VR8300 CONTINUOUS PILOT COMBINATION GAS CONTROL

69-0668—05

6

Table 7. Maximum Length of Supplementary Limit Leadwires in in. (m) When Using Q390/Q340 Thermocouple.

START-UP AND CHECKOUT

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury, or 

death.

1. Do not force the gas control knob. Use only 

your hand to push down the reset button or turn 

the gas control knob. Never use any tools.

2. If the gas control knob or reset button does not 

operate by hand, or if the reset button stays 

depressed after it is released, the gas control 

should be replaced by a qualified service 

technician.

Gas Control Knob Settings

The gas control knob has three settings:

OFF: prevents pilot and main burner gas flow.

PILOT: permits pilot gas flow only. Gas control 

knob must be held depressed or thermocouple 

must be heated sufficiently to hold the safety 

control valve open.

ON: permits main burner and pilot gas flow. Gas 

control and thermostat controls the main 

burner gas flow.

NOTE:

Gas controls are shipped with the gas control 

knob in the ON position.

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury, or 

death

Check for gas leaks with rich soap and water 

solution any time work is done on a gas control.

Gas Leak Test

1.

Paint the pipe connections upstream of the gas 

control with a rich soap and water solution. Bub-

bles indicate a gas leak.

2.

If a leak is detected, tighten the pipe connection.

3.

Stand clear while lighting the main burner to pre-

vent injury caused from hidden gas leaks that 

could cause flashback in the appliance vestibule. 

Light the main burner.

4.

With the main burner in operation, paint pipe joints 

(including adapters) and gas control inlet and out-

let with rich soap and water solution.

5.

If another leak is detected, tighten the adapter 

screws, joints, and pipe connections.

6.

Replace the part if gas leak cannot be stopped.

Light Pilot Burner Flame

1.

Turn the gas control knob clockwise 

 to OFF. 

Wait five minutes to dissipate any unburned gas. 

Sniff around the appliance near the floor. Do not 

relight the pilot flame if you smell gas.

2.

Turn the gas control knob counterclockwise 

 

to PILOT. Push down and hold the gas control knob 

while lighting the pilot flame.

3.

Hold the gas control knob down about one minute, 

then release.

a. If the pilot flame goes out, turn the gas control 

knob clockwise 

 

to OFF and repeat steps 

1 through 3.

b. If pilot flame remains lit, turn the gas control 

knob counterclockwise 

 

to ON.

Adjust Pilot Burner Flame

The pilot flame should envelop 3/8 to 1/2 in. (10 to 13 

mm) of the thermocouple tip. See Fig. 10.

To adjust the pilot flame:

1.

Remove the pilot adjustment cover screw. See 

Fig. 1.

2.

Turn the inner adjustment screw clockwise 

 

to decrease or counterclockwise 

 

to increase 

the pilot flame.

3.

Always replace the cover screw after adjustment 

and tighten firmly to ensure proper operation.

Fig. 10. Proper flame adjustment.

Light Main Burner

Follow the appliance manufacturer instructions or set the 

thermostat setpoint 10°F (6°C) above the room 

temperature to call for heat.

Thermocouple Length

Maximum Leadwire Length x 2 (Wires)

AWG No. 14

AWG No. 16

AWG No. 18

in.

in.

in.

in.

in.

in.

in.

in.

12

0.3

47

1.2

30

0.8

18

0.5

18

0.5

41

1.0

26

0.7

16

0.4

24

0.6

35

0.6

22

0.6

14

0.4

30

0.8

29

0.8

18

0.5

11

0.3

36

0.9

23

0.6

15

0.4

9

0.2

40

1.0

19

0.5

12

0.3

7

0.2

48

1.2

11

0.3

7

0.2

60

1.5

DO NOT USE

M3086C

PROPER FLAME

ADJUSTMENT

3/8 TO 1/2 IN.

(10 TO 13 MM)

THERMOCOUPLE

Содержание VR8300A

Страница 1: ...equency 24 Vac 50 60 Hz Current Draw 0 70A Table 1 Temperature Range and Regulatory Type Table 2 Capacity a Capacity based on 1000 Btu cu ft 0 64 specific gravity natural gas at 1 in wc pressure drop 37 3 MJ cu m 0 64 specific gravity natural gas at 0 25 kPa pressure drop Use conversion factors in Table 3 to convert capacities for other gases Table 3 Gas Capacity Conversion Factors Table 4 Flange ...

Страница 2: ... if available otherwise use the instructions provided below Converting Between Natural Gas and LP Gas If needed convert valve between Natural and LP gas WARNING Fire or Explosion Hazard Can cause property damage severe injury or death 1 Do not use a gas control set for natural gas on LP gas or a gas control set for LP gas on natural gas 2 When making the conversion the main and pilot burner orific...

Страница 3: ...rol following the same precautions and instructions that are used for installing the gas control After the adapter is installed the gas control is attached to the adapter as outlined above Note that using an adapter increases the overall length of the gas control Choose Gas Control Location Do not locate the gas control where it can be affected by steam cleaning high humidity dripping water corros...

Страница 4: ...Do not bend tubing within 3 inches of the gas control or pilot burner after compression fitting is tightened because this can result in gas leakage at the connection 2 Square off and remove the burrs from the end of the tubing 3 Unscrew the compression fitting from the pilot out let Fig 1 Slip the compression fitting over the tubing and slide out of the way NOTE When replacing a gas control cut of...

Страница 5: ...r servicing All wiring must comply with applicable electrical codes and ordinances Refer to the appliance manufacturer instructions if available or use the following procedure 1 Check the power supply rating on the gas control and make sure it matches the available supply Install the transformer thermostat and other con trols as required 2 Connect the control circuit to the gas control termi nals ...

Страница 6: ...he main burner in operation paint pipe joints including adapters and gas control inlet and out let with rich soap and water solution 5 If another leak is detected tighten the adapter screws joints and pipe connections 6 Replace the part if gas leak cannot be stopped Light Pilot Burner Flame 1 Turn the gas control knob clockwise to OFF Wait five minutes to dissipate any unburned gas Sniff around th...

Страница 7: ...ary adjust the pressure regulator to match the appliance rating Refer to Table 7or 8 for the factory set nominal outlet pressures and adjustment ranges a Remove the pressure regulator adjustment cap and screw b Use a screwdriver to turn the inner adjustment screw clockwise to increase or counter clockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to...

Страница 8: ...utdown before re energizing step opening model to ensure light off at step pressure If Pilot Burner Flame does not Light 1 Make sure that the main gas supply valve is open and the pilot gas supply line is purged of air 2 Light the pilot burner flame following procedures in Light the Pilot Burner Flame section If pilot burner flame does not light a Check the pilot gas adjustment screw If closed rea...

Страница 9: ...ng 2 Disconnect all electric power to the appliance 3 Remove the gas control access panel 4 Push in the gas control knob slightly and turn clockwise to OFF NOTE The gas control knob cannot be turned from PILOT to OFF unless it is pushed in slightly Do not force the gas control knob 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow the instructions in step 3 IF YOU...

Страница 10: ...VR8300 CONTINUOUS PILOT COMBINATION GAS CONTROL 69 0668 05 10 ...

Страница 11: ...VR8300 CONTINUOUS PILOT COMBINATION GAS CONTROL 11 69 0668 05 ...

Страница 12: ...chnologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 0668 05 M S Rev 06 20 Printed in United States ...

Отзывы: