background image

HE3XRT               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134773_005                      HE3XRTMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 6

Sound Attenuation

General Practices

Take these simple steps to attenuate noise from the unit.

Outside the building:

The exhaust hood is the primary source of noise outside the 

building. When practical, orient the exhaust air hood to point 

away from houses or public areas.

At the Curb:

Cut the holes in the roof deck to fit closely around the duct(s) 

passing through the roof deck. Seal all gaps around the duct(s) 

at the roof deck.

Ducts:

Make sure the ductwork at the unit outlets is stiff enough to 

resist the flexure and resulting booming associated with system 

start-up and shut-off, as well as the turbulent flow conditions at 

the blower outlets.

In general, provide smooth transitions from the ERV’s outlets to the 

duct. The ducts connecting to the outlets should be straight for a 

sufficient distance, with gradual transitions to the final duct size.

These guidelines are consistent with SMACNA recommended duct 

layout  practices  for  efficient  and  quiet  air  movement.  Follow 

SMACNA guidelines.

Radiated Noise

The HE3XRT is insulated with high-density fiberglass. This provides 

significant attenuation of radiated sound from the unit itself.

The  outlet  ducts  can  be  significant  sources  of  radiated  sound 

as well. The FA duct should be insulated for sound control. This 

insulation  should  start  at  the  unit. At  a  minimum  the  first  ten 

feet of duct should be insulated. All parts of the FA and RA ducts 

located in a mechanical space with noise-generating equipment 

also should be insulated for sound control, both to minimize 

sound radiation out of the FA duct, and also to control sound 

radiation into both ducts.

Aerodynamic (Velocity) Noise

When sound attenuation is a design concern, the primary 

consideration is velocity noise at the unit’s Fresh Air blower 

outlet.  The average velocity at the Fresh Air blower outlet is 

3470 FPM when the unit is operating at 3470 CFM.  The average 

velocity at the Exhaust Hood outlet is 3040 FPM when the unit is 

operating at 3070 CFM.

Danger of Electrical Shock when servicing an installed unit.

ALWAYS DISCONNECT POWER SOURCE BEFORE 

SERVICING! More than one disconnect switch may be 

required. 

Proper Wiring Size Selection and Wiring Installation 

are the Responsibility of the Electrical Contractor.

Before bringing power to the unit check unit nameplate 

to  confirm  it  matches  the  voltage  and  phase  of  the 

power you are supplying.
Remember  that  your  field  connections  need  to  be 

accessible for inspection.

Electrical Specifications

Electrical Options are identified on the Unit Label (located near 

electrical box). Find the complete Unit Model Number in the 

lower left corner of the Unit Label.

Содержание HE3XRTF

Страница 1: ...unit to the building 7 Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this e...

Страница 2: ...should be at least 10 away from any exhaust such as dryer vents chimneys furnace and water heater exhausts or other sources of contamination or carbon monoxide Do not locate the fresh air inlet where...

Страница 3: ...rformance of the HE3XRT Unit In most cases the job engineer will specify flow rates and ESP requirements The blower motors will also be specified to provide the required performance See unit specifica...

Страница 4: ...irectly measure airflow in the unit Energy Exchange Precise determination of installed sensible energy exchange effectiveness requires careful measurement of temperatures and air flows in all four air...

Страница 5: ...T CONTROL A STANDARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM...

Страница 6: ...und from the unit itself The outlet ducts can be significant sources of radiated sound as well The FA duct should be insulated for sound control This insulation should start at the unit At a minimum t...

Страница 7: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Страница 8: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Страница 9: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Страница 10: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Страница 11: ...put using the conversion chart NOTE Be sure to replace cap into pressure port when air flow measuring is completed ONLY RTH RTF RA OA FA RTV RTF ONLY RTV RTR ONLY RA RTH RTR FA ONLY FRONT VIEW E box P...

Страница 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Отзывы: