L4081A,B AND L6081A,C MULTIPLE AQUASTAT® CONTROLLERS

60-2105—07

4

INSTALLATION

When Installing This Product.

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-

tion.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

techni-

cian.

4.

After installation is complete, check out product 

opera-

tion as provided in these instructions.

WARNING

Electrical Shock Hazard. 

Can cause serious injury, death or equipment 

damage.

Disconnect power supply before installation to 

prevent electrical shock or equipment damage.

NOTE:

These devices can be installed in any position. 

Proper location, sizing and threaded boiler tapping 

are required.

1.

Maximum pressure rating for these models is 200 psi 

(1380 kPa)

2.

Maximum permissible ambient temperature as sensing 

bulb is 265°F (130°C); at switches, 150°F (66°C).

3.

The L6081C is without enclosure or well assembly.

MOUNTING

Follow instructions provided by system manufacturer, if 

available. Otherwise, proceed as follows:

1.

Drain the boiler if the system is filled with water.

2.

Place the front of the controller down on a horizontal 

surface and gently raise the sensing bulb until it is at a 

right angle with the back of the case and centered with 

the large hole in the case. This requires bending the 

capillary tube, but be sure to make no sharp bends and 

no bends near the bulb.

NOTE:

Some models have an adjustable tubing length to 3 

in. (76 mm). In these models, extra tubing inside the 

case can be pulled out, if needed. See Fig. 3.

Fig. 3. Adjusting the capillary length.

3.

Adjust the position of the bulb so that the bulb projects 

4-7/8 in. (124 mm) from the back of the case for 

immersion well designed for 1-1/2 in. (38 mm) insula-

tion; or 6-3/8 in. (162 mm), if designed for 3 in. (76 mm) 

insulation. If this requires bending the tube inside the 

case, insert the end of your index finger through the 

hole and carefully mold the tube into the correct shape 

as you gently pull (or push) the bulb to the correct posi-

tion. The bulb must project the right distance so that 

after the case in installed, the spring force of the capil-

lary tube holds the bulb against the inner end of the 

well for good thermal contact. The tube must be 

straight for at least 3/8 in. (10 mm) inside the case so 

the end of the well spud does not strike the coiled tube 

and pull the bulb away from contact with the inner end 

of the well.

4.

Remove the plug from a properly located boiler tapping.

5.

Apply pipe dope sparingly to the threads of the well, 

then screw the well tightly into the boiler tapping.

6.

Fill the system with water, then carefully examine 

around the threads for leakage. Tighten the well if nec-

essary to stop any leakage.

7.

Loosen the wallclamp screw three or four turns., move 

the screw in and out and not how it moves the well 

clamp. See Fig. 4. Loosen the screw enough so that 

when the screw is pushed inward, the T-shaped clamp 

guide is at the far end of the slot in the case.

8.

Mount the case on the well spud in any position that 

facilitates wiring. With the case in final position, care-

fully insert the sensing bulb into the well until the case 

slips over the end of the well spud and fits squarely 

against the shoulder of the spud.

NOTE:

Open the clamp to receive the spud by pushing in 

the well clamp screw.

9.

While holding the case in the correct position, firmly 

tighten the well clamp screw.

M8882

SENSING ELEMENT IS FACTORY FORMED FOR 1.5 INCH
INSULATION WELL ASSEMBLIES.

FOR 3 INCH INSULATION WELL ASSEMBLIES, PULL OUT
SUFFICENT CAPILLARY TO ASSURE THAT THE CAPSULE
BOTTOMS IN THE WELL.

STRAIGHTEN CAPILLARY  SUFFICENTLY SO IT DOES NOT 
INTERFERE WITH INSERTING THE  CAPSULE INTO THE WELL.

CAUTION:
EXCESSIVE HANDLING OR SHARP BENDS 
CAN DAMAGE THE CAPILLARY.

1

2

3

1

2

3

Содержание Multiple Aquastat L4081A

Страница 1: ...The other switch operates as a low limit and or circulator control depending on the model Controller may be mounted in any positioning and needs no leveling Separate easy to read calibrated dial and setpoint adjustments for each switch Differential adjustment on low limit or circulator switch All adjustments accessible inside front cover Push in terminals for quick connecting Single sensing elemen...

Страница 2: ...if well is needed refer to form 68 0040 for ordering information bDevice is less case and cover Scale Markings For Fahrenheit models High Limit 160 180 200 220 F Low Limit or Circulator 120 140 160 180 200 F For Celsius models High Limit 55 65 75 85 95 C Low Limit or Circulator 45 55 65 75 85 95 C Differentials High Limit 10 F 6 C nominal Low Limit or Circulator L6081A C 10 to 25 F 6 to 14 C adjus...

Страница 3: ...sius scale on L4081A Accessories ordered separately 126580 Setting Stop Used to prevent turning setting knob beyond a predetermined point 124904 Well Adapter Use to convert mounting on some competitive wells to fit L4081 L6081 See form 68 0040 7 8 IN 22 MM DIA KNOCKOUT FOR 1 2 IN 12 5 CONDUIT 6 1 3 16 30 2 3 64 63 4 3 32 125 5 3 4 19 2 2 1 13 64 30 5 2 1 13 64 30 5 WELL CLAMP SCREW MAXIMUM INSERTI...

Страница 4: ...a tion or 6 3 8 in 162 mm if designed for 3 in 76 mm insulation If this requires bending the tube inside the case insert the end of your index finger through the hole and carefully mold the tube into the correct shape as you gently pull or push the bulb to the correct posi tion The bulb must project the right distance so that after the case in installed the spring force of the capil lary tube hold...

Страница 5: ...no 14 or 16 unistranded wire for connecting the push in terminals 2 Strip the insulation from the end of each wire 3 Insert a screwdriver into the rectangular slot near the terminal and hold it in the slot while inserting the wire into the terminal hole as far as possible 4 Remove the screwdriver when complete Jumper When using the controller field addable jumper Fig 4 connect terminals R R When t...

Страница 6: ... LIMIT LOW LIMIT M8788A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED B TERMINALS ARE TAB TERMINALS L1 HOT L2 1 GAS VALVE PILOTSTAT CONTROL T T T T X X L1 HOT L2 1 2 1 2 1 2 4 3 1 CIRCULATOR 1R1 1R2 1R 24V THERMOSTAT B R B R RA832A SWITCHING RELAY L4081A HIGH LIMIT LOW LIMIT OIL PRIMARY CONTROL L2 L1 HOT JUNCTION BOX M8786A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVER...

Страница 7: ...s at 155 F 69 C On a temperature fall the switch makes at 130 F 55 C L4081B Setpoint of 140 F 60 C differential set at 25 F 14 C On a temperature rise the switch makes at 155 F 69 C On a temperature fall the switch breaks at 130 F 55 C L6081A B Setpoint of 140 F 60 C differential set at 25 F 14 C On a temperature rise R B breaks and R W makes at 155 F 69 C On a temperature fall R B makes and R W b...

Страница 8: ...tching response to temperature changes LOW LIMIT SETTING HIGH LIMIT SETTING SWITCH BREAKS ON RISE BURNER TURNS OFF SWITCH MAKES ON FALL BURNER OPERATES ON A CALL FOR HEAT SWITCH BREAKS ON RISE 10 F 5 6 C DIFFERENTIAL SWITCH MAKES ON FALL BURNER ON M8847B SWITCH BREAKS ON RISE 25 F 13 9 C DIFFERENTIAL 10 F 5 6 C DIFFERENTIAL 25 F 13 9 C DIFFERENTIAL 10 F 5 6 C DIFFERENTIAL CIRCULATOR SETTING HIGH L...

Страница 9: ...on container May also contain minute amounts of lithium and molybdenum lubricant compounds Section 3 Hazard Identification Acute Health Effects Skin Excessive contact can cause skin irritation and dermatitis Eye Direct contact with eye will cause irritation Inhalation No adverse effects are expected Ingestion Ingestion of product may cause nausea vomiting and diarrhea Chronic Health Effects Existi...

Страница 10: ...r faceshield if potential for eye contact exists especially if material is heated Hand Clothing Protection Not normally required Protective gloves and clothing are recommended as material is difficult to remove from skin and clothing Other Protective Equipment None required Section 9 Physical and Chemical Properties Appearance Odor Aluminum color semi solid material pleasant odor Solubility in Wat...

Страница 11: ...L4081A B AND L6081A C MULTIPLE AQUASTAT CONTROLLERS 11 60 2105 07 ...

Страница 12: ...Technologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 60 2105 07 M S Rev 04 20 Printed in United States ...

Отзывы: