INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

WWW.RENEWAIRE.COM 

FIELD CONVERSION

FIELD CONVERSION OF OPENINGS

The HE1.5-RT is designed to allow field conver-
sion of the Return Air (RA) and Fresh Air (FA) unit 
openings. This means the RA motorized impeller 
subassembly can be moved to an adjacent side or 
base of the unit if that opening is preferred.  The 
FA outlet opening can also be moved to an adja-
cent wall or base.
 

 
Before you start, plan the duct work layout.  
Determine which openings are to be converted.
- Turn off the disconnect switch on the unit.   
 

Make sure electrical power is shut off to  

  the unit and disconnect switch.

- Open the access doors to the unit.
- Remove the core strap, filters, and energy  
  exchanger cores from the unit.

TO FIELD CONVERT INLET OPENING

1.  Disconnect motor harness connector by the  

motor. Move the wire harness out of the way if 
necessary.

2.   Support the impeller subassembly.  Remove the  

eight ¼-20 bolts retaining the impeller 
subassembly  plate to the side rails and front 
and back tabs.

3.  

Lift the entire impeller subassembly out of 
the unit and set aside.  Leave the rails in  
the unit.

4.  Remove the patch pan from the desired opening. 
  Note:  The RA patch pan may be on the underside  
 

of the base pan.  Safely access the underside of the  

  unit to remove the patch pan.
5.  Using the exposed sheet metal cutout, cut the  
  insulation from the desired opening.
6.  Seal the edges of the cut insulation to prevent  
 

erosion of the insulation edges and having debris in  

  the air stream.
7.  Install the patch pan over the undesired opening. 
  Note:  The RA patch pan may be installed on  
  the underside of the base pan.  Safely access the  
  underside of the unit to install the patch pan.
8.  Install the insulation in the undesired opening.  Seal  
  the insulation.
9.  At this point, if the Fresh Air (FA) outlet opening  
  is to be converted, you will want to address it  
  before proceeding with the RA inlet opening.
10. After converting the FA outlet opening proceed  
  with the RA inlet opening.
11. Install the impeller subassembly into the new inlet  
  opening and fasten with eight ¼-20 bolts to retain  
  to the side rails and front and back tabs.  Make  
  sure the motor harness connector is towards the  
  front of the unit.
12. Connect the motor harness.
13. Tidy up any wire harnesses that were moved  
  making sure motor wires are taut and away from  
  the impeller blades.

TO FIELD CONVERT OUTLET OPENING

1.  Remove the patch pan from the desired opening.
  Note:  The FA patch pan may be on the underside 

of the base pan.  Safely access the underside of 
the unit to remove the patch pan.

2. Using the exposed sheet metal cutout, cut the 

insulation from the desired opening.

3. Seal the edges of the cut insulation to prevent 

erosion of the insulation edges and having debris 
in the air stream.

4. Install the patch pan over the undesired opening.
  Note:  The FA patch pan may be installed on the 

underside of the base pan.  Safely access the 
underside of the unit to install the patch pan.

5. Install the insulation in the undesired opening.  

Seal the insulation.

6. If the RA Inlet Opening is being converted return 

to Step 10 in the “To Field Convert Return Air 
(RA) Inlet Opening” instructions.

After completion of the field conversion,
-  Clean out the interior of the unit to remove any debris.
-  Install energy exchanger cores, filters, and core strap.

www.renewaire.com     (800) 627- 4499 

[email protected]

INSTALLATION

Содержание HE1.5XRT

Страница 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR HE1 5XRT WWW RENEWAIRE COM MODEL HE1 5XRT...

Страница 2: ...NG The unit s fresh air inlet should be at least 10 away from any exhaust such as dryer vents chimneys furnace and water heater exhausts or other sources of contamination or carbon monoxide Do not loc...

Страница 3: ...Voltage Codes 4 8 only available with Phase Code 3 Three Phase 3 Motor Codes EE EC Motors only available with Phase Code 1 Single Phase 4 Unit Control Code G Terminal Strip only available with Motor C...

Страница 4: ...t MC W Carbon dioxide control wall mount CO2 W duct mount CO2 D Electric duct heater EK series 1 60 kW designed for indoor ductwork installation only Indirect gas fired duct furnace GH series 50 400 M...

Страница 5: ...Roof Curb HE1 5XRTR Room Air RA enters bottom of unit Fresh Air FA exits side of unit Roof Curb HE1 5XRTF Room Air RA enters side of unit Fresh Air FA exits bottom of unit Roof Curb HE1 5XRTH Room Air...

Страница 6: ...IEW Door Swing Door Swing FA RTV Damper Location Optional 2 1 8 1 1 8 17 1 8 I D 17 1 8 I D 4 1 4 1 7 8 38 1 2 I D 42 1 4 O D 24 1 2 I D 28 1 4 O D A A FA RA TOP VIEW CURB 1 5X 1 7 8 3 SECTION A A CUR...

Страница 7: ...l 2 1 8 1 1 8 17 1 8 I D 17 1 8 I D 4 1 4 1 7 8 38 1 2 I D 42 1 4 O D 24 1 2 I D 28 1 4 O D A A FA RA TOP VIEW CURB 1 5X 1 7 8 3 SECTION A A CURB CROSS SECTION A A TYP 1 1 2 X 1 4 Neoprene Gasket 3 4...

Страница 8: ...5X RTV RTR Drawing Type Unit Dimension Version MAY18 ABBREV EA Exh OA Ou RA Roo FA Fres RTV Ro RTR Ro INSTALL Unit mu shown NOTE 1 UNLE DIMENS NEARES 2 SPEC TO CHA F1 It is the installer s responsibi...

Страница 9: ...t Use slings or shackles at all four corners Spreader bars are recommended in order to avoid damage to the unit CURB SPECIFICATIONS F2 INSTALLATION HE1 5XRT UNIT CORNER WEIGHTS LBS SINGLE WALL PHASE U...

Страница 10: ...ep drywall spray construction dust etc out of unit CAUTION 1 Before servicing or cleaning the unit switch power off at disconnect switch or service panel and lockout tag out to prevent power from bein...

Страница 11: ...an may be installed on the underside of the base pan Safely access the underside of the unit to install the patch pan 8 Installtheinsulationintheundesiredopening Seal the insulation 9 At this point if...

Страница 12: ...rs to Set and Balance Airflow Rates In most applications the airflow rate for both the Fresh Air and the Exhaust Air should be roughly equal or balanced for best performance of the HE1 5XRT Unit See u...

Страница 13: ...the bottom of the HE1 5XRT are generally installed at this time Install 2 ducts with HE1 5XRTV 1 duct with HE1 5XRTR or RTF Drop duct s into openings in top of roof curb Install appropriate gasket on...

Страница 14: ...Supply with an External Power Supply NOT AVAILABLE IN EVERY UNIT DOOR INTERLOCK SWITCH This wire omitted with single phase power supply These wires omitted with single phase power supply TRANSFORMER w...

Страница 15: ...OT interconnect this unit s Class 2 Power Supply with an External Power Supply NOT AVAILABLE IN EVERY UNIT DOOR INTERLOCK SWITCH This wire omitted with single phase power supply These wires omitted wi...

Страница 16: ...Trip Point 3A 1 Connect only to components intended for use with 24VAC power 2 Do not undersize the low voltage wires connected to this device Observe the wire length and gauge limits indicated in th...

Страница 17: ...ndependent Blower Control Only Use this schematic if the external control system provides no voltage or current at its output contacts Install jumper provided between terminals 2 3 Connect one side of...

Страница 18: ...ally Open N O contacts to terminals 1 4 NOTE See Wiring Schematics G Control System on separate Power Supply Independent Blower Control Use this schematic only if no power is present at the controls o...

Страница 19: ...ity These may include timer clocks occupancy sensors dehumidistats for cool weather operation carbon dioxide sen sors and others DDC systems may also control the unit Most control schemes will operate...

Страница 20: ...uring device to the Outside Air OA port and the low pressure side to the Fresh Air FA port To read SCFM of Room Air RA install the high pressure side of your measuring device to the Room Air RA port a...

Страница 21: ...30 0 40 400 600 800 1000 1200 1400 1600 Clean filter Pressure Drop in w g Unit Airflow CFM Initial Pressure Drop of Optional MERV 13 Filters available for this unit V15 xlsx 14 16x20x2 MERV 8 IOM 0 0...

Страница 22: ...ERV HE1 5XRT WWW RENEWAIRE COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 22 MAINTENANCE SERVICE PARTS HE1 5XRT www renewaire com 800 627 4499 support renewaire com...

Страница 23: ...the unit are usually able to keep the energy exchange core clear for several months Finer filters can be used but must be cleaned more often If using finer filters their increased resistance to flow...

Страница 24: ...pital costs by reducing HVAC loads and decreases operational expenses by downsizing equipment resulting in major energy and cost savings RenewAire technologies also enjoy the industry s best warranty...

Отзывы: