OPERATION 

The operation of the pilot safety system is accomplished by 
manipulation of a knob, provided with programming symbols 
that indicate lighting and shutt off.

 

Lighting

 

•  Depress knob and hold it down.

 

•  Ignite pilot burner.

 

•  Hold knob down for 20 seconds, after pilot burner has 

been lit.

 

•  Release knob.

 

•  Wait at least three minutes before a second attempt to light 

the pilot burner is made, when pilot flame has not been 
established.

 

Shut off

 

In order to interrupt all gas flow through the gas control, knob 
must be turned clockwise to its stop.

 

After release the knob will automatically rotate to its ready 
position.

 

IMPORTANT

 

A safety latching device prevents the knob from 
being fully depressed until the thermocouple has 
cooled down sufficiently to de

energize the power 

unit, after which the knob will be effective again.

 

When the knob is depressed during latch position, 
pilot gas will flow to pilot burner. However, when 
knob is released, pilot gas extinguishes and main 
gas supply is not affected.

 

Wait one minute after shut off before starting lighting 
procedure.

 

ADJUSTMENTS AND CHECKOUT 

    

WARNING 

Adjustments must be made by qualified persons only. 
If the appliance manufacturer supplies checkout and/ 
or service and maintenance instructions carefully

 

To ensure a safe closing of the valve, it is essential 
that voltage over the terminals of electric on/off servo 
operator is reduced to 0 Volt.

 

Pressure tap

 

The gas control is provided with a pressure tap of 9 mm outer 
diameter at inlet and outlet side.

 

When checking the pressure undo the screw a half turn and 
slip tube over nipple.

 

Ensure that screw is retightened after making test.

 

Pilot flame adjustment (see fig. 1.)

 

The gas control is packed for shipment with pilot flow at 
maximum. Refer to the pilot burner manufacturer’s 
instructions for recommended size of pilot flame.

 

If adjustment is required turn pilot flow adjustment screw 
clockwise to decrease or counter clockwise to increase pilot 
flame.

 

Outlet pressure adjustment (see fig. 1.)

 

•  Energize electric on/off servo operator in order to have gas 

input to burner.

 

•  Check input to the appliance using a clocking gas meter or 

alternatively a pressure gauge connected to the outlet 
pressure tap.

 

•  Open cap to expose throttle adjustment screw.

 

•  Turn the flow adjustment screw with a screw driver 

either 

way 

until the burner pressure required is recorded on the 

pressure gauge.

 

•  Close cap.

 

Check of slow opening (softlite)

 

The softlite pressure is factory set.

 

Check burner performance at this pressure observing burner 
ignition and flame characteristics.

 

Burner should ignite promptly and without flash back to orifice 
and all ports should remain lit.

 

Cycle burner several times (wait 10 seconds between cycles 
to allow servo system to resume slow open action).

 

Repeat check of slow opening after allowing the appliance to 
cool down.

 

Checkout

 

Set appliance in operation after any adjustment and observe 
several complete cycles to ensure that all burner components 
function correctly.

 

Maintenance and service

 

Under normal circumstances no maintenance or service is 
required.

 

Screws on the valve that have been sealed must never be 
removed.

 

 

 

 

 

Resideo Pittway Sàrl 

Z.A. La Pièce 4 

1180 Rolle 

Switzerland

 

 
 
 

 

TR 

TH 

Содержание V4600

Страница 1: ...electric safety device according to european standards EN 125 and EN 126 and closes off the gas supply to both main burner and pilot burner The electric on off servo operator is an automatic shut off valve of class J according to EN 161 and closes off the gas supply to the main burner SPECIFICATIONS Models V4600 serie 220 240 V 50 Hz V8600 serie 24 V 50 Hz Suffix E fast opening and throttle valve ...

Страница 2: ...uding cover IP 40 with cover or plug IP 44 with plug according to DIN 43650 INSTALLATION IMPORTANT Take care that installer is a trained experienced service person Turn off gas supply before starting installation Disconnect power supply to prevent electrical shock and or equipment damage Do not remove seals over gas control inlet and outlet until the device is ready to be installed Working voltage...

Страница 3: ...With the main burner in operation paint all pipe joints including adapters and gas control inlet and outlet with with a rich soap and water solutionan approved leak detection fluid If another gas leak is detected tighten adapter screws joints and pipe connections Replace the part if gas leak can not be stopped CAUTION Keep soap and water solution away from electrical connections Electrical connect...

Страница 4: ...0 Volt Pressure tap The gas control is provided with a pressure tap of 9 mm outer diameter at inlet and outlet side When checking the pressure undo the screw a half turn and slip tube over nipple Ensure that screw is retightened after making test Pilot flame adjustment see fig 1 The gas control is packed for shipment with pilot flow at maximum Refer to the pilot burner manufacturer s instructions ...

Отзывы: