached, the pump 

is activated. If the temperature difference falls below the 
adjusted switch-off temperature difference (DT F) the 
controller switches off.

note:

 

The switch-on temperature difference must be 
at least 0.5 K (1 °Ra) higher than the switch-off 
temperature difference.

DT F:
switch-off temperature dif-
ference
adjustment range:
0.5 ... 19.5 K
1.0 ... 39.0 [°Ra]
factory setting:
4.0 K; 8.0 [°Ra]

Содержание DeltaSol AL

Страница 1: ...L product Please read this manual carefully to get the best performance from this unit Please keep this manual carefully RESOL DeltaSol AL Mounting Connection Operation Troubleshooting Examples Manual...

Страница 2: ...contents Advice 2 1 Overview 3 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 5 2 3 Data communication Bus 5 2 4 Terminal allocation 6 3 Operation 6 3 1 Buttons for adjustment 6 3 2 System...

Страница 3: ...tem states background illumination and operating control lamp Operation 3 push buttons at the front of the housing and 1 slide switch Functions Differential temperature controller for standard solar t...

Страница 4: ...ver Mark the upper fastening point on the wall Drill and fasten the enclosed wall plug and screw leaving the head protruding Hang the housing from the upper fastening point and mark the lower fastenin...

Страница 5: ...erminal 12 conductor R1 R normally closed contact 13 conductor R1 A normally open contact 14 neutral conductor N Depending on the product version power supply cable and sensor cables are already conne...

Страница 6: ...ards through the display menu or to increase the adjustment values Button 2 is similarly used for scrolling forward and reducing values In order to access the adjustment mode scroll down in the displa...

Страница 7: ...e indication is set to F and Ra the units are not displayed 3 2 1 Channel display Channel display 3 2 2 Tool bar The additional symbols in the tool bar indicate the current system state Tool bar 3 2 S...

Страница 8: ...ing OK red green flashing initialization phase manual operation red flashing Sensor defective sensor symbol is flashing quickly 3 4 Flashing codes 3 4 2 LED flashing codes 3 4 1 System Screen flashing...

Страница 9: ...mperature TST tank temperature TST tank temperature display range 40 260 C 40 500 F Display sensor 3 Shows the current temperature of the additional sensor without control function S3 temperature sens...

Страница 10: ...n are used for determining the heat quantity delivered It is shown in kWh in the channel kWh and in MWh in the channel MWh The overall heat quantity results from the sum of both values The accumulated...

Страница 11: ...Ra Collector temperature limitation for emergency shutdown of the collector If the adjusted collector emergency shutdown temperature EM is exceeded the controller switches off the solar pump in order...

Страница 12: ...cuit will be deactivated Option recooling If the adjusted maximum tank temperature S MX is reached the controller keeps the solar pump running in order to prevent the collector from being overheated T...

Страница 13: ...In this adjustment channel the menu language can be chosen dE German En English It Italian Fr French LANG language selection adjustment range dE En It Fr factory setting En Temperature units In this...

Страница 14: ...resistance values corresponding to different temperatures are listed yes Check the supply line and reconnect it If a malfunction occurs an error code will be indicated on the display by means of symb...

Страница 15: ...Heat exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the tube collector function Change Ton and Toff correspondingly Switch o...

Страница 16: ...Does the pump start up in manual operation yes No current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which make...

Страница 17: ...the data issued by the controller collector and tank temperature as well as heat quantity produced in the solar system The use of high efficient LEDs and antireflective filter glass assures a high opt...

Страница 18: ...DeltaSol AL 18 RESOL 10341 deltasol_al monus indd Notes...

Страница 19: ...DeltaSol AL 19 RESOL 10341 deltasol_al monus indd Notes...

Страница 20: ...f RESOL Elektronische Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice Th...

Отзывы: