Front Panel Rotary Switch (Sensitivity)
The eight-position rotary switch selects one of eight (8) sensitivity levels as shown in the table below. 0 is
lowest and 7 is highest, with normal (factory default) being 3. Use the lowest sensitivity setting that will
consistently detect the smallest vehicle that must be detected. Do not use a sensitivity level higher than necessary.
Position
0
1
2
3 *
4
5
6
7
-
∆
L/L
1.28%
0.64%
0.32%
0.16% *
0.08%
0.04%
0.02%
0.01%
Current
Draw
3.3 mA
3.5 mA
3.8 mA
4.6 mA *
5.0 mA
5.1 mA
5.2mA
7.0 mA
* Factory default setting.
iii
Front Panel DIP Switches
Switch
ON
OFF
Factory Default
1
Frequency
(See table in Frequency section)
OFF
2
OFF
3
Limited Presence
True Presence
TM
OFF
4
Sensitivity Boost
No Boost
OFF
5
Two Second Delay
No Delay
OFF
6
Fail-Safe Output A
Fail-Secure Output A
OFF
7
Exit Pulse Output B
Entry Pulse Output B
OFF
8
Presence Mode Output B
Pulse Mode Output B
OFF
Frequency (DIP Switches 1 and 2)
In situations where loop geometry forces loops to be located in close proximity to one another, it may be necessary
to select different frequencies for each loop to avoid loop interference, commonly known as crosstalk. DIP
switches 1 and 2 can be used to configure the detector to operate at one of four frequencies corresponding to
Low
,
Medium / Low
,
Medium / High
, and
High
as shown in the table below.
NOTE:
After changing any frequency DIP switch setting(s), the detector must be reset by momentarily changing
one of the other DIP switch positions.
Switch
Frequency
Low (0) Medium / Low (1) * Medium / High (2) High (3)
1
ON
OFF *
ON
OFF
2
ON
ON *
OFF
OFF
* Factory default setting.
Presence Hold Time (DIP Switch 3)
Output A always functions as a presence output. DIP switch 3 can be used to select one of two presence hold
times; Limited Presence or True Presence
TM
. Both modes provide a detect output when a vehicle is present
in the loop detection zone. True Presence
TM
is selected when DIP switch 3 is
OFF
. If DIP switch 3 is
ON
,
Limited Presence is selected. Limited Presence will typically hold the detect output for one to three hours. True
Presence
TM
will hold the detect output as long as the vehicle is present in the loop detection zone provided that
power is not interrupted, and the detector is not reset. TruePresence
TM
time applies only for normal size
automobiles and trucks and for normal size loops (approximately 12 ft
2
to 120 ft
2
). The factory default setting is
OFF
(True Presence
TM
Mode).
Sensitivity Boost (DIP Switch 4)
DIP switch 4 can be turned
ON
to increase sensitivity during the detect period without changing the sensitivity
during the no detect period. The boost feature has the effect of temporarily increasing the sensitivity setting by up
to two levels. When a vehicle enters the loop detection zone, the detector automatically boosts the sensitivity level.
As soon as no vehicle is detected, the detector immediately returns to the original sensitivity level. This feature is
particularly useful in preventing dropouts during the passage of high bed vehicles. The factory default setting is
OFF
(no Sensitivity Boost).
Output Delay (DIP Switch 5)
A two second delay of Outputs A and B can be activated by setting DIP switch 5 to the
ON
position. Output delay
is the time the detector outputs are delayed after a vehicle first enters the loop detection zone. If the two second
Output Delay feature is activated, the outputs will only be turned on after two seconds have passed with a vehicle
continuously present in the loop detection zone. If the vehicle leaves the loop detection zone during the two
second delay interval, detection is aborted and the next vehicle to enter the loop detection zone will initiate a new
full two second delay interval. The detector provides an indication that a vehicle is being detected but that the
outputs are being delayed, by flashing the front panel
DET
(Detect) LED at a four Hz rate with a 50% duty cycle.
The factory default setting is
OFF
(no Output Delay).
Fail-Safe / Fail-Secure (DIP Switch 6)
When DIP switch 6 is in the
ON
position, the detector will operate in Fail-Safe mode when a loop fault condition
exists. If a loop fault condition occurs while Fail-Safe mode is selected, Output A will activate (Relay A Normally
Open contacts closed, Relay A Normally Closed contacts open or Solid State Output A sourced to ground). When
DIP switch 6 is in the
OFF
position, the detector will operate in Fail-Secure mode when a loop fault condition
exists. If a loop fault condition occurs while Fail-Secure mode is selected, Output A will not activate (Relay A
Normally Open contacts open, Relay A Normally Closed contacts closed or Solid State Output A not sourced to