5.2 Setting parameter SET 4: PRESETTING
The presetting flow rate of valve V5006TF can be set through the parameter SET 4 of the M5006 actuator: the parameter should
set between the max and min presetting flow rate of the valve. SET 3 should be left at 0.
6
Ratio of Value of Flow According to Flow Curve
7
Manual Override Operation
7.1 Manual Override M5006
If a manual opening of the valve is needed, proceed as follows:
To re-assembly the actuator, follow the same procedure on INSTALLATION section.
Valve
V5006T
F1050
V5006T
F1065
V5006T
F1080
V5006T
F1100
V5006T
F1125
V5006T
F1150
V5006T
F1200LF
V5006TF
1200HF
V5006TF
1250LF
V5006TF
1250HF
Max
presetting
flow rate
(m
3
/h)
20
30
30
55
90
150
200
300
300
500
Min
presetting
flow rate
(m
3
/h)
2
3
3
5.5
9
15
20
30
30
50
POSITION of
VALVE LIFT
(Unit: %)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
LINEAR
CURVE (Unit:
%)
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
EQUAL
PERCENTAG
E CURVE
(Unit: %)
0 2 3 4 4 5 6 8 10 12 14 17 21 25 31 38 46 56 68 82 100
1. Open the rubber cover on the actuator upper face and insert
the 6mm Allen key
2. Turn the key keeping the released button pushed under the
actuator