background image

7

en

The antifreeze function activates the loading circuit between 
the collector and the tank when the collector temperature 
falls  below  +4 °C / 39,2 °F. This  will  protect  the  fluid  against 
freezing or coagulating. If the temperature at S1 reaches 
+5 °C / 41 °F, the pump will be switched off.
When the antifreeze function is active, the operating control 
lamp flashes quickly.

Examples

4.1 

Standard solar system with 1 tank

S1

RO

S2

 Use the grounding terminal!

The controller calculates the temperature difference between collector sensor 
S1 and tank sensor S2. If the difference is larger than or identical to the adjusted 
switch-on temperature difference, the pump (R1) will be switched on and the tank 
will be loaded. If the temperature difference falls by 1.6 K / 2.9 °Ra (non-adjustable 
hysteresis) below the adjusted temperature difference, the pump will be switched 
off.
S1  =  Collector sensor
S2  =  Tank sensor
RO  =  Solar pump

S1 

S2 

2  3  4 

RO RC  N  N  L 

8  9  10  11 

2

2

3

3

Power 
supply

4.2 

Switch-on temperature difference

Adjustment  range:  2 … 16 K
Factory setting: 6 K 

The controller calculates the temperature difference between 
the temperature sensors S1 and S2. If the difference is larger 
than or identical to the adjusted nominal value, the relay will 
be switched on. The operating control LED is green. If the 
temperature difference falls by 1.6 K / 2.9 °Ra (non-adjustable 
hysteresis) below the nominal value, the relay will be switched 
off.

4.3 

Antifreeze function

Deactivated by default

Note
Since this function uses the limited heat quantity of the tank, the anti-
freeze function should be used in regions with few days of temperatures 
around the freezing point.

Содержание DeltaSol A

Страница 1: ...arefully to get the best performance from this unit Please keep this manual safe DeltaSol A Mounting Connection Operation Troubleshooting Differential temperature controller for solar heating air cond...

Страница 2: ...d to strong electromagnetic fields Subject to technical change Errors excepted Target group These instructions are exclusively addressed to authorized skilled personnel Only qualified electricians are...

Страница 3: ...cone sealing cord guarantees a protection against dripping water 130 45 Drill hole positions 112 mm Contents 1 Overview 4 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 6 3 Operation and fu...

Страница 4: ...LED Operation 1 potentiometer and 1 jumper Protection type IP 20 DIN EN 60529 with seal IP 22 Protection class II Ambient temperature 0 40 C 32 104 F Degree of pollution 2 Dimensions 139 mm 5 2 depth...

Страница 5: ...to the wall carry out the following steps 2 2 1 112mm 2 4 5 6 7 3 8 T4A fuse Power supply connection Relay load Grounding terminal common terminal block Jumper antifreeze function Potentiometer Temper...

Страница 6: ...th power via a power supply cable The power supply of the device must be 115V The controller is equipped with 1 electromechanical relay to which a load such as a pump a valve etc can be connected Rela...

Страница 7: ...rature difference falls by 1 6K 2 9 Ra non adjustable hysteresis below the adjusted temperature difference the pump will be switched off S1 Collector sensor S2 Tank sensor RO Solar pump 1 S1 S2 2 3 4...

Страница 8: ...usted temperature difference the valve will be put into its initial position S1 Tank sensor S2 Heating circuit return sensor RO 3 port valve S1 RO S2 1 S1 S2 2 3 4 7 RO RC N N L 8 9 10 11 2 2 3 3 Powe...

Страница 9: ...econ nect it The fuse of the controller could be blown The fuse holder which holds the spare fuse becomes accessible when the cover is removed The fuse can then be replaced Check the power supply of t...

Страница 10: ...10 en...

Страница 11: ...11 en...

Страница 12: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: