VR8300 CONTINUOUS PILOT COMBINATION GAS CONTROL

69-0668—05

4

3.

Install sediment trap in the supply line to the gas 

control. See Fig. 4.

Fig. 4. Sediment trap installation.

Install Gas Control

To install:

1.

Mount the gas control 0 to 90 degrees, in any 

direction, from the upright position of the gas con-

trol knob, including vertically.

2.

Mount the gas control so the gas flow is in the 

direction of the arrow on the bottom of the gas 

control.

3.

Thread pipe the amount shown in Table 5 for inser-

tion into the gas control. Do not thread pipe too far. 

Valve distortion or malfunction can result if the 

pipe is inserted too deeply into the gas control. See 

Fig. 5.

Fig. 5. Use moderate amount of pipe compound.

Table 5. NPT Pipe Thread Length in in.

IMPORTANT

On LP installations, use compound resistant to 

LP gas. Do not use Teflon tape.

4.

Apply a moderate amount of good quality pipe 

compound (DO NOT use Teflon tape) to pipe only, 

leaving two end threads bare. On LP installations, 

use compound resistant to LP gas.

5.

Remove seals over the gas control inlet and outlet 

if necessary.

6.

Connect the pipe to the gas control inlet and outlet. 

Use a wrench on the square ends of the gas con-

trol. If an adapter is used, place the wrench on the 

adapter rather than the gas control. Refer to Fig. 1 

and 6.

Fig. 6. Proper use of wrench on gas control.

Connect Pilot Gas Tubing

1.

Cut tubing to desired length and bend as necessary 

for routing to pilot burner. Do not make sharp 

bends or deform the tubing. Do not bend tubing 

within 3 inches of the gas control or pilot burner 

after compression fitting is tightened, because this 

can result in gas leakage at the connection.

2.

Square off and remove the burrs from the end of 

the tubing.

3.

Unscrew the compression fitting from the pilot out-

let (Fig. 1). Slip the compression fitting over the 

tubing and slide out of the way.

NOTE:

When replacing a gas control, cut off the old 

compression fitting and replace with the new 

compression fitting provided on the gas control. 

Never use the old compression fitting as it may 

not provide a gas-tight seal.

4.

Push tubing into the pilot gas tapping on the outlet 

end of the control until it bottoms. While holding 

the tubing all the way in, slide the compression fit-

ting into place and engage threads—turn until fin-

ger-tight. Then tighten one more turn with wrench. 

Do not overtighten. Refer to Fig. 7.

Pipe Size

Thread Pipe 

this Amount

Maximum Dept Pipe can be 

Inserted into Control

3/8 in.

9/16 in.

3/8 in.

1/2 in.

3/4 in.

1/2 in.

3/4 in.

13/16 in.

3/4 in.

GAS

CONTROL

 

GAS

CONTROL

HORIZONTAL

DROP

PIPED

GAS

SUPPLY

PIPED

GAS

SUPPLY

3 IN.

(76 MM)

MINIMUM

3 IN.

(76 MM)

MINIMUM

RISER

GAS

CONTROL

TUBING

GAS

SUPPLY

HORIZONTAL

DROP

3 IN.

(76 MM)

MINIMUM

RISER

M3077B

2

1

2

2

1

2

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

CAUTION:  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING

END CAP TO PREVENT GAS FROM FILLING THE WORK AREA.  TEST 

FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

TWO IMPERFECT 

THREADS

GAS CONTROL

THREAD PIPE THE AMOUNT 

SHOWN IN TABLE FOR 

INSERTION INTO GAS CONTROL 

APPLY A MODERATE AMOUNT OF

PIPE COMPOUND TO PIPE ONLY

(LEAVE TWO END THREADS BARE).

M3075C

PIPE

APPLY WRENCH

TO FLANGE ONLY

M16012A

Содержание VR8300A

Страница 1: ...equency 24 Vac 50 60 Hz Current Draw 0 70A Table 1 Temperature Range and Regulatory Type Table 2 Capacity a Capacity based on 1000 Btu cu ft 0 64 specific gravity natural gas at 1 in wc pressure drop 37 3 MJ cu m 0 64 specific gravity natural gas at 0 25 kPa pressure drop Use conversion factors in Table 3 to convert capacities for other gases Table 3 Gas Capacity Conversion Factors Table 4 Flange ...

Страница 2: ... if available otherwise use the instructions provided below Converting Between Natural Gas and LP Gas If needed convert valve between Natural and LP gas WARNING Fire or Explosion Hazard Can cause property damage severe injury or death 1 Do not use a gas control set for natural gas on LP gas or a gas control set for LP gas on natural gas 2 When making the conversion the main and pilot burner orific...

Страница 3: ...rol following the same precautions and instructions that are used for installing the gas control After the adapter is installed the gas control is attached to the adapter as outlined above Note that using an adapter increases the overall length of the gas control Choose Gas Control Location Do not locate the gas control where it can be affected by steam cleaning high humidity dripping water corros...

Страница 4: ...Do not bend tubing within 3 inches of the gas control or pilot burner after compression fitting is tightened because this can result in gas leakage at the connection 2 Square off and remove the burrs from the end of the tubing 3 Unscrew the compression fitting from the pilot out let Fig 1 Slip the compression fitting over the tubing and slide out of the way NOTE When replacing a gas control cut of...

Страница 5: ...r servicing All wiring must comply with applicable electrical codes and ordinances Refer to the appliance manufacturer instructions if available or use the following procedure 1 Check the power supply rating on the gas control and make sure it matches the available supply Install the transformer thermostat and other con trols as required 2 Connect the control circuit to the gas control termi nals ...

Страница 6: ...he main burner in operation paint pipe joints including adapters and gas control inlet and out let with rich soap and water solution 5 If another leak is detected tighten the adapter screws joints and pipe connections 6 Replace the part if gas leak cannot be stopped Light Pilot Burner Flame 1 Turn the gas control knob clockwise to OFF Wait five minutes to dissipate any unburned gas Sniff around th...

Страница 7: ...ary adjust the pressure regulator to match the appliance rating Refer to Table 7or 8 for the factory set nominal outlet pressures and adjustment ranges a Remove the pressure regulator adjustment cap and screw b Use a screwdriver to turn the inner adjustment screw clockwise to increase or counter clockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to...

Страница 8: ...utdown before re energizing step opening model to ensure light off at step pressure If Pilot Burner Flame does not Light 1 Make sure that the main gas supply valve is open and the pilot gas supply line is purged of air 2 Light the pilot burner flame following procedures in Light the Pilot Burner Flame section If pilot burner flame does not light a Check the pilot gas adjustment screw If closed rea...

Страница 9: ...ng 2 Disconnect all electric power to the appliance 3 Remove the gas control access panel 4 Push in the gas control knob slightly and turn clockwise to OFF NOTE The gas control knob cannot be turned from PILOT to OFF unless it is pushed in slightly Do not force the gas control knob 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow the instructions in step 3 IF YOU...

Страница 10: ...VR8300 CONTINUOUS PILOT COMBINATION GAS CONTROL 69 0668 05 10 ...

Страница 11: ...VR8300 CONTINUOUS PILOT COMBINATION GAS CONTROL 11 69 0668 05 ...

Страница 12: ...chnologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 0668 05 M S Rev 06 20 Printed in United States ...

Отзывы: