S89E,F DIRECT SPARK IGNITION CONTROL MODULE

3

68-0066—05

Fig. 1. S89 dimensions in in. (mm).

INSTALLATION

When Installing This Product…

1.

Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.

2.

Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property damage.

1. Disconnect power supply before wiring to avoid 

electrical shock, explosion, or equipment damage.

2. If a new gas control is being installed, turn off gas 

supply before starting installation. Conduct Gas 
Leak Test after gas control is installed.

3. In an LP gas installation, remember that LP gas is 

heavier than air and will not vent upward naturally. 
Do not operate electric switches, lights, or 
appliances until you are sure that work area is free 
of gas.

4. Never install an S89 where water can flood, drip, or 

condense on the device. It can malfunction if it gets 
wet.

5. Never try to use a device that has been damp or 

wet—replace it.

6. If the control might be exposed to water or moisture, 

install it in a suitable waterproof enclosure.

7. Any replacement S89 must have the same or shorter 

lockout time 

and

 the same or longer delay timing as 

the original control.

Replacement Application Requirements

If this is a replacement application, follow the appliance 
manufacturer instructions, if available. The manufacturer 
usually provides wiring diagrams, start-up and checkout 
instructions, and service procedures for their appliance. If the 
manufacturer instructions are not available, use the general 
guidelines that follow.

7/8 (22)

3-3/8 (86)

3-3/8 (86)

4-1/16 (103)

7/8 (22)

4-1/16

(103)

2 (51)

M2331

12 (305) LEADS

5-13/16

(132)

2 (51)

7/8

(22)

2-7/8 (73)

1/4 IN. Q.C.

3/8 (86)

HOLE (4)

1/4 IN. Q.C. (1)

3/16 IN. Q.C. (5)

3/8 (10)

Содержание S89E

Страница 1: ...e with 4 or 11 second nominal lockout timing 100 percent shutoff for use with all heating gases Ambient temperature rating is 40 F to 175 F 40 C to 80 C Separate electrodes for spark ignition and flame sensing Uses Resideo or any other 2A or less dual valve combination gas control designed for Direct Spark Ignition DSI applications Locks out system after trial for ignition if main burner fails to ...

Страница 2: ...input 2 2A maximum Valve Contacts 2 0A maximum run 20A maximum inrush at 24 Vac Spark Generator Relay Contacts 1 5A at 120 Vac 50 60 Hz Transformer Rating See Table 1 Thermostat Heat Anticipator Setting 0 2A plus gas control current Delay Timing S89E Safe Start Check 10 seconds maximum S89F Safe Start Check plus Valve On Delay 38 seconds maximum Table 1 Transformer Rating Safety Lockout Timing 4 o...

Страница 3: ... LP gas is heavier than air and will not vent upward naturally Do not operate electric switches lights or appliances until you are sure that work area is free of gas 4 Never install an S89 where water can flood drip or condense on the device It can malfunction if it gets wet 5 Never try to use a device that has been damp or wet replace it 6 If the control might be exposed to water or moisture inst...

Страница 4: ...isconnect the external timer when using an S89E or F To disconnect the timer a Turn off power b Cut the two leadwires at the external timer c Strip the ends of the wires 1 2 in 13 mm and connect with a solderless connector d Restore power 3 Wire system components and S89 as shown in Figures 2 and 3 Refer to appliance manufacturer instructions for connections to other auxiliary controls 4 Make sure...

Страница 5: ...gas supply 6 Gas control closes 7 The module begins the safe start check S89E 10 seconds maximum or safe start check plus valve on delay 30 seconds minimum after which the igniter starts and gas control opens 8 Time system until gas control closes S89 is now in safety lockout The lockout time should be within the specifications in Table 2 9 Open gas supply System remains off and no gas flows to th...

Страница 6: ...lly If adjusting the thermostat does not reset the S89 turn off power to the appliance for 45 seconds and then turn it on Final Checkout With power and gas supply on set thermostat to call for heat and observe operation through at least one complete cycle to make certain that all controls are operating safely BLUE WHITE GROUND BURNER IGNITER M19837 FLAME SENSOR 120 V SPARK GENERATOR BLACK AIR PROV...

Страница 7: ...all for heat ends If flame is not proved the gas control closes and the system is locked out until the S89 is reset If flame is lost after being proved the S89 will close the gas control perform a safe start check and on the S89F valve on delay then return ignition as described above The S89 is reset by turning the thermostat below room temperature or removing power to the system for 45 seconds Fi...

Страница 8: ... to protect the ground wire from radiant heat Check Spark Ignition Circuit The S89 spark generator relay switches 120 Vac to the remote mounted spark generator which in turn powers the spark igniter at the burner Check as follows 1 Shut off gas supply to the gas control 2 Disconnect the ignition cable at the spark generator stud terminal 3 Set the thermostat to call for heat 4 Reset the S89 by rem...

Страница 9: ... SHIELD CABLE IF NECESSARY MAKE SUE BURNER SPARK IGNITER AND S89 GROUND BURNER TERMINAL HAVE EFFECTIVE COMMON GROUND POOR OR ERRATC GROUND WILL CAUSE NUISANCE SHUTDOWNS CHECK FOR CRACKED INSULATOR ON IGNITER OR FLAME SENSOR REPLACE DEVICE WITH CRACKED INSULATOR TO PREVENT SHORT TO GROUND NOTE IF S89 LOCKS OUT RESET BEFORE CONTINUING CHECK FOR 24 VAC ACROSS VALVE AND VALVE GROUND TERMINALS ON S89 I...

Страница 10: ...nt must be at least 0 8 μA and steady 3 If the meter reads less than 0 8 μA or reading is unsteady recheck points under Check Flame Sensor and Igniter above Fig 6 S89 flame current measurement Fig 7 Check burner flame condition GND BURNER 24V GND 24V VALVE VALVE GND SENSE TO SENSOR BLACK RED M19840 FLAME SENSOR CURRENT CHECK USE µA SCALE 0 8 µA DC MINIMUM AND STEADY DISCONNECT WIRE FROM SENSE TERM...

Страница 11: ... 24 V THERMOSTAT SAFE START CHECK CIRCUIT ALTERNATE LIMIT ON OFF SWITCH 24 V GND GND BURNER SENSE WHITE FLAME SENSOR SPARK IGNITER RELAY BLUE BLUE BLACK WIRING EXTERNAL TO S89 WIRING INSIDE S89 2K1 1K2 2K2 SPARK IGNITER SPARK GENERATOR VALVE SPARK IGNITER RELAY 1K 2K VALVE GND SENSOR CIRCUIT TIMING CIRCUIT DUAL VALVE L1 HOT L2 ...

Страница 12: ... in United States Fig 9 S89F simplified control system schematic M19843A LIMIT CONTROL AIR PROVING SWITCH COMBUSTION AIR BLOWER 24 V THERMOSTAT SAFE START CHECK VALVE ON DELAY CIRCUIT COMBUSTION AIR BLOWER RELAY ALTERNATE LIMIT ON OFF SWITCH 24 V GND GND BURNER SENSE WHITE FLAME SENSOR SPARK IGNITER RELAY BLUE BLUE BLACK WIRING EXTERNAL TO S89 WIRING INSIDE S89 2K1 1K2 2K2 SPARK IGNITER SPARK GENE...