4
MU1H-2327GE23 R0121
3.
Operating Control
To ensure that the valve is working in its operating differential
pressure range.
Measure the differential pressure across the valve as shown
in the picture below.
Provided the differential pressure is higher than the start up
pressure, the valve keeps flow constant at the set value.
4.
Maintenance and Cleaning
5.
Use a damp cloth to clean the actuator.
6.
Do not use any detergent or chemical product that
may seriously damage or compromise the function of
the valve.
2.1 M5006
2.1.1 Application
Electromotive actuators M5006 - 24V are used with many kind of control systems used for HVAC applications, including ON/
OFF, floating, proportional managed by thermostat or BMS handling analogue signals or PWM digital, of HVAC installations
where V5006TF PICV balancing valves are used; in order to properly set the presetting, see the specific section devoted to
actuator setting.
For further information about electrical connections, see the specific section.
2.1.2 Dimensions
Note:
Dimensions in mm
2.1.3 Approvals
•
CE
1
Display
2
Button UP
3
Button MODE
4
Button DOWN
5
Manual override
1
3
2
4
5
Overview