resideo Multiple Aquastat L4081A Скачать руководство пользователя страница 9

L4081A,B AND L6081A,C MULTIPLE AQUASTAT® CONTROLLERS

9

60-2105—07

Fig. 11. Setting stop shown in position to limit the high limit 

setting to 180°F (82°C).

CHECKOUT

After completing installation and controller settings, operate 

the system. Carefully observe the operation of all 

components through at least one complete cycle. Be sure to 

include a check of the high limit switch operation. Make any 

correction needed; then repeat the checkout. Repeat until 

system operates properly.

MATERIAL SAFETY DATA SHEET

Section 1. Product and Company 
Identification.

Product Name: Heat conductive compound.

MSDS ID: DS9021.

Synonyms: MS1699.

Product Use: Heat conductive material used to enhance 

contact and heat transfer in temperature sensor applications.

Manufacturer: Resideo Technologies, Inc., 1985 Douglas 

Drive North, Minneapolis, MN 55422.

Date Released: October 8, 1999.

NFPA Ratings:

Health 0; Flammability 1; Reactivity 0;

Personal Protection B.

Section 2. Composition, Information on 
Ingredients (Table 3).

a

Additional Information: Part No. 120650 (0.5 oz. tube); Part No. 107408 (4 oz. can); Part number 197007 (5 gallon container).

May also contain minute amounts of lithium and molybdenum lubricant compounds.

Section 3. Hazard Identification

Acute Health Effects:

Skin - Excessive contact can cause skin irritation and 

dermatitis.

Eye - Direct contact with eye will cause irritation.

Inhalation - No adverse effects are expected.

Ingestion - Ingestion of product may cause nausea, vomiting 

and diarrhea.

Chronic Health Effects:

Existing skin rash or dermatitis may be aggravated by 

repeated contact.

OSHA Hazard Classifications:

None.

Carcinogenicity:

Not considered to be a carcinogen by either OSHA, NTP, IARC, 

or ACGIH.

Target Organs:

None known.

220

200

160

140

180

SETTING STOP

SETTING

STOP ARM

PROJECTION "A"

KNOB SET AT 180 F (82 C)

M2844A

1

1

SCALE MARKINGS IN FAHRENHEIT ONLY.

Table 3. Ingredients of Heat Conductive Compound

a

.

Ingredients

CAS Number

Percent

PEL

TLV

No. 2 Lithium Complex Grease (70%):
Mineral Oil

64742-65-0

35-50

5 mg/m

3

5 mg/m

3

Mineral Oil

64742-62-7

20-25

5 mg/m

3

5 mg/m

3

Lithium Hydrostearate/Sebacate 

Complex

68815-49-6

4-9

--

--

Zinc Alkyldithiophosphate

68649-42-3

0-2

--

--

Aluminum Paste (30%):
Aluminum, as Al

7429-90-5

20-25

15 mg/m

3

10 mg/m

3

Aliphatic Petroleum Distillates

8052-41-3

10-15

2900 mg/m

3

525 mg/m

3

Stearic Acid

57-11-4

1-2

--

--

Aromatic Petroleum Distillates

64742-95-6

1-2

5 mg/m

3

5 mg/m

3

Содержание Multiple Aquastat L4081A

Страница 1: ...The other switch operates as a low limit and or circulator control depending on the model Controller may be mounted in any positioning and needs no leveling Separate easy to read calibrated dial and setpoint adjustments for each switch Differential adjustment on low limit or circulator switch All adjustments accessible inside front cover Push in terminals for quick connecting Single sensing elemen...

Страница 2: ...if well is needed refer to form 68 0040 for ordering information bDevice is less case and cover Scale Markings For Fahrenheit models High Limit 160 180 200 220 F Low Limit or Circulator 120 140 160 180 200 F For Celsius models High Limit 55 65 75 85 95 C Low Limit or Circulator 45 55 65 75 85 95 C Differentials High Limit 10 F 6 C nominal Low Limit or Circulator L6081A C 10 to 25 F 6 to 14 C adjus...

Страница 3: ...sius scale on L4081A Accessories ordered separately 126580 Setting Stop Used to prevent turning setting knob beyond a predetermined point 124904 Well Adapter Use to convert mounting on some competitive wells to fit L4081 L6081 See form 68 0040 7 8 IN 22 MM DIA KNOCKOUT FOR 1 2 IN 12 5 CONDUIT 6 1 3 16 30 2 3 64 63 4 3 32 125 5 3 4 19 2 2 1 13 64 30 5 2 1 13 64 30 5 WELL CLAMP SCREW MAXIMUM INSERTI...

Страница 4: ...a tion or 6 3 8 in 162 mm if designed for 3 in 76 mm insulation If this requires bending the tube inside the case insert the end of your index finger through the hole and carefully mold the tube into the correct shape as you gently pull or push the bulb to the correct posi tion The bulb must project the right distance so that after the case in installed the spring force of the capil lary tube hold...

Страница 5: ...no 14 or 16 unistranded wire for connecting the push in terminals 2 Strip the insulation from the end of each wire 3 Insert a screwdriver into the rectangular slot near the terminal and hold it in the slot while inserting the wire into the terminal hole as far as possible 4 Remove the screwdriver when complete Jumper When using the controller field addable jumper Fig 4 connect terminals R R When t...

Страница 6: ... LIMIT LOW LIMIT M8788A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED B TERMINALS ARE TAB TERMINALS L1 HOT L2 1 GAS VALVE PILOTSTAT CONTROL T T T T X X L1 HOT L2 1 2 1 2 1 2 4 3 1 CIRCULATOR 1R1 1R2 1R 24V THERMOSTAT B R B R RA832A SWITCHING RELAY L4081A HIGH LIMIT LOW LIMIT OIL PRIMARY CONTROL L2 L1 HOT JUNCTION BOX M8786A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVER...

Страница 7: ...s at 155 F 69 C On a temperature fall the switch makes at 130 F 55 C L4081B Setpoint of 140 F 60 C differential set at 25 F 14 C On a temperature rise the switch makes at 155 F 69 C On a temperature fall the switch breaks at 130 F 55 C L6081A B Setpoint of 140 F 60 C differential set at 25 F 14 C On a temperature rise R B breaks and R W makes at 155 F 69 C On a temperature fall R B makes and R W b...

Страница 8: ...tching response to temperature changes LOW LIMIT SETTING HIGH LIMIT SETTING SWITCH BREAKS ON RISE BURNER TURNS OFF SWITCH MAKES ON FALL BURNER OPERATES ON A CALL FOR HEAT SWITCH BREAKS ON RISE 10 F 5 6 C DIFFERENTIAL SWITCH MAKES ON FALL BURNER ON M8847B SWITCH BREAKS ON RISE 25 F 13 9 C DIFFERENTIAL 10 F 5 6 C DIFFERENTIAL 25 F 13 9 C DIFFERENTIAL 10 F 5 6 C DIFFERENTIAL CIRCULATOR SETTING HIGH L...

Страница 9: ...on container May also contain minute amounts of lithium and molybdenum lubricant compounds Section 3 Hazard Identification Acute Health Effects Skin Excessive contact can cause skin irritation and dermatitis Eye Direct contact with eye will cause irritation Inhalation No adverse effects are expected Ingestion Ingestion of product may cause nausea vomiting and diarrhea Chronic Health Effects Existi...

Страница 10: ...r faceshield if potential for eye contact exists especially if material is heated Hand Clothing Protection Not normally required Protective gloves and clothing are recommended as material is difficult to remove from skin and clothing Other Protective Equipment None required Section 9 Physical and Chemical Properties Appearance Odor Aluminum color semi solid material pleasant odor Solubility in Wat...

Страница 11: ...L4081A B AND L6081A C MULTIPLE AQUASTAT CONTROLLERS 11 60 2105 07 ...

Страница 12: ...Technologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 60 2105 07 M S Rev 04 20 Printed in United States ...

Отзывы: