If  any  problems  occur  during  battery  operation,  please  refer  to  the  following  instructions  or 
contact us for assistance:

If the Power Button is not able to switch the battery to active mode or the battery resting 
voltage is under 41.62V in active mode at room temperature, the battery may have been 
severely over-discharged due to self-discharge or parasitic loads. Please revive the battery 
using a battery charger or charge controller with the lithium battery activation function.

If the battery terminal voltage shows 0V in active mode, the battery internal fuses may have 
blown due to severe over-current. Please contact us for assistance.

If  the  battery  voltage  gets  too  low  to  reliably  power  electric  loads  or  triggers  the  battery 
under-voltage protection, please disconnect the battery from electric loads and charge the 
battery as soon as possible.

If  the  battery  temperature  gets  too  high/low  during  the  operation  and  triggers  the  battery 
high/low  temperature  protection,  please  disconnect  the  battery  from  the  charging  source 
and electric loads and cool down/warm up the battery to room temperature. The battery will 
automatically recover from the battery high/low temperature protection.

If  too  high  a  current  passes  through  the  battery  and  triggers  the  charge/discharge 
over-current  protection,  please  disconnect  the  battery  from  the  charging  source/electric 
load  immediately.  The  battery  will  automatically  recover  from  the  charge/discharge 
over-current  protection  after  1  minute.  If  the  charge/discharge  over-current  protection  is 
triggered  3  times  in  a  row,  the  battery  will  no  longer  recover  automatically.  Please 
discharge/charge the battery with a current greater than 1A to recover the battery from the 
charge/discharge over-current protection.

If the battery is short circuited and triggers the short circuit protection, please remove the 
short circuit immediately and charge the battery with a current greater than 1A to recover the 
battery from the short circuit protection.

Troubleshooting

Содержание 50LFP48S

Страница 1: ...Version 2 0 Battery SMART LITHIUM IRON PHOSPHATE 48V 50Ah...

Страница 2: ...re including fire typhoon flood earthquake war and terrorism Intentional or accidental misuse abuse neglect or improper maintenance and use under abnormal conditions Improper installation improper ope...

Страница 3: ...of the battery Please keep the battery out of the reach of young children Please wear proper protective equipment when working on the battery Please use insulated tools when working on the battery DO...

Страница 4: ...arts Additional Components Preparation Battery Installation Inspection Troubleshooting Specifications Cable Sizing Connecting Batteries in Banks Securing Cable Connections Installation Environment Bat...

Страница 5: ...built in intelligent self heating the battery is rechargeable even in low temperature conditions The battery management system BMS and high performance dual processors provide comprehensive protection...

Страница 6: ...s RS485 UP Communication Port RS485 LINK Communication Port CAN Communication Ports Positive Terminal w Terminal Cover Negative Terminal w Terminal Cover LED Indicator Power Button 22 70 in 576 0 mm 1...

Страница 7: ...fore the purpose of this section is only to serve as a guideline as all scenarios cannot be covered The Long Terminal Bolts M8 x 1 x 20 are used to secure multiple cable lugs on a single battery termi...

Страница 8: ...sion and dry If any problems are detected with the battery please contact us for assistance Refer to the last page of the manual for contact information Inspection Battery cables sold separately shoul...

Страница 9: ...rated capacities or nominal voltages in parallel Please avoid too high a voltage difference between paralleled batteries despite the auto balancing function to avoid triggering the over current prote...

Страница 10: ...o that the washer stack is slightly larger than the observed gap The battery should be installed in a clean cool and dry place keeping water oil and dirt away from the battery The accumulation of thes...

Страница 11: ...on on any battery To switch paralleled batteries to shelf mode simulta neously please enable the communication between paralleled batteries and use the Power Button on the first battery Otherwise plea...

Страница 12: ...er than 3A for each battery in the parallel battery bank The self heating function will start operating automatically once the battery and the battery temperature drops below 41 F 5 C and stop operati...

Страница 13: ...ully charge the battery prior to the initial use The self heating function will not be able to operate normally if a PWM charge controller or a small current battery charger is used to charge the batt...

Страница 14: ...dirty Ensure the battery is completely dry before switching it to active mode and or reconnecting it to the charging source or electric load Battery Maintenance Terminal corrosion may adversely affect...

Страница 15: ...arge the battery at least once every 3 6 months to prevent over discharge When the battery is taken out of storage it should be given a full charge prior to use DO NOT expose the battery to the extrem...

Страница 16: ...Battery Voltage 55 5V Battery Voltage 51V Discharge Current 1A Battery Cell Voltage 3 75V Battery Cell Voltage 3 4V Discharge Current 1A Battery Voltage 45 75V Battery Voltage 50V Charge Current 1A B...

Страница 17: ...hest voltage and the lowest voltage battery cell group exceeds the set voltage difference the switch connected to the highest voltage battery cell group will be closed to shunt the charge current arou...

Страница 18: ...ng the operation and triggers the battery high low temperature protection please disconnect the battery from the charging source and electric loads and cool down warm up the battery to room temperatur...

Страница 19: ...attery Cell 50A 54V 22 7 x 8 5 x 7 9 inch 576 x 215 x 200 mm Maximum Continuous Charging Current Charging Voltage Connection Method Certifications 77 F 9 F 25 C 5 C Standard Operation Temperature Disc...

Страница 20: ...761 USA 909 287 7111 www renogy com support renogy com https www renogy cn support renogy cn CN 400 6636 695 CA https ca renogy com supportca renogy com https au renogy com supportau renogy com AU JP...

Отзывы: