background image

393200-1 ECO CONNECTOR FOR THE VR8200 FAMILY OF CONTINUOUS PILOT COMBINATION GAS CONTROLS

© 2020 Resideo Technologies, Inc. All rights reserved.
 This product is manufactured by Resideo Technologies, Inc. and its affiliates.

www.resideo.com

Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
69-0317—05    M.S.  Rev. 05-20 | Printed in United States

INSTALLATION

When Installing This Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a haz-

ardous condition.

2.

Check the ratings given in the instructions and on 

the product to make sure the product is suitable 

for your application. 

3.

Installer must be a trained, experienced service 

technician. 

4.

After installation is complete, check out product 

operation as provided in these instructions. 

Install ECO Connector 

Install the gas control as described in the instructions 

provided with the control until you are ready to connect 

the thermocouple lead, then:

1.

Insert the ECO connector as shown in Fig. 1. 

2.

Hold the connector in place with one hand and 

insert the thermocouple lead. 

NOTE:

This is an electrical connection and must 

be clean and dry. Never use pipe com-

pound.

3.

Tighten the thermocouple lead until finger tight, 

then tighten 1/4 turn more. Do not overtighten. 

Tighten only enough to give good electrical conti-

nuity. 

Fig. 1. lnstall ECO connector into gas control at 

thermocouple terminal location. 

Install Limit

Install ECO as described in the instructions provided 

with the limit.

WIRING 

Fit limit control leadwires with female 1/4 in. [6.4 mm] 

quick connects. Run leadwires from the limit and attach 

them to the male quick-connects on the ECO connector. 

Do not exceed the leadwire lengths shown in Table 1 and 

2. 

CHECKOUT

After completing installation of the gas control, check 

operation of the limit as described in the instructions 

provided with the limit. Make certain that when the limit 

is activated, the pilot safety valve in the control drops 

out and the pilot burner flame is extinguished. 

THERMOCOUPLE 

LEAD

ECO

CONNECTOR

1

THIS IS AN ELECTRICAL CONNECTION AND MUST BE

CLEAN AND DRY.  DO NOT USE PIPE COMPOUND.

M3095C

1

Отзывы: