28
9.1 Tower Case (220V)
Rated Power
Capacity
1KVA / 700W
2KVA / 1400W
3KVA / 2100W
Input
Voltage
Single phase 220Vac, 160~300Vac at 100~70% load
140~300Vac at 70~50% load, 120~300Vac at 0~50% load
Frequency
50Hz or 60Hz +/- 4Hz
Power Factor
≧
0.95
≧
0.97
Output
Voltage, Frequency
Single phase /- 2% (230V or 240V re-settable via
LCD panel), 50Hz or 60Hz +/-0.2Hz (Battery mode)
Transient Response
+/- 3% (100% load variation)
Waveform / Distortion
Sine wave, THD < 3% at 0-100%
linear load
Sine wave, THD < 4% at
0-100% linear load
Over Load Capacity
110~150% 30sec, then switch to bypass and auto
re-transfer; >150% for 300ms
Crest Ratio
3 : 1
Battery
Voltage (longer backup
time is available upon
request)
7Ah / 12V * 3pcs
7Ah / 12V * 8pcs
Recharge Time
5 hrs to 90% of full capacity after full load discharge
Bypass
Automatic: Overload and UPS failure
By setting: Voltage Range 176V~ 253V+/-20V (re-settable via LCD panel)
Transfer Time
AC fail 0 ms; 2.5ms typical from inverter to bypass and vice versa
Audible Alarm
Battery Mode
Beeping every 4 seconds (re-settable) and per second
when battery low
Overload
> 110% Beeping twice per second
Fault
Beep Continuously
Indicator
LED
Normal (green), Warning (yellow), Fault (red) LED
Communications
DB9 Connector
RS-232 Interface; Power monitoring software (Option)
SNMP Intelligent Slot
For Net Agent II / Mini (Option) with SNMP manager and
Web browser
Network
Surge Protection
RJ11 I/O port available for 10 base-T network
or Fax / Modem
Environment
Temperature
0-40 degree C; 32-104 degree F
Relative Humidity
0-95% non-condensing
Acoustic Noise (at 1 M)
< 45 dBA
< 50 dBA
Physical
Net Weight (w/o batt.)
7 kgs
13.5 kgs
14.5 kgs
Net Weight (w/ batt.)
14 kgs
34 kgs
35 kgs
Dimension(LxWxH)mm
400*160*220
465*200*352
465*200*352
※
Specifications are subject to change without notice.
9. SPECIFICATIONS
29
9.2
Tower Case (120V)
Rated Power
Capacity
1KVA / 700W
1.5KVA / 1050W
3KVA / 2100W
Input
Voltage
60~138VAC
Base on load
percentage
(110%-70%/60%-50%/50%-40%/40%-0%)
Frequency
50Hz or 60Hz +/- 4Hz
Power Factor
≧
0.95
Output
Voltage, Frequency
Single phase /- 2% (115V or 120V re-settable via
LCD panel), 50Hz or 60Hz +/-0.5% (Battery mode)
Transient Response
+/- 3% (100% load variation)
Waveform / Distortion
Sine wave, THD < 3% at 0-100% linear load
Over Load Capacity
105~150% 30sec, then switch to bypass and auto
re-transfer >150% for 200ms
Crest Ratio
3 : 1
Battery
Voltage (longer backup time
is available upon request)
7Ah / 12V * 3pcs
7Ah / 12V * 4pcs
7Ah / 12V * 8pcs
Recharge Time
8 hrs to 90% of full capacity after full load discharge
Bypass
Automatic: Overload and UPS failure
By setting: Voltage Range 115V+/-20V (re-settable via LCD panel)
Transfer Time
AC fail 0 ms; 2.5ms typical from inverter to bypass and vice versa
Audible Alarm
Battery Mode
Beeping every 4 seconds (re-settable) and per second
when battery low
Overload
Beeping twice per second
Fault
Beep Continuously
Indicator
LCD
UPS status, I/P&O/P voltage& frequency, Battery voltage,
Battery capacity, Loading %, Temperature, History record
LED
Normal (green), Warning (yellow), Fault (red) LED
Communications
DB9 Connector
RS-232 Interface; Power monitoring software (Option)
SNMP Intelligent Slot
For Net Agent II / Mini (Option) with SNMP manager and Web browser
Network
Surge Protection
RJ11 I/O port available for 10 base-T network
or Fax / Modem
Environment
Temperature
0-40 degree C; 32-104 degree F
Relative Humidity
0-95% non-condensing
Acoustic Noise (at 1 M)
< 45 dBA
< 45 dBA
< 50 dBA
Physical
Net Weight (w/o batt.)
7kgs
9kgs
16kgs
Net Weight (w/ batt.)
13kgs
17.5kgs
33kgs
Dimension (LxWxH)mm
400*160*220
465*160*220
450*200*352
※
Specifications are subject to change without notice.
Содержание RP-UPH
Страница 5: ...8 2KVA 3KVA Tower Case 9 1KVA 2KVA 3KVA Rack Mount Case...
Страница 17: ...32...