resideo V4600 Скачать руководство пользователя страница 2

EN1R

9099 2040R8

NE 

 

 

 

 

Fig. 1. Dimensions and adjustment points

 

 

Electrical data 

 
 
 

 

Timing

 

Closing time: 2 s

 

Dead time:  Suffix E: < 5 s

 

Suffix T: < 6 s 

Opening time:

 

Suffix E: 1 s from start of flow till 50% of outlet pressure. 
Suffix T: 1.5 s from start of flow till softlite pressure

 

Enclosure (including cover)

 

IP 40 (with cover or plug)

 

IP 44 (with plug according to DIN 43650

 

INSTALLATION 

IMPORTANT

 

Take care that installer is a trained experienced 
service person.

 

Turn off gas supply before starting installation.

 

Disconnect power supply to prevent electrical shock 
and/or equipment damage.

 

Do not remove seals over gas control inlet and outlet 
until the device is ready to be installed.

 

Working voltage

 

Current (mA)

 

Power consumption 
(W)

 

220/240 V, 50 Hz

 

20.4/24

 

3.4/4.5

 

24 V, 50 Hz

 

211

 

3.8

 

 

Содержание V4600

Страница 1: ...electric safety device according to european standards EN 125 and EN 126 and closes off the gas supply to both main burner and pilot burner The electric on off servo operator is an automatic shut off valve of class J according to EN 161 and closes off the gas supply to the main burner SPECIFICATIONS Models V4600 serie 220 240 V 50 Hz V8600 serie 24 V 50 Hz Suffix E fast opening and throttle valve ...

Страница 2: ...uding cover IP 40 with cover or plug IP 44 with plug according to DIN 43650 INSTALLATION IMPORTANT Take care that installer is a trained experienced service person Turn off gas supply before starting installation Disconnect power supply to prevent electrical shock and or equipment damage Do not remove seals over gas control inlet and outlet until the device is ready to be installed Working voltage...

Страница 3: ...With the main burner in operation paint all pipe joints including adapters and gas control inlet and outlet with with a rich soap and water solutionan approved leak detection fluid If another gas leak is detected tighten adapter screws joints and pipe connections Replace the part if gas leak can not be stopped CAUTION Keep soap and water solution away from electrical connections Electrical connect...

Страница 4: ...0 Volt Pressure tap The gas control is provided with a pressure tap of 9 mm outer diameter at inlet and outlet side When checking the pressure undo the screw a half turn and slip tube over nipple Ensure that screw is retightened after making test Pilot flame adjustment see fig 1 The gas control is packed for shipment with pilot flow at maximum Refer to the pilot burner manufacturer s instructions ...

Отзывы: