PLACEMENT OF THE HE1.5XRT
The HE1.5XRT is designed for installation on a roof or other outside location. Select a location that is
central to the inside duct runs, and close to any other air handler that might be part of the system.
PLANNING
YOUR INSTALLATION
INSTALLATION
86" Overall
5" Damper
Frames Typ.
CL 2 1/2" Control In
CL 5 5/8" Power In
42 7/8" Lift Lugs
OA
EA
RTV
ONLY
FA
RA
E-Box
Pressure
Ports (4) Typ.
Disconnect
Switch
(2) 7/8" holes for
wiring in bottom of
E-Box
FRONT VIEW
RTR
ONLY
FA
22 1/8" Wiring
3 5/8"
56 3/4" Overall
5 7/8"
CL 26 1/8"
Wiring
54" Case
FA (RTR)
Damper Location
(Optional)
EA Damper
Location
(Optional)
LEFT VIEW
FA (RTR)
18" X 18"
Duct Receiving
Flange
33 1/4"
Overall
1 7/8"
29 3/4"
Lift Lugs
RIGHT VIEW
45 3/4" Case
32 5/8" Case
10 1/8"
11 1/8"
32 1/4"
15 3/8"
55 5/8" Minimum
Service Area
24 3/4" Minimum Service
Area
FA (RTV)
14" x 16"
Opening
RA
Opening
14" x 16"
TOP VIEW
Door
Swing
Door
Swing
FA (RTV)
Damper Location
(Optional)
2 1/8"
1 1/8"
17 1/8" I.D.
17 1/8" I.D.
4 1/4"
1 7/8"
38 1/2" I.D.
42 1/4" O.D.
24 1/2"
I.D.
28 1/4" O.D.
A
A
FA
RA
TOP VIEW
CURB 1.5X
1 7/8"
3"
SECTION A-A
CURB CROSS-SECTION A-A (TYP.)
1 1/2" X 1/4"
Neoprene Gasket
3/4" X 3 1/2"
Wooden Nailer
Model: HE1.5X RTV/RTR
Drawing Type: Unit Dimension
Version: MAY18
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
RTV: Rooftop Vertical RA & FA
RTR: Rooftop Vertical RA Only
INSTALLATION ORIENTATION
Unit must be installed in orientation
shown.
NOTE:
1. UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE ROUNDED TO THE
NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT
TO CHANGE WITHOUT NOTICE.
F1
It is the installer’s responsibility to make sure that
the screws or bolts used for securing the units
are properly selected for the loads and substrates
involved. Secure the HE1.5XRT so that it cannot fall
or tip in the event of accident, structural failure or
earthquake. See Rigging Information for unit weight.
RenewAire strongly recommends that you secure
rooftop units properly to the building structure.
Strong winds, tornados, and hurricanes can and do
displace or remove rooftop equipment from rails or
curbs. When this happens, the equipment, adjacent
roof structure, and even vehicles parked near the
building can be damaged, and rain typically enters the
building. The equipment is put out of service and the
collateral damage can be very expensive.
Provide Adequate Service Access for Maintenance. The HE1.5XRT will require regular filter and core
inspections. Install the HE1.5XRT where you can open the doors for cleaning the core and replacing the
filters, and where you can get at the wiring for installation and service. Observe all safety precautions when
working on roofs, including locating the unit away from roof edges, provision of safety railings and use of fall
protection equipment.
CAUTION
CAUTION
Provide service access to the unit to allow for cleaning the core and filter.