 2  

 3 

 

Front Panel DIP Switches 

Switch 

On 

Off

 

Factory Default 

Off 

See Table under Frequency Section 

Off 

Limited Presence 

True Presence 

Off 

4 Sensitivity 

Boost  No 

Boost 

Off 

2 Second Delay 

No Delay 

Off 

Fail Safe (Output A) 

Fail Secure (Output A) 

Off 

7 Exit 

Pulse 

Entry 

Pulse 

Off 

Presence Mode 

Pulse Mode 

Off 

 

Frequency (DIP switches 1 and 2) 

Switch 

Low 

Med. Low 

Med. High 

High 

1 On  Off  On  Off 
2 On  On  Off  Off 

 

Loop frequency is controlled by DIP switches 1 and 2 on the front panel.  Sometimes where 
loops are in close proximity, it is necessary to select a different frequency for each loop to 
avoid loop interference – commonly known as crosstalk.  Four frequencies are available as 
shown in the above table. High is the default frequency.

 

Limited Presence/True Presence (DIP switch 3) 

Output A is the presence output.  In Presence Mode, the detector has two presence hold times:  
Limited Presence and True Presence.  Both of these modes output a “Call”, i.e. vehicle 
detected, for as long as a vehicle is present in the loop detection area.  Limited Presence will 
typically hold the Call output for about one to three hours.  However, True Presence will hold 
the Call for as long as the vehicle is present and power is not removed or reset applied.  The 
True Presence time applies only for normal size automobiles and trucks and for normal size 
loops (approx. 12 ft

2

 – 120 ft

2

).

 

Sensitivity Boost (DIP Switch 4) 

DIP switch 4 can be turned ON to increase sensitivity only during the detect period without 
changing the sensitivity of a vacant loop.  When a vehicle enters the loop, the detector then 
automatically boosts the loop sensitivity but only during the detect condition.  As soon as no 
vehicle is detected, the detector immediately returns to the original sensitivity level.  This 
feature helps prevent dropouts during the passage of high-bed vehicles and is particularly 
useful in sliding gate situations.

 

Output Delay (DIP Switch 5) 

A 2 second delay of outputs A and B can be activated by setting DIP switch 5 to the ON 
position.  Output delay is the time the detector output is delayed after a vehicle first enters the 
loop detection area.  If the 2 second Output Delay feature is activated, the output relays will 
only be turned on after 2 seconds has passed with a vehicle continuously present in the loop 
detection area.  If a vehicle leaves the loop detection area during the 2 second delay interval, 
detection is aborted and the next vehicle to enter the loop detection area will initiate a new full 
2 second delay interval.  By flashing the front panel DET LED at 4 Hz with a 50% duty cycle, 
the detector indicates that a vehicle is being detected but that the output is being delayed.

 

 

Fail Safe/Fail Secure (DIP switch 6)

 

When in the ON position, the detector will operate in Fail Safe mode during a loop fault.  If a 
loop failure occurs while Fail Safe is activated, Output A activates. When in the OFF position, 
the detector will operate in Fail Secure mode during a loop fault.  If a loop failure occurs while 
Fail Secure is activated, Output A DOES NOT activate.  Factory default is Fail Secure.

 

Entry Pulse/Exit Pulse (DIP switch 7)

 

In Pulse Mode (with DIP switch 8 set to OFF), the detector can be programmed to output a 250 
millisecond pulse only upon vehicle entry over the loop or only upon vehicle exit from the loop. 
DIP switch 7 has no effect on output A (the presence output).

 

Presence/Pulse (DIP Switch 8)

 

Relay B has 2 modes of operation: Presence and Pulse.  When in Pulse mode (DIP switch 8 set 
to OFF), the 250 ms pulse can be set for entry pulse or exit pulse via DIP switch 7.  When in 
Presence mode, the presence hold time is the same as Output A. 

III. Reset 

Changing any DIP switch position (except 1 or 2) will reset the detector.  After changing the 
frequency selection switches, the detector will require a reset (a reset will clear the loop fault 
memory).

 

IV.  Failed Loop Diagnostics 

The FAIL LED indicates whether or not the loop is currently within tolerance.  If out of 
tolerance, the LED indicates whether the loop failed (1 flash per second) or had an intermittent 
loop failure (1 flash every 5 seconds). 

 

V. Pin 

Connections  (Harness Model 802-4) 

Pin 

Color 

Relay 

Solid State 

1 Black 

DC 

DC 

2 White 

DC 

DC 

Orange 

Relay B, Normally Open 

Output B, Open Drain 

4 Green 

No 

Connection 

No 

Connection 

Yellow 

Relay A, Common 

DC – 

Blue 

Relay A, Normally Open 

Output A, Open Drain 

7 Gray 

Loop 

Loop 

8 Brown 

Loop 

Loop 

Red 

Relay B, Common 

DC - 

10 

Violet or White/Black 

Relay A, Normally Closed 

No Connection 

11 

White/Green or White/Red 

Relay B, Normally Closed 

No Connection 

Note: All contacts shown above are with power applied, loops connected, and no vehicle 
present.  Output B always operates in Fail Secure mode when loop or power fails.

 

VI. Warnings

 

Separately for each loop, a twisted pair should be created consisting of only two (2) loop wires 
all the way from the loop to the detector (including through all wiring harnesses) at 
approximately six (6) full twists per foot. For trouble free operation, it is 

highly recommended

 

that all connections 

(including crimped connectors)

 be soldered.

 