1.800.627.4499
4
RENEWAIRE.COM
1.800.627.4499
4
SPECIFICATIONS & DIMENSIONS
Specifi cations may be subject to change without notice.
INDOOR UNIT
SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airfl ow Range:
200-540 CFM
AHRI 1060 Certifi ed Core:
One L85-G5
Standard Features:
Non-fused disconnect
24 VAC transformer/relay package
Cross-core differential pressure ports
Filters:
Total qty. 2, MERV 8: 14" x 20" x 2"
Unit Dimensions & Weight:
54 1/2" L x 16 3/8" W x 36 3/4" H
137-199 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet):
62" L x 42" W x 22" H
250 lbs.
Motor(s), choice of:
Qty. 1, 0.6 HP (standard single phase)
Qty. 1, 0.5 HP (standard three phase)
Options:
Qty. 1, Variable Speed/ECM - Direct Drive Motors
(see EV450IN EC Motor submittal) -
0.5 HP, 120V/1Ph/60HZ,
0.5 HP, 208-230V/1Ph/60HZ
Fused disconnect
Integrated programmable controls -
enhanced, premium
Qty. 2, Factory mounted fi lter alarms -
both airstreams
Double wall construction
Exterior paint - white, custom colors
Accessories:
Filters - MERV 13, 2
"
(shipped loose)
Backdraft damper 10
"
Wall cap 10
"
- galvanized, paintable galvanneal
Vibration isolation kit
Hanging bracket kit
Transition kit 10
"
- round, qty. 2
Flange kit - rectangular 12
"
x 8
"
, 2 fl anges
Solid state speed control kit - 115V, qty. 1,
208-230V, qty. 1
Digital time clock - wall mount (TC7D-W),
in exterior enclosure (TC7D-E)
Carbon dioxide sensor/control -
wall mount (CO2-W), duct mount (CO2-D)
IAQ sensor - wall mount (IAQ-W),
duct mount (IAQ-D)
Motion occupancy sensor/control -
ceiling mount (MC-C), wall mount (MC-W)
Smoke detector - duct mount (SD-D)
Louver with 10
"
round duct connection -
12
"
(W) x 12
"
(H)
Electric duct heater - RH series (1-11.5 kW);
EK series (1–175 kW);
designed for indoor ductwork installation only
HP
Volts
HZ Phase
FLA
Min.
Cir.
Amps
Max.
Overcurrent
Protection
Device
0.6
120
60 Single
7.2
9.0
15
0.6 208-230 60 Single 3.9-3.6
4.9
15
0.6
277
60 Single
3.5
4.4
15
0.5 208-230 60
Three 1.7-1.5
2.1
15
0.5
460
60
Three
0.8
1.0
15
UNIT PERFORMANCE
Airfl ow CFM
ESP in H
2
0
Watts
1P 3P
225
1.25
335
181
375
0.89
464
333
420
0.75
518
394
480
0.50
584
472
500
0.43
600
491
540
0.25
640
540
575
0.00
690
610
ELECTRICAL DATA
Note:
Watts is for the entire unit.
Note:
Airfl ow performance includes effect of clean, standard fi lter supplied with unit.
450
IN
EV
Energy Recovery Ventilator
Standard
Download specification at:
renewaire.com/specifications
Note:
Indirect Gas-Fired Duct Furnace is not available on the EV450IN.
Specifications may be subject
to change without notice.