10
z
Please close the Viewing Window and tighten the captive screws after completing the steps
above.
z
The operating voltage of the solar array shall exceed 60VDC, the open circuit voltage shall NOT
exceed 150VDC, and the short circuit current shall NOT exceed 20A.
z
Make sure that the 2 solar arrays have the same operating voltage and are not partially shaded.
Operating voltage mismatches or partial shading can cause current backflow and damage solar
arrays.
z
Press the Solar Inverter Charger UP and DOWN Buttons to turn the page and view detailed
charging status. Please refer to the full user manual of 48V 3500W Solar Inverter Charger on
renogy.com for more instructions.
z
Additional protection devices including DC ground fault circuit interrupters, DC arc fault circuit
interrupters, and rapid shutdown devices (not included) may be required to comply with the local
and state codes for solar systems.