Reo Elektronik REOTRON MEW Скачать руководство пользователя страница 5

 
 

Operating Instructions

 

REOTRON MEW 

 

REO

 

UK LTD 

 

5

 

ELEKTRONIK

ELEKTRONIK

ELEKTRONIK

ELEKTRONIK

 

2.1 Effective Current Value

 

 
The effective current value is measured inside the unit through a current transformer and a burden 
resistor. The internal microprocessor determines the effective value of the output current and adjusts 
this using a PI regulator. 
 

2.2 Effective Voltage Value 

 

 
The effective voltage value is also measured internally using a voltage transformer and the effective 
value is controlled by the microprocessor using a PI regulator. 
 

2.3 Current Regulator

 

 
Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using 
trimmer P4. The units maximum output current (Rated Current) is factory set. If the thyristor controller 
is to be adapted for a small load current, then a correction can be made by using trimmer Imax. 

BEWARE

: It is possible to obtain an output current which is higher than the rated current because of 

component and manufacturing tolerances, however, for safety, it is essential that the current limit is 
not set higher than the rated current 
In current regulation mode the LED Imax is permanently illuminated. 
 

2.4 Voltage Regulator

 

 
Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using 
trimmer P3. The units maximum voltage output is factory set to the rated voltage (for 100% set point).

 

 

Therefore, the  setpoint cannot be fully used during voltage regulation since this would not allow for 
any over voltage. In this operating mode (voltage regulation) either the setpoint must be limited or the 
maximum unit output voltage must be reduced by using the trimmer Umax. 
 

2.5 Pulse Generation

 

 
The pulses required for the control of the thyristors are generated by the microprocessor and are fed 
to amplifiers prior to the pulse conductors. The secondary windings of the pulse conductors directly 
control the thyristors. 
 

2.6 Temperature Monitoring

 

 
A temperature switch is fitted into the heat sink to monitor its temperature and this switches off the 
thyristor controller, permanently, if the temperature exceeds a maximum of 80oC. Fault indication is 
provided by the general fault relay and displayed by the LED on the front panel. 
  

3.0 Control Inputs and Outputs

 

 

Control Inputs 

Setpoint Input  U 

 

0(4)...20 mA, 0-10V DC or Potentiometer 10k

 

Setpoint Input  I 

 

0(4)...20 mA, 0-10V DC or Potentiometer 10k

 

Enable 

   12-24V 

DC 

or 

contacts 

 

Outputs:

 

Effective Current Value  

0-10V DC corresponding to 0-100% (Option) 

Effective Voltage Value  

0-10V DC corresponding to 0-100% (Option) 

Fault Indication  

 

Relay Contact 250V/1A (Change over) 

 
 
 
 
 
 
 
 

Содержание REOTRON MEW

Страница 1: ...10 Long Lane Industrial Estate 08 99 Craven Arms Shropshire SY7 8DU Tel 01588 673411 Fax 01588 672718 http www reo co uk eMail main reo co uk Operating Instructions REOTRON MEW Single Phase Power Controller ELEKTRONIK ELEKTRONIK ELEKTRONIK ELEKTRONIK ...

Страница 2: ...cording to IEC 364 Safety Instructions The following instructions are provided for the personal safety of operators and also for the protection of the described product and connected equipment Warning Hazardous Voltage Failure to observe can kill cause serious injury or damage Isolate from mains before installation or dismantling work as well as for fuse changes or post installation modifications ...

Страница 3: ... and Outputs 5 3 1 Setpoint Input U 6 3 2 Setpoint Input I 6 3 3 Enable Regulator Inhibit 6 3 4 Actual Voltage Output Option 6 3 5 Actual Current Output Option 6 3 6 Fault Indication 6 4 0 Construction 6 5 0 Adjustment Facilities 7 6 0 Adjustment Instructions 7 7 0 Technical Data 9 8 0 Ordering Codes 10 9 0 Adjustment Components 11 10 0 Fuse Change 12 11 0 Installation Guidelines 12 12 0 Guideline...

Страница 4: ...s Preheating Plants Air Conditioning Plant Tunnel Heaters Room Heating Equipment Fan Heating Systems Plastic Moulding Equipment Extruders 2 0 Function description The MEW thyristor control unit was designed to operate with a symetrical load They include a voltage and current regulator In the voltage regulation mode the output voltage determined by the set point is held constant by an internal circ...

Страница 5: ...ocessor controller with PI Characteristics the P portion is adjustable externally by using trimmer P3 The units maximum voltage output is factory set to the rated voltage for 100 set point Therefore the setpoint cannot be fully used during voltage regulation since this would not allow for any over voltage In this operating mode voltage regulation either the setpoint must be limited or the maximum ...

Страница 6: ...mentary voltage output This generates 10V for 100 of the units possible output voltage using the Umax set value 3 5 Actual Current Output Option A 0 10 V DC output signal is provided and this corresponds to the units momentary current output This generates 10V for 100 of the units possible output current using the Imax set value 3 6 Fault Indication Relay changeover contacts are provided for indic...

Страница 7: ...ends from zero to the adjusted range maximum The maximum value must be set first Adjustment of the MAX Values Umax Hint If the output voltage is to be regulated at the maximum set point then the maximum output voltage must be limited at a value which reduces the regulation range Switch on the mains voltage and enable the unit Set the current set point to maximum Now increase the voltage set point ...

Страница 8: ...is similarly achieved using the trimmer P1 for Ramp up and P2 for Ramp down times With the voltage set point at zero and the current set point at maximum Set rotary switch S2 on the front panel to position 3 and press the RESET button Next set the required ramp time 0 1 10s using trimmer P1 and test for a set point change from zero to 100 afterwards set the ramp down time with trimmer P2 and again...

Страница 9: ...0 230 230 V 6 10 0 230 V 110 A MEW 110 400 400 V 6 10 0 400 V 110 A MEW 150 400 400 V 6 10 0 400 V 150 A Load Types resistive resistive inductive for transformers max induction 1 45 Tesla Setpoint source 5 10 kΩ Potentiometer 0 10V DC 0 20 mA Ramp up down time 0 1 10 sec Enable Switch 12 24 V DC Actual value output I 0 10 V DC Actual value output U 0 10 V DC Fault relay 1 change over contacts 250 ...

Страница 10: ...unit REOTRON MEW 50 230 DA 6338 50 A 230 V with D A Module REOTRON MEW 50 400 DA 6337 50 A 400 V with D A Module REOTRON MEW 50 230 RS 6339 50 A 230 V with RS 232 Interface REOTRON MEW 50 400 RS 63310 50 A 400 V with RS 232 Interface REOTRON MEW 50 230 IS 6333 50 A 400 V with INTERBUS S Interface REOTRON MEW 50 400 IS 6334 50 A 400 V with INTERBUS S Interface REOTRON MEW 80 230 6341 80 A 230 V Sta...

Страница 11: ...tor P4 P Characteristic current regualtor Selector Switch S1 S1 1 OFF Phase angle control ON Full wave control S1 2 S1 3 Reserved for curent controller S1 4 S1 5 OFF 0 20 mA ON 4 20 mA Setpoint S1 6 OFF I U Regulation ON Power regulation S1 7 OFF without data interface ON with data interface S1 8 OFF Reserved Selector Switch S2 0 Normal operation Regulator 1 Adjustment Umin 2 Adjustment Imin 3 Adj...

Страница 12: ...ce of approximately 250mm The control cables should be shielded and the shield should be connected to earth 12 0 Guidelines on Electromagnetic Interference INTERBUS S is a serial data transfer system which was conceived for applications in an industrial environment When correctly installed INTERBUS S complies with all the requirements specified in the standard IEC 801 for data transfer systems in ...

Страница 13: ...U 230V 50 60Hz 400V 50 60Hz Load NC C NO 0 0 0 10V 0 10V Actual value Voltage Actual value Current 11 12 13 14 15 16 17 18 19 20 Optional 21 22 23 24 25 26 L1 L L2 N PE 0 0 10V 10V 1 2 3 4 5 6 7 8 9 10 10k 10k Voltage setpoint Current setpoint Enable 1 2 3 4 5 6 7 8 9 10 0 0 Setpoint Voltage Setpoint Current 0 20mA 0 20mA Enable 24V DC to terminal 15 1 2 3 4 5 6 7 8 9 10 Enable 0 0 Setpoint Voltag...

Страница 14: ...RROR ENABLE TEMP SYNC I max LOAD MAX INIT READY IN1 IN2 P1 P2 P3 P4 S1 U max I max S2 RESET SETUP 0 1 2345 6 7 8 9 A B C D E F e REOTRON MEW d x 205 ELEKTRONIK ELEKTRONIK ELEKTRONIK ELEKTRONIK Dimension MEW10 MEW20 MEW50 MEW80 MEW110 a 70 70 60 90 b 35 15 15 30 30 c 70 110 110 150 180 d 290 290 290 320 320 e 280 280 280 304 304 x 5 5 5 10 ...

Страница 15: ...EOTRON MEW FOR CONTINUED FIRE PROTECTION REPLACE ONLY WITH SPECIFIED TYPE AND RATED FUSE DISCONNECT POWER INPUT BEFORE REPLACING FUSE 320 290 90 180 1 4 7 8 F ELEKTRONIK ELEKTRONIK ELEKTRONIK ELEKTRONIK 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 21 22 26 25 23 24 7 8 1 Control terminals 2 Power terminal Input L1 3 Power terminal Input L2 N 4 Power terminal Output V N 5 Power te...

Отзывы: